Chapter 2 • Hydran 201Ti Intelligent Transmitter
3.
Install the new battery inside the CPU module's cover.
4.
Solder the wires from the new battery to the same locations on the circuit board: Red
(+) to W8 and blue (-) to W9.
Note: If preferred, battery wires can be cut and spliced back.
5.
Reinstall the JP5 jumper to reconnect the battery.
6.
Replace the cover on the CPU module.
7.
Fasten the cover using the three screws removed during step 7 on page 2-17.
8.
Verify the state of the connector pins.
9.
Reinstall carefully the CPU module on the H201Ti.
10. Fasten the CPU module with the two screws removed during step 4 on page 2-17.
11. Reconnect the H201Ti's power supply.
12. Power on the H201Ti. The H201Ti executes the self-test sequence as described in
Section 4.2.5 on page 4-6.
13. When requested, use the H201Ti's keypad to enter:
• The date and time
• The identification number of the H201Ti
• The identification number of the power station
Note: Except for the Hydran 201 sensor and its calibration parameters, all H201Ti's
parameters are now set to their hardware default values.
14. Using the Hydran Host software or the H201Ti's keypad, enter the values noted
during step 1 on page 2-16.
Note: Use the Hydran Host software to quickly restore the H201Ti's adjustable
parameters.
15. Discard the removed battery.
2-18