Panasonic U-8ME1E8E Service Manual page 130

2way system
Table of Contents

Advertisement

2. Detailed Settings Function
Item code
Item
(1B)
Forced thermostat ON time
Cooling discharge
temperature shift
Heating discharge
temperature shift
Temperature shift for
cooling/heating change in
auto heat/cool mode
(Upper limit)
(Lower limit)
(Upper limit)
Change to remote
(Lower limit)
control temperature
setting range
(Upper limit)
(Lower limit)
(Upper limit)
(Lower limit)
Humidifi er operation
Filter (CN70) input
switching
Indoor unit electronic
control valve
T10 terminal switching
No.
0000
5 minutes
0001
4 minutes
–010
–10°C
–009
–9°C
–008
–8°C
0010
10°C
–010
–10°C
–009
–9°C
–008
–8°C
0010
10°C
0001
±1°C
0002
±2°C
0003
±3°C
0007
±7°C
0018
18°C (Lower limit at shipment)
0019
19°C
0029
29°C
0030
30°C (Upper limit at shipment)
0016
16°C (Lower limit at shipment)
0017
17°C
0029
29°C
0030
30°C (Upper limit at shipment)
0018
18°C (Lower limit at shipment)
0019
19°C
0029
29°C
0030
30°C (Upper limit at shipment)
0017
17°C (Lower limit at shipment)
0018
18°C
0026
26°C
0027
27°C (Upper limit at shipment)
0000
Normal
0001
Ignore heat exchanger temperature conditions.
0000
Filter input (differential pressure switch input)
0001
Alarm input (for trouble input about air cleaner or similar device)
Humidifi er input (Operates linked with drain pump when humidifi er is
0002
ON.)
0000
Present (Setting at shipment)
0002
None
0000
Normal (Used as optional relay PCB or JEMA standard HA terminal.)
0001
Used for OFF reminder
0002
Fire prevention input
5 - 7
Remote Controller Functions
Setting data
Description
2WAY SYSTEM