Download Print this page

Accessory - Omega OTEC ERVD Series Service Manual

Energy recovery ventilator

Advertisement

9. Accessory

Name
Installation and owner's manual
Butt-joint wire of wire control display panel
(6 meters)
HRV wire controller
Annex 1
Resistance KΩ
Temp.℃
-10
62.2756
-9
58.7079
-8
56.3694
-7
52.2438
-6
49.3161
-5
46.5725
-4
-3
41.5878
-2
39.8239
-1
37.1988
0
35.2024
1
33.3269
2
31.5635
3
29.9058
4
28.3459
5
26.8778
6
25.4954
7
24.1932
8
22.5662
9
21.8094
10
20.7184
11
19.6891
12
18.7177
13
17.8005
14
16.9341
15
16.1156
16
15.3418
Quantity
Temp.℃
17
18
19
20
21
22
44
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
shape
1
1
1
Resistance KΩ
14.6181
13.918
13.2631
12.6431
12.0561
11.5
10.9731
10.4736
10
9.5507
9.1245
8.7198
8.3357
7.9708
7.6241
7.2946
6.9814
6.6835
6.4002
6.1306
5.8736
5.6296
5.3969
5.1752
4.9639
4.7625
4.5705
Purpose
must be delivered to the customer
For connect wire control and display control box
For controlling HRV units
Characteristic of temperature sensor
Temp.℃
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
Resistance KΩ
4.3874
4.2126
4.0459
3.8867
3.7348
3.5896
3.451
3.3185
3.1918
3.0707
2.959
2.8442
2.7382
2.6368
2.5397
2.4468
2.3577
2.2725
2.1907
2.1124
2.0373
1.9653
1.8963
1.830
1.7665
1.7055
1.6469

Advertisement