20 | Specific Application Considerations

Open Well Water Systems

When a water well is used exclusively for supplying
water to the heat pump, operate the pump only
when the Heat Pump operates. A 24 volt,
double-pole single-throw (DP/ST) contactor can
be used to operate the well pump with the heat
pump. When two or more units are supplied from
one well, the pump can be wired to operate
independently from either unit. Two 24-volt
double-pole single-trow relays wired in parallel are
required. In either case, a larger sized VA
transformer may be required.
Fig. 13 Open Well Water Setup
[1] Line-Voltage Disconnect
[2] Flex Duct Connection
[3] Low-Voltage Control Connection
[4] Line-Voltage Connection
[5] Vibration Pad
[6] P/T Ports
[7] Hose Kits (optional)
[8] Ball Valves
[9] Solenoid Valve Slow Closing
[10] Condensate Drain Connection
[11] Pressure Tank (optional)
8733829041 (2021/07)
The discharge water from the heat pump is not
contaminated in any manner and can be disposed
of in various ways depending on local codes (i.e.
discharge well, dry well, storm sewer, drain field,
stream, pond, etc.)
Subject to change without prior notice
QV Series Heat Pumps
For Reference Only.
A typical setup is shown
for illustration purposes
QV Series Heat Pumps