Performance Curves - Huawei FusionModule5000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Item
Power system
Fan type
Speed adjustment
Rated air volume
Maximum
operating pressure
Configuration of a
condensate pump
Configuration of an
air deflector
Heating function
Humidification
function
External
dimensions (H x W
x D)
Package
dimensions (H x W
x D)
Net weight
Installation mode
Certification
a refers to the test condition (return air dry/wet bulb temperature: 37.8°C/20.8°C; chilled
water inlet temperature: 10°C; water flow rate: 5.5 m

3.3.2.4 Performance Curves

Figure 3-43 and Figure 3-44 respectively show the cooling capacity derating coefficient curve
in proportion to the altitude and the cooling capacity curve in proportion to the glycol solution
density when the NetCol5000-C works under rated power and air flow.
NetCol5000-C030H7A201E12
0E0
208 V to 240 V, 1 Ph, 50 Hz/60
Hz
208 V rated voltage tolerance:
–10% to +6%, 220 V and 240 V
rated voltage tolerance: –10% to
+10%, rated frequency
tolerance: ±3 Hz, one active
power supply, and one standby
power supply
EC fan
Stepless
3
5100 m
/h
1.6 MPa
No
No
Yes
Yes
2000 mm x 300 mm x 1000 mm
2200 mm x 760 mm x 1350 mm
≤ 171 kg
On a concrete or ESD floor
RoHS and REACH
NetCol5000-C030H7A201002
0E1
208 V to 240 V, 1 Ph, 50 Hz/60
Hz
208 V rated voltage tolerance:
–10% to +6%, 220 V and 240 V
rated voltage tolerance: –10% to
+10%, rated frequency tolerance:
±3 Hz, one active power supply,
and one standby power supply
EC fan
Stepless
3
5100 m
/h
1.6 MPa
Yes
No
No
No
2000 mm x 300 mm x 1000 mm
2200 mm x 760 mm x 1350 mm
≤ 165 kg
On a concrete or ESD floor
RoHS and REACH
3
/h).
61

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r001

Table of Contents