Honeywell MultiPRO TB7100A1000/U Manual page 13

Multispeed and multipurpose thermostat for conventional, heat pump, fan coil and ptac systems

Advertisement

Installer
Setup
Installer Setup
Number
Name
0310
Deadband
0320
Temperature
Indication Scale
0330
Daylight Saving
0340
Remote Temp
Sensor/Remote
Setback/
Changeover Input
0340
Remote Temp
(Non-
Sensor/Remote
program
Setback/
mable)
Changeover Input
0342
Override Option
(only available in
non-programmable
mode)
0343
Unoccupied
Heating Setpoint
(only when remote
setback enabled)
0346
Unoccupied
Cooling Setpoint
(only when remote
setback is enabled)
0347
Fan Ramping
0348
Fan Mode
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 6. Installer Setup Menu. (Continued)
Default
Setting
All Settings
3°F
2 (1.5)—2°F (1.5°C)
(2°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
0
0—°F
1—°C
1
0—Disabled
1—Enabled (US)
0
0—None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe Fan Coil
modes only
4—Changeover 2 pipe Fan Coil
modes only
0
0—None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe Fan Coil
modes only
4—Changeover 2 pipe Fan Coil
modes only
5—Remote Setback
6—Remote Setback
0
0—No Override
1—Override
60°F
50-65°F
10-18°C
80°F
75-90°F
24-30°C
1
0—Disabled (Lo, Med, Hi)
1—Enabled
0
0—User can choose Cycle or
Constant 3 speed: Low->Med->
High->Auto-> Low
1—Cycle Only - Auto only
Only shown if Automatic Changeover selected (ISU
0300).
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
Hotel card NO, with 1 second software delay going
from UnOcc to Occupied; 2 minute delay going from
Occupied to UnOcc.
Hotel Card NC, with 1 second software delay going
from UnOcc to Occupied; 2 minute delay going from
Occupied to UnOcc.
This option is only available for non-programmable
mode (ISU #160)
To enable the fan ramping algorithm. Only available
for fan coil or PTAC applications (ISU #170)
To select a particular fan mode: Auto is the fan ramp
mode. If ramping is not selected, fan mode
automatically defaults to Low Med High (Constant
only) and ISU 0348 is unavailable. Only available for
fan coil or PTAC applications (ISU #170)
13