MMF-300A: Addressable Monitor Module for one zone of nor-
mally-open dry-contact initiating devices. Mounts in standard
10.16 cm box. Includes plastic cover plate and end-of-line resis-
tor. Module may be configured for either a Style B (Class B) or
Style D (Class A) IDC.
MDF-300A: Dual Monitor Module. Same as MMF-30A except it
provides two Style B (Class B) only IDCs.
MMF-301A: Miniature version of MMF-300A. Excludes LED and
Style D option. Connects with wire pigtails. May mount in device
backbox.
MMF-302A: Similar to MMF-300A, but may monitor up to 20
conventional two-wire detectors. Requires resettable 24 VDC
power. Consult factory for compatible smoke detectors.
CMF-300A: Addressable Control Module for one Style Y/Z
(Class B/A) zone of supervised polarized Notification Appli-
ances. Mounts directly to a 10.16 cm electrical box. Notification
Appliance Circuit option requires external 24 VDC to power noti-
fication appliances.
CRF-300A: Addressable relay module containing two isolated
sets of Form-C contacts, which operate as a DPDT switch.
Mounts directly to a 10.16 cm box, surface mount using the
SMB500.
BG-12LX: Addressable manual pull station with interface mod-
ule mounted inside.
I300A: Fault Isolator Module. This module isolates the DCL loop
from short circuit conditions (required for Style 6 or 7 operation).
SMB500: Used to mount all modules except the MMF-301A and
M301A.
MMF-300-10A: Ten-input monitor module. Mount one or two
modules in a BB-2F cabinet (optional). Mount up to six modules
on a CHS-6 chassis in a BB-6F.
MMF-302-6A: Six-zone interface module for compatible conven-
tional two-wire detectors. Mount one or two modules in a BB-2F
cabinet (optional). Mount up to six modules on a CHS-6 chassis
in a BB-6F.
CMF-300-6A: Six-circuit supervised control module. Mount one
or two modules in a BB-2F cabinet (optional). Mount up to six
modules on a CHS-6 chassis in a BB-6F.
CRF-300-6A: Six Form-C relay control module. Mount one or
two modules in a BB-2F cabinet (optional). Mount up to six mod-
ules on a CHS-6 chassis in a BB-6F.
ADDRESSABLE DEVICE ACCESSORIES
End-of-Line Resistor Assembly (R-47K and R-3.9K):
47k ohm supervises the MMF-300A, MDF-300A, MMF-301A,
and CMF-300A module circuits. 3.9k ohm End-of-Line Resistor
assembly supervises the MMF-302A module circuit. These
resistors are included with each module.
Power Supervision Relay: Supervises the power to 4-wire
smoke detectors and notification appliances.
EOL-CR, EOL-CW: Single End-of-Line resistor plate (required).
EOL-CR is red; EOL-CW white.
NOTE: 1) For more information on compatible equipment, see the
following data sheets (document numbers): ACM-8RF (DF-
51555), ACS/ACMSeries (DF-52378), LDM Series (DF-51384),
LCD-80FC (DF-52185), AD355 (DF-52324), BG-12LX (DF-
52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-60379), CMF/
CRF Series (DF-52130), CP355 (DF-52383), D355PL (DF-52398),
H355 Series (DF-52385), I300 (DF-52389), MMF-300 Series/
MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-
52356), SD355/SD355T (DF-52384). 2) Legacy 300 Series detec-
tion devices such as the CP300/CP350, SD300(T)/SD350(T) and
older modules such as the M300, M301, M302, C304, and BG-
10LX are not compatible with LiteSpeed polling. If the DCL con-
tains one of these devices, polling must be set for standard
LiteSpeed protocol. Please consult factory for further information
on previous 300 Series devices.
Wiring Requirements
While shielded wire is not required, it is recommended that all
DCL wiring be twisted-pair to minimize the effects of electrical
interference. Wire size should be no smaller than 18 AWG (0.78
mm²) and no larger than 12 AWG (3.1 mm²). The wire size
depends on the length of the DCL circuit. Refer to the panel
manual for wiring details.
Fire Alarm Control Panel
OR
80-Character backlit LCD
remote fire annunciator
SD355A
Photo Detector
AD355A
Adapt Detector
H355A, H355RA/
H355HTA
Heat Detector
Power Supply
FCPS-24FS6C
FCPS-24FS8C
MDF-300A
Dual Monitor Module
SD355TA
Photo/Thermal
MMF-300A
Multi-Modules
Monitor Module
• CRF-300-6A Six-Relay Control Module
• CMF-300-6A Six-Circuit
Supervised Control Module
• MMF-302-6A Six-Zone Interface Module
• MMF-300-10 Ten-Input Monitor Module
MMF-302A
2-Wire Detector
Monitor Module
D355PLA / D350RPLA
Beam Detector/Beam 355A/Beam 355SA
(with relay)
Duct Detector
BG-12LX Addressable
Manual Pull Station
Canadian DF-60599:B • 02/11/2011 — Page 3 of 4
ANN-80C
LCD-80FC
SPSRVA
Series
Speaker
Strobes
P2RA Strobe
P2RA Strobe
P2RA Strobe

Advertisement