Specifications - Honeywell Notifier SFP-2402 Instruction Manual

Table of Contents

Advertisement

Specifications


Walktest

Zone Enable/Disable (one per zone)
LED Indicators

Fire Alarm (one per zone)

Supervisory (one per zone)

Trouble (one per zone)

Maintenance (one per zone)

AC Power

NAC Disable

Zone Disable

NAC Fault

System Trouble

Power Trouble

Walktest

Alarm Silence

Earth Fault LED (on circuit board) lights if zero impedance between FACP and ground exist

Battery Fault (on circuit board)

Charger Fault (on circuit board)
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Alarm Verification
NACs Programmable for:

Silence Inhibit

Auto-Silence

Strobe Synchronization

Selective Silence (horn-strobe mute)

Temporal or Steady Signal

Silenceable or Nonsilenceable
Automatic battery trickle charger
Silent or audible walktest capabilities
Optional NAC Class A converter module (SFP-2404 only)
Optional 4XTM Transmitter Module (SFP-2402 and SFP-2404)
Optional 4XZM Zone Relay Module (SFP-2404 only)
Optional 4XLM Module for RZA-4X Remote LED Annunciator (SFP-2404 only)
1.2 Specifications
AC Power - TB8
SFP-2402/SFP-2404: 120 VAC, 50/60 Hz, 2.3 amps
SFP-2402E/SFP-2404E: 240 VAC, 50 Hz, 1.15 amps
Wire size: minimum #14 AWG (2.0 mm
Battery (sealed lead acid only) - J8
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can be housed in the
FACP cabinet. Larger batteries require a separate battery box such as the BB-17.)
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
2
) with 600V insulation