Honeywell Gamewell FCI Velociti Series Installation And Maintenance Instructions page 4

Supervised control module

Advertisement

FIGURE 5. TYPICAL WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Y:
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE INSTALLATION MANUAL FOR DETAILED INFORMATION.
DO NOT LOOP WIRE AROUND TERMINALS 10 &
11. BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AM-50, AM-50-70, AA100
OR AA-120. AMPLIFIER MUST PROVIDE
WIRING SUPERVISION PER NFPA.
47K EOL
RESISTOR
ELR-47K
MODULE POLARITIES ARE
SUPERVISION
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
FIGURE 6. TYPICAL FAULT TOLERANT WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Z:
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE YOUR PANEL'S SLC WIRING DOCUMENTATION FOR DETAILS.
DO NOT LOOP WIRE AROUND TERMINALS 10 & 11. BREAK WIRE TO
ENSURE SUPERVISION OF CONNECTIONS.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AM-50, AM-50-70, AA100
OR AA-120. AMPLIFIER MUST PROVIDE
WIRING SUPERVISION PER NFPA.
47K EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9
BYPASS CAPACITORS: 100µ
A2143-20 NONPOLARIZED
SUPERVISION
MODULE POLARITIES ARE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
Velociti
®
, Gamewell-FCI
®
, System Sensor
®
, and Honeywell
AUDIO CIRCUIT
SHOWN IN ALARM
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
AUDIO CIRCUIT
<10µA LEAKAGE
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
SHOWN IN ALARM
®
are registered trademarks of Honeywell International, Inc.
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
CONTROL
MODULE
ALL WIRING SHOWN IS SUPERVISED
SPEAKERS MUST BE LISTED
FOR FIRE PROTECTION.
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
CONTROL
MODULE
WARNING
4
FROM
PANEL OR
PREVIOUS
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
AND POWER LIMITED
TO NEXT
DEVICE
FROM
PANEL OR
PREVIOUS
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
TO NEXT
DEVICE
SPEAKERS MUST BE LISTED
FOR FIRE PROTECTION.
©2018 Honeywell. 06/19/2018
C1016-01
C1024-02
I56-3550-008