V8043 Zone Valves
with Press Connection
Model
Pipe Size
V8043A1311/U
V8043A1312/U
V8043A1313/U
V8043E1411/U
V8043E1412/U
V8043E1413/U
V8043F1511/U
V8043F1512/U
V8043F1513/U
APPLICATION
These valves consist of an actuator motor and valve
assembly for controlling the flow of hot and/or cold
water. The V8043A provides two-position, straight-
through control of supply water. The valves are
designed for use with fan coil and other units
requiring quiet, compact water valves. The V8043E
and V8043F also control supply water for baseboard
radiators and convectors.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to
follow them could damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and
on the product to make sure the product is
suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
DN15
1/2" Zone Valve Pro Press with 18" lead wires
DN20
3/4" Zone Valve Pro Press with 18" lead wire
DN25
1" Zone Valve Pro Press with 18" lead wires
DN15
1/2" Zone Valve Pro Press with 18" lead wires and End Switch
DN20
3/4" Zone Valve Pro Press with 18" lead wires and End Switch
DN25
1" Zone Valve Pro Press with 18" lead wires and End Switch
DN15
1/2" Zone Valve Pro Press with Terminal Block Connections and End Switch
DN20
3/4" Zone Valve Pro Press with Terminal Block Connections and End Switch
DN25
1" Zone Valve Pro Press with Terminal Block Connections and End Switch
INSTALLATION INSTRUCTIONS
Description
CAUTION
1. Disconnect power supply before connecting
wiring to prevent electrical shock of
equipment damage.
2. Normally it is not necessary to remove the
powerhead from the valve body during
installation. If the valve must be disassembled,
be certain that it is reassembled with the water
flow in the direction of the arrow. Reversal of
the powerhead will result in damage to the
gear train.
3. On 24V systems, never jumper the valve coil
terminals even temporarily. This may burn
out the heat anticipator in the thermostat.
IMPORTANT
Use this valve in hydronic heating systems
which do not contain dissolved oxygen in the
system water. The dissolved oxygen, which is
found in systems that have a frequent source
of makeup water, causes the rubber plug inside
the valve to deteriorate and eventually fail.
LOCATION
Install the valve in an area with adequate clearance to:
move the manual opening lever on the side of
the powerhead;
remove the powerhead cover;
wire the powerhead;
replace the powerhead motor.
The valve location should be in an area where the
temperature does not exceed the maximum valve
operating temperature as shown in Specifications.
33-00402EF-01

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell V8043A1312/U

  • Page 1 INSTALLATION INSTRUCTIONS Model Pipe Size Description V8043A1311/U DN15 1/2" Zone Valve Pro Press with 18" lead wires V8043A1312/U DN20 3/4" Zone Valve Pro Press with 18" lead wire V8043A1313/U DN25 1" Zone Valve Pro Press with 18" lead wires V8043E1411/U DN15 1/2"...
  • Page 2: Specifications

    Auxiliary Switch Ratings: Ambient: 4 to 52 °C (40 to 125 °F). ‘E’, ‘F’ Models: 4.4 Amps running at 120 Vac. Steam: Consult your local Honeywell representative. Recommended Wall Thermostats: Humidity Rating: 5-95% RH (non-condensing) Heating Only - T86A, T822D: Atmosphere: non-corrosive, non-explosive (T822C for normally open [N.O.] valves).
  • Page 3 V8043 ZONE VALVES WITH PRESS CONNECTION MOUNTING 3. Check seal for correct fit. Do not use oils or lubricants. 4. Mark proper insertion depth as shown in Table 2. The valve can be mounted in any position on a vertical Improper insertion depth may result in improper line.
  • Page 4: Operation And Checkout

    TRADELINE® Catalog. Fig. 7 (left). When the powerhead is de-energized, a spring-return mechanism drives the valve to the NOTE: Honeywell zone valves are designed and closed position as shown in Fig. 7 (right). The valve tested for silent operation in properly can also be opened with no electrical power by designed and installed systems.
  • Page 5: Notice D'installation

    V8043A1311/U DN15 Vanne de commande de zone ½ po Pro Press avec fils de raccordement de 18 po (457 mm) V8043A1312/U DN20 Vanne de commande de zone ¾ po Pro Press avec fils de raccordement de 18 po (457 mm)
  • Page 6: Spécifications

    Thermostats Muraux Recommandés: Ambiantes: 4 à 52 °C [40 à 125 °F] Chauffage seulement -T86A, T822D (T822C pour Vapeur: Consulter un représentant Honeywell vannes normalement ouvertes [NO].) Refroidissement seulement ou chauffage- Condition d'humidité:5-95% HR (sans condensation) refroidissement -T87F avec Q539.
  • Page 7: Montage

    V8043 VANNES DE COMMANDE DE ZONE À RACCORDS À COMPRESSION MONTAGE 5. Faire glisser le raccord à compression sur le tube en le tournant légèrement jusqu’à atteindre la La vanne peut être montée dans n'importe quelle marque de profondeur. position sur une ligne verticale. Si la vanne est montée REMARQUE : L’extrémité...
  • Page 8: Fonctionnement Et Vérification

    Lorsque la tête motrice est désactivée, un mécanisme de ressort de rappel ferme la vanne comme illustré REMARQUE : Les vannes de zone Honeywell sont sur la Fig. 7 (droite). La vanne peut aussi être ouverte conçues et testées pour un sans alimentation électrique en déplacement le levier...

Table of Contents