Download Print this page

Specifications; Ordering Information - Honeywell VR8205 Manual

Direct ignition dual automatic valve combination gas controls

Advertisement

VR8205; VR4205
SPECIFICATIONS • ORDERING INFORMATION
IMPORTANT: The specifications given in this publica-
tion do not include normal manufacturing toler-
ances. Therefore, this unit may not exactly match the
listed specifications. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be ex-
pected if those conditions are changed.
®
TRADELINE
MODELS
TRADELINE controls are selected and packaged to
provide ease of stocking, ease of handling and maximum
replacement value. TRADELINE model specifications are
the same as those of standard models except as noted
below.
TRADELINE MODEL AVAILABLE: VR8205A Dual
Automatic Combination Gas Control for Direct Ignition
Systems. Models for natural or LP gas.
Model No.
Opening
Suffix Letter
Characteristic
VR8205A,M
Standard
VR4205M
VR8205C,P
Step-opening
VR4205P
VR8205H,K
Slow-opening
VR4205H
a
Step pressure not adjustable.
When purchasing replacement and modernization products from your wholesaler or your distributor, refer to the price sheets for complete
ordering number, or specify—
1. Order number, TRADELINE
2. Natural or LP gas.
3. Step pressure for step-opening gas control.
4. Accessories, if desired.
5. Order separately: transformer, igniter, sensor, module, limit controller, and thermostat or controller as required.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
2. Home and Building Control Customer Satisfaction
Honeywell, Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitee, 740 Ellesmere Road, Scarborough, Ontario M1P2V9. International Sales and
Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0049—2
TABLE 1—MODEL SPECIFICATIONS.
Standard
Factory Regulator Settings
Type
of Gas
in. wc
kPa
Natural
3.5
LP
10.0
Natural
Step—0.7,
Step—0.17,
0.9,1.2 or 1.7,
0.22, 0.30 or
a
0.48, as
as ordered
Full Rate—
ordered
3.5
Full Rate—
LP
Step—1.4,
Step—0.35,
2.5, 4.0 or
0.62, 0.99 or
5.5, as
1.37, as
a
ordered
ordered
Full Rate—10
Full Rate—
Natural
3.5
LP
10.0
®
if desired.
ADDITIONAL FEATURES:
• 3/8 in. bushing.
• 3/4 in. straight flange assembly (with O-ring and screws).
• Tool for flange hex screws.
STANDARD MODELS
MODELS: VR8205 and VR4205 Dual Automatic Valve
Combination Gas Controls for use in Direct Ignition
Systems. See Table 1 for specifications.
SUPPLY VOLTAGE:
VR4205: 120 Vac, 60 Hz.
VR8205: 24 Vac, 60 Hz.
(50/60 Hz models available on request.)
CURRENT DRAW:
VR4205: 0.1A
VR8205: 0.5A
Optional
Factory Regulator Settings
in. wc
kPa
0.9
3 to 5
0.7 to 1.2
2.5
8 to 12
2 to 3
Step—0.7,
Step—0.17,
0.9,1.2 or 1.7,
0.22, 0.30 or
a
0.48, as
as ordered
a
Full Rate—
ordered
3 to 5
Full Rate—
0.9
0.7 to 1.2
Step—1.4,
Step—0.35,
2.5, 4.0 or
0.62, 0.99 or
5.5, as
1.37, as
a
a
ordered
ordered
Full Rate—8
Full Rate—
2.5
to 12
2-3
0.9
3 to 5
0.7 to 1.2
2.5
8 to 12
2 to 3

Ordering Information

2

Specifications

Range of
Field Adjustment
in. wc
kPa
3 to 5
0.7 to 1.2
8 to 12
2 to 3
Step—none;
Step—none;
Full Rate—
Full Rate—
3-5
0.7 to 1.2
a
Step—none;
Step—none;
Full Rate—
Full Rate—
8-12
2 to 3
a
3 to 5
0.7 to 1.2
8 to 12
2 to 3

Hide quick links: