INSTALLATION AND MAINTENANCE INSTRUCTIONS
Velociti
Series
®
AOM-2SF Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
Maximum NAC Line Loss:
External Supply Voltage (between Terminals T10 and T11)
Maximum (NAC):
Maximum (Speakers):
Drain on External Supply:
Temperature Range:
Humidity:
Dimensions:
Accessories:
RELAY CONTACT RATINGS:
CURRENT RATING
2 A
3 A
2 A
0.46 A
0.7 A
0.9 A
0.5 A
0.3 A
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
AOM-2SF Supervised Control Modules are intended for use in intelligent, two-
wire systems, where the individual address of each module is selected us-
ing the built-in rotary switches. This module is used to switch an external
power supply, which can be a DC power supply or an audio amplifier (up
to 80 VRMS), to notification appliances. It also supervises the wiring to the
connected loads and reports their status to the panel as NORMAL, OPEN, or
SHORT CIRCUIT. The AOM-2SF has two pairs of output termination points
available for fault-tolerant wiring and a panel-controlled LED indicator.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Gamewell-FCI system control panels only (list available from Gamewell-FCI).
MOUNTING
The AOM-2SF mounts directly to 4-inch square electrical boxes (see Figure
2A). The box must have a minimum depth of 2
electrical boxes (SMB500) are available. The module can also mount to the
DNR(W) housing.
15 to 32 VDC
6.5 mA (LED on)
375µA (LED flashing - in Velociti Mode); 350µA (LED flashing - in CLIP mode)
4 VDC
Regulated 24 VDC
70.7 V RMs, 50W
1.7 mA Maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply
32°F to 120°F (0°C to 49°C)
10% to 93% Non-condensing
4.675" H x 4.275" W x 1.4" D (Mounts to a 4˝ square by 2
SMB500 Electrical Box; CB500 Barrier
MAXIMUM VOLTAGE
25 VAC
30 VDC
30 VDC
30 VDC
70.7 VAC
125 VDC
125 VAC
125 VAC
1
/
inches. Surface mounted
8
1
/
˝ deep box.)
8
LOAD DESCRIPTION
PF = 0.35
Resistive
Resistive
(L/R = 20ms)
PF = 0.35
Resistive
PF = 0.75
PF = 0.35
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
CB500 Module Barrier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and wiring. The barrier
must be inserted into a 4˝ × 4˝ × 2
must be placed into the barrier and attached to the junction box (Figure 2A).
The power-limited wiring must be placed into the isolated quadrant of the
module barrier (Figure 2B).
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box (supplied by installer), see Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length
is
1
/
" to
3
/
"). Exposed conductor should be secured under the clamping plate
4
8
and should not protrude beyond the terminal block area. Caution: Do not loop
wire under terminals. Break wire run to provide supervision of connections.
IMPORTANT: When using the AOM-2SF for audio applications, remove Jumper
(J1) and discard. The Jumper is located on the back as shown in Figure 1B. J1
must be removed whenever power supply monitoring feature is not required.
NOTE: All references to power limited represent "Power Limited (Class 2)".
All references to Class A also include Class X.
1
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161; Fax: 203.484.7118
www.gamewell-fci.com
APPLICATION
Non-coded
Non-coded
Coded
Non-coded
Non-coded
Non-coded
Non-coded
Non-coded
1
/
˝ junction box, and the control module
8
I56-3550-008
06/19/2018

Advertisement

loading

Summary of Contents for Honeywell Gamewell FCI Velociti Series

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS Velociti Series ® 12 Clintonville Road Northford, CT 06472-1653 AOM-2SF Supervised Control Module Phone: 203.484.7161; Fax: 203.484.7118 www.gamewell-fci.com SPECIFICATIONS Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 6.5 mA (LED on) Average Operating Current: 375µA (LED flashing - in Velociti Mode);...
  • Page 2 FIGURE 1A: FIGURE 1B. JUMPER LOCATION: C1059-00 C0910-00 FIGURE 2A. MODULE MOUNTING FIGURE 2B: WITH BARRIER: C1070-00 I56-3550-008 06/19/2018...
  • Page 3 FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Y: 24 VDC CIRCUIT CONNECT MODULES TO LISTED COMPATIBLE DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE CONTROL PANELS ONLY RUN TO PROVIDE SUPERVISION OF CONNECTIONS. (–) FROM 24 VDC POWER SUPPLY CONTROL PANEL OR...
  • Page 4 Velociti ® , Gamewell-FCI ® , System Sensor ® , and Honeywell ® are registered trademarks of Honeywell International, Inc. I56-3550-008 ©2018 Honeywell. 06/19/2018...

This manual is also suitable for:

Aom-2sf