Figure 4-9: Select System Options Screen - Motorola RF-Conductor! 3200 Manual

Hide thumbs Also See for RF-Conductor! 3200:
Table of Contents

Advertisement

SuperStream Commands

Figure 4-9: Select System Options Screen

The WMS-Data NIU supports a primary system ID and eight alternate system IDs. The
alternate system IDs are also referred to as Supersystems. The default primary system ID
is 1. Initially, all the alternate IDs are disabled. The system IDs should be unique at all
times. If the primary system ID is the same as one of the alternate system IDs, then that
alternate system ID will be removed from the list. The NIU ignores system IDs sent from
the control point if they are the same as the programmed system IDs. The NIU also
ignores the system IDs if all the alternate systems are programmed.
2.
To change a primary system ID, use the
listing and press:
The Change System ID screen appears (see Figure 4-10).
3.
Enter the system ID to change and press:
4-10
<tab>
<Return>.
6880494G55-O
RF-Conductor! Controller NIU Remote Configuration
to position the cursor to the left of the
Valid values are 1-255.
<Return>.