Specifications
Walktest
Zone Enable/Disable (one per zone)
•
LED Indicators
Fire Alarm (one per zone)
Supervisory (one per zone)
Trouble (one per zone)
Maintenance (one per zone)
AC Power
NAC Disable
Zone Disable
NAC Fault
System Trouble
Power Trouble
Walktest
Alarm Silence
Earth Fault LED (on circuit board) lights if zero impedance between FACP and ground exist
Battery Fault (on circuit board)
Charger Fault (on circuit board)
•
Piezo sounder for alarm, trouble and supervisory
•
24 volt operation
•
Low AC voltage sense
•
Alarm Verification
•
NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
•
Automatic battery trickle charger
•
Silent or audible walktest capabilities
•
Optional NAC Class A converter module (SFP-2404 only)
•
Optional 4XTM Transmitter Module (SFP-2402 and SFP-2404)
•
Optional 4XZM Zone Relay Module (SFP-2404 only)
•
Optional 4XLM Module for RZA-4X Remote LED Annunciator (SFP-2404 only)
1.2 Specifications
AC Power - TB8
SFP-2402/SFP-2404: 120 VAC, 50/60 Hz, 2.3 amps
SFP-2402E/SFP-2404E: 240 VAC, 50 Hz, 1.15 amps
Wire size: minimum #14 AWG (2.0 mm
Battery (sealed lead acid only) - J8
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can be housed in the
FACP cabinet. Larger batteries require a separate battery box such as the BB-17.)
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
2
) with 600V insulation