Title
f115
f116
Acceleration/ deceleration pattern
Acceleration/deceleration patterns can be selected individually, using the acceleration/deceleration 1, 2
and 3 parameters.
6
Title
f502
f503
f512
For an explanation of acceleration/deceleration patterns, see 6.23.1.
Both the settings of the S-pattern lower-limit and upper-limit adjustment parameters ( and
) are applied to any acceleration/deceleration S-pattern.

6. 28 Shock monitoring function

f590: Shock monitoring
f591: Shock monitoring trip/ alarm selection
f592: Shock monitoring detection direction selection
f593: Shock monitoring detection level
f595: Shock monitoring detection time
f596: Shock monitoring detection hysteresis
f597: Shock monitoring detection start waiting time
f598: Shock monitoring detection action selection
⇒ Refer to "Shock monitoring function Instruction Manual: E6581875".
a) Operating method: Terminal input
Set the operation control mode selection cmod to 0.
b) Use the S2 and S3 terminals for switching. (Instead, other terminals may be used.)
S2: Acceleration/deceleration switching signal 1
S3: Acceleration/deceleration switching signal 2
Function
Input terminal selection 5 (S2)
Input terminal selection 6 (S3)
1) Linear acceleration/deceleration
2) S-pattern acceleration/deceleration 1
3) S-pattern acceleration/deceleration 2
Function
Acceleration/ deceleration 1 pattern
Acceleration/ deceleration 2 pattern
Acceleration/ deceleration 3 pattern
Adjustment range
0-203
0-203
Adjustment range
0: Linear
1: S-pattern 1
2: S-pattern 2
F-100
E6581611
Setting value
24 (the second
acceleration/deceleration
mode selection)
26 (the third
acceleration/deceleration
mode selection)
Setting value
0
0
0