Install to Fit Your Application
Flex duct is recommended in connecting to the TrueDRY DR90-AP collars to reduce vibration noise.
Dedicated Return to Main Supply
A
RETURN
SEPARATE
RETURN
Main Return to Main Supply
B
RETURN
T
u r
e
D
y r
D
R
9
0
A -
P
D
e
h
u
m
i d i
c i f
AIR HANDLER
TrueDRY
BACKDRAFT
DAMPER
AIR HANDLER
TrueDRY
t a
o i
n
S
s y
e t
m
5
0
0
7
7
4
7
0
0 -
0
1
Duct Sizing: Use minimum 10-in. diameter round for
duct lengths up to 25 ft. Minimum 12-in. required for
lengths longer than 25 ft. Duct branches from the main
inlet/exhaust should be minimum 10-in. round for 2-3
branches, and 12-in. round or larger for 4 branches or
more.
For the optional fresh air ventilator port, use 6-in. round,
insulated duct for lengths up to 50 ft.
Use 8-in. round duct for more than 50 ft. of if more than
100 CFM is required.
Isolated Areas: Effective dehumidification may require
ducting to isolated or stagnant air flow areas.
Electrical requirements:
220 VAC outlet. Ground fault
interrupter (GFI) recommended.
Ideal when...
SUPPLY
•
Access to dedicated central return for
TrueDRY is available.
•
Requires backdraft damper on the
exhaust port to minimize backdraft when
TrueDRY is not on but A/C is.
(OPTIONAL)
•
(optional) Duct TrueDRY supply with 20%
GRAVITY DAMPER
open gravity damper to provide dry air to
M33150
a specific area
Ideal when...
SUPPLY
•
Running TrueDRY when not running A/C.
•
Requires damper on the exhaust port to
minimize backdraft when TrueDRY
DR90-AP is not on but A/C is.
•
Access to a dedicated central return is
not possible.
BACKDRAFT
DAMPER
M27324