Single Switch Adapter
Pairing Steps when using a WDRR (see Figure 9): The battery will need to be activated in the WLS Single Switch Adapter and
proper power applied to the WDRR (green  LED illuminated) before proceeding with this pairing procedure. Once the pairing is
completed, the WLS Single Switch Adapter selected will only communicate with the WDRR it was paired to and no other device.
Step
Action
1
Completely read this procedure before starting in order to understand the timing of events that need to be performed.
2
WLS Single Switch Adapter: Remove (if required) the two screws  on the housing cover (See Figure 8, page 8) of the
WLS Single Switch Adapter and locate the function button (see Figure 10) to be used in Step 4.
3
WDRR: Press the Function button  on WDRR (See Figure 12, page 10) for more than four seconds and less than eight
seconds at which time the green and yellow LEDs  (see Figure 12, page 10) will be flashing which indicates to release
the function button immediately as it has entered the pairing mode.
4
WLS Single Switch Adapter: Within a 30 second interval of Step 3, depress the WLS Single Switch Adapter function button
 (See Figure 10, page 8) and hold depressed for more than one second and less than 12 seconds at which time the
orangeLED turns on (see Figure 10, page 8). While in pairing mode, the orange LED will flash on for 100 ms every
second. The orange LED flashes three times 100 ms on, 100 ms off when pairing succeeds. If pairing does not suc-
ceed, the orange LED will turn off and user will need to repeat steps starting with Step 3.
5
WDRR Receiver: Successful pairing will be indicated by the green and yellow LEDs  (see Figure 12, page 10) ceasing to
flash and remaining on for a few seconds before turning off. The specific Tricolor Output LED will also turn on.
6
To confirm proper pairing between the WLS Single Switch Adapter and WDRR, actuate the user supplied switch, and the
Tricolor Output LED  (see Figure 12, page 10) should turn on to indicate the proper output status.
7
Record the WLS Single Switch Adapter Sequence # on identification labels † and apply to the WLS Single Switch Adapter
housing in desired locations (See Figure 11, page 8).
8
Repeat Steps 2-7 to add additional Limitless™ switch. Up to 14 WLS Single Switch Adapters can be paired to a single