5. Propane Metering Valve. Low fire is adjusted at the main LP fuel valve. Adjust while
watching the LP fuel flow meter. If freezing occurs, open the low fire setting ¼ of a position
at a time until the freezing stops. The valve travel varies for a given burner model
(see individual burner capacity and performance data sheets).
U. OPERATION
Adjustment of this equipment by unqualified personnel can result in fire,
explosion, severe personal injury, or even death.
TM
1. The MegaStar
uses individual control motors directly coupled for each fuel control valve.
The optional remote rack mounted fuel manifold includes a separate control motor for the
fuel control valves, which is electronically linked to the air control. Air control is performed
with a VFD, modulating the output frequency between 16 Hz and 60 Hz to achieve a precise
air flow.
Figure 19. Individual Control Motor Settings
X7870
(NOT TO SCALE)
WARNING
Page 36
MS-9