HPF602ULADA Distributed Power Module Installation Manual
RBB Remote Battery Box. See Section 4.7 for battery installation.
The following is the maximum current draw from the auxiliary power terminals for standby calculations. These
currents assume 24 or 60 hours of standby time, followed by 5 minutes of maximum alarm current.
195 mA for 24 Hour Standby Current
39 mA for 60 Hours of Auxiliary Standby Current
The above numbers were calculated assuming the use of 7 AH batteries at 100% of rated capacity.
The total current of the HPF602ULADA, plus all items powered from it, must not exceed 6 A when the panel is
in alarm. Use Table 4-2 to ensure that the current does not exceed 6 A and, that the desired amount of standby is
possible for the battery intended for use with the HPF602ULADA.