Master Programming Level

3.5 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and
the system Trouble indicator flashes until Programming mode is exited. The following display will
appear:
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the
display, pressing the 'down' arrow key will display the subsequent Programming Screens as
illustrated below while pressing the 'up' arrow key will display the previous screen.
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP
3.5.1 FACP CONFIG (Application Templates)
PROGRAMMING
For a detailed description of each Template, refer to "FACP Configuration Templates" on
1=FACP CONFIG USER
page 100. The FACP Configuration option allows the user to program the FACP with 1 of 13
2=INPUT ZONES
3=OUTPUT CIRCUITS
factory preprogrammed templates or one custom template which can be programmed by the user.
Programming Screen #1
The templates have been provided to allow the user to quickly program the panel with typical job-
site configurations. The user may choose to select one of the templates or bypass this option,
proceeding to the next sections which detail customized programming of the FACP.
A factory template may be chosen and later changed to better fit a site requirement. The changed
template can be saved as the one custom template.
Pressing 1, while viewing Programming Screen #1, will select the FACP Config option and display
the following screen:
Press the down arrow key to view all available templates. During initialization of the panel
following power-up or reset, the selected Template will be displayed by the LCD.
NOTE: Template 1 through Template 13 as well as the Custom Template are available for the
RP-2002/E Agent Release Control Panel.
To select a pre-programmed template, press the number key corresponding to the desired template.
Note that the factory templates may pre-set most programmable features of the FACP.
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
PROGRAMMING
Programming Screen #2
PROGRAMMING
1=FACP CONFIG
T1
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
PROGRAMMING
1=ANN-BUS
2=HISTORY 256 EVENTS
3=WALKTEST
Programming Screen #3
FACP CONFIG
1=TEMPLATE 1
2=TEMPLATE 2
3=TEMPLATE 3
FACP Config Screen #1
Programming
PROGRAMMING
1=CLEAR PROGRAM
2=PASSWORD CHANGE
Programming Screen #4