10-2.Power Supply For Heat Source Unit - Mitsubishi Electric CITY MULTI PQRY-P72-336ZLMU-A1 Data Book

Table of Contents

Advertisement

10. ELECTRICAL WORK
10-2. Power supply for Heat source unit
10-2-1. Electrical characteristics of Heat source unit at cooling mode
PQRY-P-Z(S)LMU
Model
Unit Combination
PQRY-P72ZLMU
PQRY-P96ZLMU
PQRY-P120ZLMU
PQRY-P144ZLMU
PQRY-P168ZLMU
PQRY-P192ZLMU
PQRY-P144ZSLMU
PQRY-P72ZLMU
PQRY-P72ZLMU
PQRY-P168ZSLMU
PQRY-P72ZLMU
PQRY-P96ZLMU
PQRY-P192ZSLMU
PQRY-P96ZLMU
PQRY-P96ZLMU
PQRY-P216ZSLMU
PQRY-P96ZLMU
PQRY-P120ZLMU
PQRY-P240ZSLMU
PQRY-P120ZLMU
PQRY-P120ZLMU
PQRY-P288ZSLMU
PQRY-P144ZLMU
PQRY-P144ZLMU
PQRY-P312ZSLMU
PQRY-P144ZLMU
PQRY-P168ZLMU
PQRY-P336ZSLMU
PQRY-P168ZLMU
PQRY-P168ZLMU
MEES21K047
Hz
Volts
-
-
-
-
-
-
60Hz
575V
Symbols: MCA: Minimum Circuit Ampacity
SC: Starting Current, RLA: Rated Load Amps
Heat source unit
Voltage range
MCA(A)
MOP(A)
5
7
11
13
16
20
5
5
5
7
7
518 to 633V
7
7
11
11
11
13
13
13
16
16
16
WR2-Series-575V
Compressor
Output (kW)
SC(A)
15
4.3
7
15
6.0
7
15
7.7
7
20
9.5
7
25
11.0
7
30
12.4
7
15
4.3
7
15
4.3
7
15
4.3
7
15
6.0
7
15
6.0
7
15
6.0
7
15
6.0
7
15
7.7
7
15
7.7
7
15
7.7
7
20
9.5
7
20
9.5
7
20
9.5
7
25
11.0
7
25
11.0
7
25
11.0
7
94