Install to Fit Your Application

Flex duct is recommended in connecting to the TrueDRY DR90-AP collars to reduce vibration noise.
Dedicated Return to Main Supply
A
RETURN
SEPARATE
RETURN
Main Return to Main Supply
B
RETURN
T
u r
e
D
y r
D
R
9
0
A -
P
D
e
h
u
m
i d i
c i f
AIR HANDLER
TrueDRY
BACKDRAFT
DAMPER
AIR HANDLER
TrueDRY
t a
o i
n
S
s y
e t
m
5
0
0
7
7
4
7
0
0 -
0
1
Duct Sizing: Use minimum 10-in. diameter round for
duct lengths up to 25 ft. Minimum 12-in. required for
lengths longer than 25 ft. Duct branches from the main
inlet/exhaust should be minimum 10-in. round for 2-3
branches, and 12-in. round or larger for 4 branches or
more.
For the optional fresh air ventilator port, use 6-in. round,
insulated duct for lengths up to 50 ft.
Use 8-in. round duct for more than 50 ft. of if more than
100 CFM is required.
Isolated Areas: Effective dehumidification may require
ducting to isolated or stagnant air flow areas.
Electrical requirements:
220 VAC outlet. Ground fault
interrupter (GFI) recommended.
Ideal when...
SUPPLY
Access to dedicated central return for
TrueDRY is available.
Requires backdraft damper on the
exhaust port to minimize backdraft when
TrueDRY is not on but A/C is.
(OPTIONAL)
(optional) Duct TrueDRY supply with 20%
GRAVITY DAMPER
open gravity damper to provide dry air to
M33150
a specific area
Ideal when...
SUPPLY
Running TrueDRY when not running A/C.
Requires damper on the exhaust port to
minimize backdraft when TrueDRY
DR90-AP is not on but A/C is.
Access to a dedicated central return is
not possible.
BACKDRAFT
DAMPER
M27324
24