Honeywell SUPER TRADELINE VR8300A Installation Instructions Manual

Continuous pilot combination gas control
Hide thumbs Also See for SUPER TRADELINE VR8300A:

Advertisement

Quick Links

VR8300A Continuous Pilot Combination
APPLICATION
These continuous pilot gas controls are used in gas-fired
appliances with capacities up to 200 cfh at 1 in. wc
pressure drop (5.7 cmh at 0.25 kPa) on natural gas.
Included are a manual valve, safety shutoff, two automatic
operators, and a pressure regulator. See Table 2 for
temperature range and regulator type.
The VR8300 setup for natural gas includes a 39369 LP
Conversion Kit. The kit contains a new cap screw, a
pressure regulator adjustment screw, a tapered spring and
a conversion label. The control must be equipped with a
standard servo pressure regulator. Step-opening gas
controls cannot be converted.
Capacity:
Size (Inlet x Outlet)
1/2 in. x 1/2 in.
1/2 in. x 3/4 in.
3/4 in. x 3/4 in.
a
Capacity based on 1000 Btu/cu ft, 0.64 specific gravity natural gas at 1 in. wc pressure drop (37.3 MJ/cu m, 0.64 specific
gravity natural gas at 0.25 kPa pressure drop).
Use conversion factors in Table 1 to convert capacities for
other gases.
Table 1. Gas Capacity Conversion Factors.
Specific
Gas
Gravity
Manufactured
0.60
Mixed
0.70
Propane
1.53
Table 2. Temperature Range and Regulator Type.
Ambient
Temperature Range
Model
°F
Number
VR8300A 0° to 175° 18° to 79° Standard-opening
®U.S. Registered Trademark
Copyright © 1998 Honeywell Inc. • All Rights Reserved
Capacity at 1 in. wc
a
Pressure Drop
180 cfh (5.1 cmh)
190 cfh (5.4 cmh)
200 cfh (5.7 cmh)
Multiply Listed
Capacity By
0.516
0.765
1.62
Regulator
°C
Type
INSTALLATION INSTRUCTIONS
Body Pattern:
Straight-through body pattern.
Inlet x Outlet Sizes Available:
1/2 x 1/2 in., 1/2 x 3/4 in., and 3/4 x 3/4 in. (factory-installed
inlet flange).
Adapters:
Adapters available for 1/2 and 3/4 in. straight and angle
connections. Refer to Table 3.
Electrical Ratings:
Voltage and Frequency: 24 Vac, 50/60 Hz.
Current Draw: 0.70A.
Minimum Regulated
Capacity
30 cfh (0.8 cmh)
30 cfh 0.8 cmh)
30 cfh (0.8 cmh)
Table 3. Flange Part Numbers.
Inlet/Outlet
Flange
Pipe Size
Type
1/2 in. NPT
Straight
Elbow
3/4 in. NPT
Straight
Elbow
NOTE: Flange kits include one flange with attached
O-ring and fan mounting screw.
Approvals:
International Approval Services Listed: L2025007.
Australian Gas Association Certificate: Applied for.
Delta C: Pending approval.
X-XX UL
Gas Control
Maximum Regulated
Capacity
225 cfh (6.4 cmh)
290 cfh (8.2 cmh)
300 cfh (8.5 cmh)
Part Number
Without Hex
With Hex
Wrench
Wrench
393690-6
393690-16
393690-3
393690-13
393690-4
393690-14
393690-5
393690-15
69-0668-1

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SUPER TRADELINE VR8300A

  • Page 1 Number Type International Approval Services Listed: L2025007. Australian Gas Association Certificate: Applied for. VR8300A 0° to 175° 18° to 79° Standard-opening Delta C: Pending approval. ®U.S. Registered Trademark 69-0668-1 Copyright © 1998 Honeywell Inc. • All Rights Reserved X-XX UL...
  • Page 2: Installation

    VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL Converting Between Natural and LP Gas INSTALLATION WARNING When Installing this Product… Fire or Explosion Hazard. 1. Read these instructions carefully. Failure to follow Can cause property damage, severe injury, them could damage the product or cause a hazard- or death.
  • Page 3 VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL COLOR CODE FOR NATRUAL CAP SCREW BLACK SILVER PRESSURE REGULATOR WHITE WHITE ADJUSTING SCREW TAPERED STAINLESS SPRING STEEL GAS CONTROL INLET FLANGE PRESSURE REGULATOR HOUSING 9/64 IN. (3.6 MM) HEX SCREWS (4) 1 DO NOT OVERTIGHTEN SCREWS. M803 TIGHTEN TO 25 IN.
  • Page 4 VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL IMPORTANT Install Gas Control On LP installations, use compound resistant to LP gas. Do not use Teflon tape. To install: 4. Apply a moderate amount of good quality pipe 1. Mount the gas control 0 to 90 degrees, in any compound (DO NOT use Teflon tape) to pipe only, direction, from the upright position of the gas control leaving two end threads bare.
  • Page 5 VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL 2. Square off and remove the burrs from the end of the 3. For attachment nut type pilot burners: From tubing. beneath, insert the tip of the Q340 into the hole or 3. Unscrew the compression fitting from the pilot outlet barrel in the pilot burner.
  • Page 6: Start-Up And Checkout

    VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL Table 5. Maximum Length of Supplementary Limit Leadwires in in. (m) When Using Q340A Thermocouple. Maximum Leadwire Length x 2 (Wires) Thermocouple Length AWG No. 14 AWG No. 16 AWG No. 18 DO NOT USE. Table 6.
  • Page 7 VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL Light Pilot Burner Flame Check and Adjust Gas Input to Main Burner 1. Turn the gas control knob clockwise to OFF. CAUTION Wait five minutes to dissipate any unburned gas. Sniff around the appliance near the floor. Do not Do not exceed the input rating stamped on the relight the pilot flame if you smell gas.
  • Page 8: Check Safety Shutdown Performance

    VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL 4. If the desired outlet gas pressure or gas flow rate Regular preventive maintenance is important in applica- cannot be achieved by adjusting the gas control, tions that place a heavy load on system controls such as in check the gas control inlet pressure using a the commercial cooking and agricultural and industrial manometer at the inlet pressure tap.
  • Page 9: Instructions To The Homeowner

    VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL If Main Burner does not Come on with Call SERVICE For Heat: WARNING 1. Make sure the gas control knob is in the ON Fire or Explosion Hazard. position. Can cause property damage, severe injury or 2.
  • Page 10: Turning Off Appliance

    VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL IMPORTANT 8. Turn the gas control knob counterclockwise Follow the operating instructions provided by the to PILOT. manufacturer of your heating appliance. The 9. Push and hold the gas control knob all the way in. information below is for a typical gas control Immediately light the pilot burner flame with a match application, but the specific controls used and the...
  • Page 11 VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL 69-0668—1...
  • Page 12 VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL Home and Building Control Home and Building Control Honeywell Inc. Honeywell Limited-Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P.O. Box 524 North York, Ontario Minneapolis, MN 55408-0524 M2H 3N7 Printed in U.S.A. on recycled paper containing at least 10% www.honeywell.com...