Bosch ADS-AMC2-4R4CF Installation Manual

Bosch ADS-AMC2-4R4CF Installation Manual

Access modular controller 2
Hide thumbs Also See for ADS-AMC2-4R4CF:

Advertisement

Quick Links

Access Modular Controller 2
ADS‑AMC2‑4R4CF | APC‑AMC2‑4R4CF
en
Installation manual

Advertisement

Table of Contents
loading

Summary of Contents for Bosch ADS-AMC2-4R4CF

  • Page 1 Access Modular Controller 2 ADS‑AMC2‑4R4CF | APC‑AMC2‑4R4CF Installation manual...
  • Page 3: Table Of Contents

    6.1.1 Computer UL 294 level descriptions Installation instructions Extended technical specification 6.4.1 RS-485 extension 6.4.2 Power consumption Troubleshooting Resetting the software Resetting the device to factory default Service and repair Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 4 Access Modular Controller 2 Disposal Technical specifications Appendices 11.1 Connecting diagrams 11.2 Status display 11.2.1 Bootloader V00.49 11.2.2 Firmware until 6x.45, 37.60 11.2.3 Firrmware xx.61, 37.71 11.2.4 Firmware xx.62, 37.72 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 5: Safety

    Warning! Risk of explosion of lithium battery The battery can explode if replaced incorrectly. Replace the battery with the same type as recommended by Bosch. Dispose used batteries according to the instructions of the manufacturer of the batteries. Warning! Risk of physical injury due to blocked escape routes This product may block escape routes if not installed correctly.
  • Page 6: Unpacking

    Do not attempt to put the product into operation if components are damaged. If any parts are missing, inform your customer service representative or a Bosch Security Systems salesperson. The shipping carton is the safest transport container for the unit. Store the shipping carton and the other packaging material for future use.
  • Page 7: Short Information

    If you need further assistance or have any questions, contact: Bosch Security Systems B.V. Torenallee 49 5617 BA Eindhoven Netherlands www.boschsecurity.com © Bosch Security Systems B.V., 2022 Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 8: Introduction

    The built in compact flash adapter provides adequate storage capability for cardholders and events. The electronics of the controller are completely covered by a plastic housing. The LCD (liquid crystal display) provides all important status information. Secured Area Unsecured Area Figure 3.2: Example 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 9 The extensions offer 8 or 16 additional inputs and outputs. In the Bosch Access Host Systems, the setup procedure for a controller is made very simple and fast by the use of door templates. Once selected, all the inputs and outputs are predefined.
  • Page 10: Product Overview

    Jumper: Interface selector RS-485 host connection, RS-485 two wire or RS-485 four wire (depends on external wiring) Configurable RS-485 host interface Compact flash memory Project-specific interface Configurable 10/100 Mbit/s Ethernet host interface 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 11 AMC2 internal power supply (“wet” mode). Jumper: Potential equalization between different systems and earth ground (shield) for the bus systems. Jumper: Equalization of potential between different systems and earth ground (shield) for the extension interface. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 12: Status Display

    - = offline "C" = Counter (0 to 9) of the received data packages from the host interface. RS 485 Bus connection: A = Address 1 … H = Address 8 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 13: System Overview

    3 and 4 are on the other bus. This gives the advantage in cabling: longer cable lengths can be used (1200 m maximum per bus). Internally the buses are processed as one interface. With this arrangement, you can connect all readers to one interface. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 14: Installing

    Push down the controller until the lower edge snaps out of the mounting rail [1]. Pull the lower end of the controller from the mounting rail [2]. Figure 4.2: Unmounting the controller from a mounting rail 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 15: Opening The Case

    The controller’s case consists of a top cover mounted with a two-point snap-in closure on a chassis. To open the case, push down the two snap-ins with a screwdriver, then swing the cover down. Figure 4.3: Opening the controller´s case Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 16: Closing The Case

    [1]. Please ensure that the BOSCH logo is not upside-down. The upper edge of the front cover now aligns with the two-point snap-in closures on the upper edge of the back cover [2], and may thus be clicked gently into place.
  • Page 17: Cabling

    Notice! These specifications apply to power supply, readers, relay outputs, and extension interface. Regarding inputs, specific voltage-drop values need to be taken into account. Refer to Connecting Analog Input Devices. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 18: Grounding And Shielding

    JP2 is set (= A3) – a party line exists and signal ground is connected, the jumper JP2 is set at the first device only (= A3) 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 19: Grounding For Extension Interface

    RS-485 ground of the bus. Only set jumper C and D (C2 or D2) if the controller powers all other peripheral devices which are directly connected. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 20: Connecting The Power Supply To The Controller

    Connect an external power supply (10 VDC - 30 VDC) to the controller at pin 1 (positive) and pin 3 (0 V) of the pluggable screw connector. Bosch recommends using the Bosch APS-PSU-60 power supply unit. This power supply can also be used as an uninterpretable power supply (UPS) when using the appropriate batteries.
  • Page 21: Ethernet Host Interface

    When using an Ethernet connection, switches 1 and 5 of the DIP switch must be set to the ON position (= factory setting) (see Figure 3.3, item 1 , page 10 ). This also ensures correct communication with the Bosch Building Integration System (BIS) and the Bosch Access Management System (AMS).
  • Page 22: Rs-485 Host Interface

    The cable length of branch lines must not exceed 100 m (330 ft). To use RS-485 mode at the controller, connect the data cables to the pluggable screw connector of the RS-485 host interface. 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 23: Rs-485 Two Wire Connection

    Switch 5 selects one of the two different protocols, SDEB and BPA (according to DIN6619). Switch 6 sets the connection to the host system to either RS-485 or the Project-specific interface (PI). Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 24 RS-485 host connection, provided only one AMC2 is connected on the bus. Set BPA (= DIP switch 5 to OFF) in the case of an: RS-485 host connection with more than one and maximum eight AMC2s per bus. 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 25 Access Modular Controller 2 Installing | en Notice! Changing the type of the host connection requires a reset of the AMC2 - see Resetting the software, page 40 . Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 26: Rs-485 For Extension Modules

    Figure 4.16: Connection of an extension module to an AMC2 Notice! The address of the board is set using a switch on the board’s underside (see Equipment Configuration). The extension boards are assigned the addresses 1 to 3. 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 27: Rs-485 Interface For Card Readers

    For the wiring of the bus system use twisted pair cable. – Any bus line conductor connects up to eight card readers. Do not exceed the maximum number of devices. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 28: Power Reader

    When you wire the reader, make sure that the voltage at the reader is the same as the reader specification. If the voltage drop on the cable is too high, increase the cable cross-section or use a separate local power supply unit for the reader. 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 29: Connecting Relay Outputs

    12/24 V of the AMC2 to each relay output (E2) to control external consumers. E 1: E 2: Figure 4.19: Relay mode settings E 1: E 2: Figure 4.20: Location of relay output jumpers (bottom side) Delivery status Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 30 Figure 4.21: Recovery diode schematic Normally open / normally closed Common Inductive load Recovery diode Notice! When you use the recovery diode, make sure to use it in the reverse direction. 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 31: Connecting Analog Input Devices

    The AMC2 can also detect the wiring conditions ‘short circuit’ and ‘broken’, and hence trigger an alarm if the appropriate devices are connected. Figure 4.23: Circuit diagram AMC2 analog input Monitoring / door contact Resistor parallel (R Resistor serial (R Broken wire Short circuit Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 32 Table 4.3: Maximum values of cable resistance per used resistor combination in Ohm Notice! We recommend using serial resistors (R ) no higher than 5K6 in order to obtain clear measurements. 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 33: Tamper Protection

    AMC2 provides an additional interface to connect external tamper contacts. This interface is a potential-free 2-pin pluggable screw connector marked with T. When not in use this tamper contact should be shorted. Figure 4.24: Location of the tamper protection contact Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 34: Operating

    Notice! The AMC2 can be renamed through the controllers IPConfig tool with a name that is not longer than 14 characters. The name has to fulfill the requirements of NetBIOS. 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 35: Ul Requirements

    The enclosures AMC2-UL01 (for one device) or AMC2-UL02 (for two devices). – For every enclosure, a power supply Bosch APS-PSU-60 is necessary, and must be located in the same room as the connected AMC2 device. Recommended maximum distance between power supply unit and AMC2 is 3 m (9.84 ft).
  • Page 36: Installation Instructions

    It may not be used for connection to readers or other accessories. – All units are to be powered by the Bosch APS-PSU-60 power supply for UL installations. The power supply must be located in the same room as the connected AMC2 device.
  • Page 37 The standby power system for the HVAC system may be supplied by an engine driven generator alone. A standby battery is not required to be used. For UL compliance, use only UL Listed readers. Figure 6.1: Example of mountings with extensions Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 38: Extended Technical Specification

