Power Management
PML630/Compact Load-Shedding Solution
Product version: 1.2.1
However, the total performance of end-to-end performance of
the cPMS load-shedding solution configuration A depends on
various factors.
• HW binary input and output activation times in feeder
protection relays
• GOOSE transmission times between the protection relays
(maximum ~10 ms for Relion 615, 620, and 630 series)
• Application function cycle times in the feeder protection
relays
• PML630 device load-shedding logic execution time
• External trip contact operation time
The end-to-end performance of the configuration A is achieved
[1]
within 60 ms
. In case of Configuration B, the load-shedding
action in power network area 2 due to a contingency in power
network area 1 is achieved within 90 ms
circuit breaker opening time, the overall performance times can
REF615
GUID-7162B4C9-E619-4940-9E24-76C0FB36200E V1 EN
Figure 8.
cPMS load-shedding Configuration A: PRP configuration
[1]
This figure is conservative and is subject to substation communication network traffic conditions.
20
[1]
. Depending on the
COM600
Ethernet switch
IEC 61850 PRP
REF620
be ascertained. When the load feeder circuit is based on ABB
MV circuit breaker, the open time is about 50 ms.

17. Redundancy

The 630 series family does not support communication or
device-level redundancy. To adapt the PML630 to work in a
redundant communication network with other redundant
devices such as 615 and 620 series, an external redundancy
box is needed. With such unit, PML630 can be used in a
network supporting High Availability Seamless Redundancy
(HSR) or Parallel Redundancy Protocol (PRP).
A 100% redundant and independent PML630 device with
identical configuration to the main PML630 device can work
together to achieve load-shedding device-level redundancy.
For additional information, contact ABB DA-Supportline.
PML630
Redundancy
Box
RET620
1MRS757334 E
Ethernet switch
REM620
REF615
ABB