Remote fire annunciator
Table of Contents

Advertisement

LCD-80F Annunciator
.
Figure 1-4:
DIP Switch Settings Example
switch 1 shown in
ON position
Note: SW1 DIP switch settings as illustrated in Figure 1-3 are as
follows:
1. DIP switch 1: ON = Key-switch disabled (membrane function
switches are always enabled with key-switch having no affect on
their function).
2. DIP switch 2: OFF = piezo sounder disabled (requires approval
of LAHJ)
3. DIP switch 3: OFF = Receive Only. This setting is used for all
annunciators except the last or only LCD-80F Annunciator on
the EIA-485 line
4. DIP switches 4 through 6: OFF = Configured correctly for
operation with the available FACP
5. DIP switches 7 and 8: OFF (these switches are not used)
Document 51338 Rev. B 08/24/05 P/N 51338:B
SW1 DIP Switch Settings
switches 2 through 8
shown in Off position