Download Print this page
Honeywell VP522A Quick Start Manual

Honeywell VP522A Quick Start Manual

Sequencing water valve

Advertisement

Quick Links

GENERAL
Description
VP522 Sequencing Water Valves are pneumatically actuated,
three-pipe water valves that control both hot and cold water
flow to fan coil units in three- and four-pipe systems.
C O N T R O L
A I R
CH I LLEO +
W A T E R
H O T +
W A T E R
Copyright 0 1992 Honeywell Inc.
Sequencing Water Valve
VP522A
V A L V E
C O I L
Fig. 1. VP522A, B Typical Application.
All Rights Reserved
l
Application
The VP522A controls the flow of hot or cold water to a fan coil
unit from the hot or chilled water supply piping.
The VP5226 is used in conjunction with the VP522A as a
diverting, return-water valve on four-pipe systems to ensure
isolation of the hot and chilled water circuits.
Operation
The VP522A (Fig. 1) is a proportioning valve that controls the
flow of first hot and then cold water to a fan coil unit as
branchline pressure increases and the reverse as branchline
pressure decreases. No flow occurs at mid-pressure. See
Table 1 for operating sequence.
The VP522B diverts the return water from the coil directly to
return piping of the system feeding the coil. During the dwell
period of the VP522A, when both ports are closed but the
valve is moving towards opening either the hot or cold port,
the VP522B is actuated to open the proper port before the
VP522A allows water to flow.
VP5220B
Honeywell
VP522A, B
A I R
V A L V E
T O
To
B O I L E R
75-2598

Advertisement

loading

Summary of Contents for Honeywell VP522A

  • Page 1 VP522A, B Sequencing Water Valve Application The VP522A controls the flow of hot or cold water to a fan coil unit from the hot or chilled water supply piping. The VP5226 is used in conjunction with the VP522A as a diverting, return-water valve on four-pipe systems to ensure isolation of the hot and chilled water circuits.
  • Page 2 VP522A, B SEQUENCING WATER VALVE Table 1. VP522A, B Operating Sequence on Control Air Pressure increase. 3/8 in 1/2 & 3/4 in. psi (kPa) Hot port open 100% 3 (21) 4 (28) Hot port closes 5 (34) Hot port closes...
  • Page 3: Maintenance

    There should be no flow at mid-pressure (see Table 1). Seats: Brass, upper seat removable, lower seat integral Adjustment Plugs: Brass Make the following adjustments after repairing the VP522A or B. Disc: Molded-in composition Operator Diaphragm: movement (dwell) occurs. Molded neoprene, rolling type Repeat above procedure for the VP522B.
  • Page 4: Troubleshooting

    TROUBLESHOOTING For troubleshooting the VP522A or B, see Figure 2. CHECK ACTUATOR REPACK VALVE AND INSPECT INTERNAL PARTS. REPLACE BENT, BROKEN, OR WORN PARTS RESTORE VALVE/SYSTEM TO OPERATION REPLACE DIAPHRAGM. MAKE OPERATIONAL CHECK. CHECK DISASSEMBLE VALVE AND DISASSEMBLE VALVE. SYSTEM...
  • Page 5 REPAIR near the top of the stem for insertion of an awl, nail, or similar tool to hold the stem while removing or replacing the stem button. Equipment Required Remove packing nut. Remove packing discs (3) and packing followers from packing nut.
  • Page 6: Parts And Accessories

    VP522A1005 313824A the top of the stem button to the top of the valve bonnet VP522A1039 314459A is 3-15/1 6 in. (100 mm) for the VP522A, or 4-1/1 6 in. VP522A1047 3144598 (103 mm) for the VP522B. VP522A1070...