INSTALLATION AND MAINTENANCE INSTRUCTIONS
SK-Zone-6
Six Zone Interface Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Max. IDC Wiring Resistance:
External Power Supply Voltage:
Ripple Voltage:
IDC (supervised and power limited)
DC Voltage:
Frequency:
Alarm Current:
Standby Current 6 circuits:
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Zone-6 Six Zone Interface Module is intended for use in an intelli-
gent alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(5) 1 x 4 Terminal Blocks
(2) 1.25" Stand offs
(4) Machine Screws
(2) Nuts
(6) 3.9k Ohm End of Line Resistors
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
15-32 VDC
2.3 mA @ 24 V
40 mA (assumes all six LEDs solid on)
32ºF to 120ºF ( 0ºC to 49ºC)
10 to 93% Non-condensing
6.8˝ H x 5.8˝ W x 1.0˝ D
IDP-ACB Cabinet and chassis
12-18 AWG
25 Ohms
Regulated 24 VDC
0.1 volts RMS maximum
18-28 volts power limited
DC
90mA per circuit
42mA Maximum @18 VDC
56mA Maximum @24 VDC
66mA Maximum @28VDC
(3) Shunts
(1) Long Power Supply Jumper
C0202-00
12 Clintonville Road, Northford, CT 06472-1610
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
A list of compatible two-wire System Sensor Smoke detectors for use with the
SK-Zone-6 is available on the System Sensor website at systemsensor.com.
COMPONENTS
The following is a description of the SK-Zone-6 mounting framework:
• One or two SK-Zone-6 modules can be installed in an IDP-ACB cabinet
FIGURE 1. IDP-ACB CABINET
The IDP-ACB cabinet has a built-in chassis that will accommodate one or two
SK-Zone-6 modules. For cabinet dimensions refer to the IDP-ACB instruction
manual.
The front SK-Zone-6 module positions of each chassis are offset below the
rear SK-Zone-6 module positions so that all of the status indicators are visible.
INSTALLATION STEPS
1.
Cabinet Mounting
• In a clean, dry area, mount the backbox using the four holes provided
in the back surface of the cabinet (Figure 2).
1
Phone: 203-484-7161 Fax: 203-484-7118
www.silentknight.com
C0234-05
I56-3441-007
7/1/2022

Advertisement

loading

Summary of Contents for Honeywell SILENT KNIGHT SK-Zone-6

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS SK-Zone-6 12 Clintonville Road, Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 Six Zone Interface Module www.silentknight.com SPECIFICATIONS Normal Operating Voltage: 15-32 VDC Stand-By Current: 2.3 mA @ 24 V Alarm Current: 40 mA (assumes all six LEDs solid on) Temperature Range: 32ºF to 120ºF ( 0ºC to 49ºC) Humidity:...
  • Page 2 FIGURE 2. TYPICAL MOUNTING HOLE LOCATIONS FIGURE 4B. INSTALLATION OF SK-ZONE-6 MODULE IN FRONT CHASSIS POSITION BACKBOX MOUNTING HOLES C0235-00 Module Installation There are two methods for installing a module in the rear position of a chas- sis. Method one is for installation of a rear module only, when no module will be installed in front of it.
  • Page 3 FIGURE 5. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B CONNECT MODULES TO 1. To use a common power supply LISTED COMPATIBLE BASE ADDRESS SILENT KNIGHT CONTROL between multiple SK-Zone-6 mod- 6 7 8 9 6 7 8 9 PANELS ONLY ules, connect a long power sup- ply jumper from T5 or T6 to T5 or T6 on the adjacent SK-Zone-6...
  • Page 4 – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. Silent Knight ® , System Sensor ® , and Honeywell ® are registered trademarks of Honeywell International, Inc. I56-3441-007 ©2022 Honeywell. 7/1/2022...