[9.2.2] Alarm Tests
[9.2.2.1] M02-04-00 Magnet Test
1. Place the painted surface of the magnet onto the TEST locator on the bottom of the detector housing (Figure 13).
2. Verify system control panel alarm status and control panel execution of all intended auxiliary functions (i.e. fan shutdown, damper
control, etc.)
3. The detector is self-restoring when the magnet is removed. Verify that
the system control panel has reset; the panel may have to be reset.
[9.2.2.2] RTS451/RTS451KEY Remote Station Test
The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct smoke detector. These accessories
provide the stimulus to initiate an alarm condition at the detector. The detector is self-restoring when the accessory test stimulus is
removed. Verify that the system control panel has reset; the panel may have to be reset.
[9.2.3] Sensitivity Tests
Notify the proper authorities that the smoke detector system is undergoing maintenance, and that the system will temporarily be out of
service. Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department.
[9.3] Maintenance of Duct Smoke Detectors
[9.3.1] Air Filters
1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with new filters (p/n F36-09-11). If they are not heavily coated, use a vacuum
cleaner or compressed air nozzle to remove dust, then reinstall the filters.
[9.3.2] Photo Detector Boards
1. Remove the screen by gently grasping on each side and pulling straight off.
2. Lift the photo chamber in the same fashion. Vacuum the screen and cover. Use clean, compressed air to loosen and blow out any
remaining debris. Replacement screens (p/n S08-39-01) are available.
3. Vacuum photo chamber, then use clean compressed air to blow area clean.
4. Replace the chamber by pressing it onto the base. Press the screen into place. It should fit tightly on the chamber.
Figure 12. Detector with optional PA400:
5
7
5 = ALARM SIGNAL
7 = AUX. POWER (–)
F300-28-00
PA400
Figure 14. Insulator card for D350RPL:
NOTE: POWER INPUTS ACCEPT 24VDC NON-POLARIZED, 24 VAC, 220/240 VAC AND 120 VAC.
Figure 13. Testing detector alarm:
H0132-00
7
H0130-00
H0133-01
I56-1974-006R