    10 VDC to 30 VDC, maximum of 3 A Power consumption 5 VA Total combined output 3 A @ 10 VDC - 12 VDC 2.5 A @ 24 VDC - 30 VDC 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 39: Troubleshooting

    – No connection to access – Check configuration AMS after factory reset. system. settings within AMS or ACE system. – Check if the controller is activated in the configuration settings. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 40: Resetting The Software

    As soon as it is online again, controller’s bootloader will download a fresh copy of the application program and configuration. If the problem persists contact after sales support. Figure 7.1: Reset button 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 41: Resetting The Device To Factory Default

    – Subnet mask = [assigned by DHCP server or “0.0.0.0” if not available] – Password = no password – Create your password in the IP Config settings of the AMC. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 42: Service And Repair

    Upon completion of service or repair work on the controller, ask the service technician to perform safety checks to ensure that the controller operates properly. After sales support For more information, visit www.boschsecurity.com/xc/en/support/. 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 43: Disposal

    The AMC2 has a CF card as storage medium. When disposing of the AMC2, ensure that the CF card or the complete AMC2 is destroyed or disposed of in accordance with the Local Data Protection Ordinance. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 44: Technical Specifications

    60 VA maximum – 55 VA (available for external devices) Display Environmental IP rating IP30 Operating temperature (°C) 0 °C – 50 °C Operating temperature (°F) 32 °F – 122 °F RoHS Compliant 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 45: Appendices

    Ground (PAG) Data Tx+ (4-wire) Data Tx- (4-wire) Table 11.4: RS-485 host on upper PCB TXD+ TXD- RXD+ Not connected Not connected RXD- Not connected Not connected Table 11.5: Ethernet Network socket (RJ45) Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 46 Analog Input 3 Analog Input 7 Analog Input 8 Analog Input 4 Relay Output 7 Relay Output 3 Relay Output 4 Relay Output 8 Figure 11.3: Connector blocks of the AMC2 4R4 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 47 Not connected Not connected Table 11.7: RS485 reader interface Analog Input, in Analog Input, out Table 11.8: Analog input Relay Output, normally open Relay Output, common Relay Output, normally closed Table 11.9: Relay output Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 48 Power supply for external devices (10V - 30V) Power supply for external devices (0V) Shield Data RxTx+ Data RxTx- Ground (PAG) Table 11.10: Host / Extension interface Tamper Contact, in Tamper Contact, out Table 11.11: External tamper contact 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 49: Status Display

    S/N1: 0910024419 Serial number 18 digits - Part1 10 digits S/N2: 22850034 Part 2 - 8 digits 11.18 12:24:18 S Current date and time (MM.DD hh:mm:ss) (S) = daylight saving Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 50: Firrmware Xx.61, 37.71

    Vxx.xx xx.xx.xx aa = Reader Protocol Version 37 - Wiegand, 60 - Lbus, 61 - BG900, 62 - OSDP bb = Firmware Version 01.05.17 release date of the firmware (dd.mm.yy) 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 51: Firmware Xx.62, 37.72

    If a brand-new AMC is connected to a host system supporting DTLS, the AMC will be configured with DHCP active and its IP address will be set to a device-specific link-local IP address in the range 169.254.0.0/16. Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 52 IP-address of the gateway M 255.255.255.0 Subnetmask H 192.168.10.10 IP-address of the host computer DHCP 1 DHCP-status: 1 = on 0 = off D 192.168.10.1 IP-address of the DNS server 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 53 AMC, if no DCP has been set. Splitted over 3 displays. Key2: GUZY-KJUN3 Random LCD Key Part2 Key3: GSJ6-HOP43 Random LCD Key Part3 Key: Customized DCP set Bosch Security Systems B.V. 2022-03 | V03 | Installation manual...
  • Page 54 Troubleshooting – Repair & Exchange – Product Security Bosch Building Technologies Academy Visit the Bosch Building Technologies Academy website and have access to training courses, video tutorials and documents: www.boschsecurity.com/xc/en/support/training/ 2022-03 | V03 | Bosch Security Systems B.V. Installation manual...
  • Page 56 Bosch Security Systems B.V. Torenallee 49 5617 BA Eindhoven Netherlands www.boschsecurity.com © Bosch Security Systems B.V., 2022 Building solutions for a better life. 202203231554...