Serviceable Sensor Cell Replacement - Honeywell Series 3000 MkIII Technical Manual

Gas detector
Table of Contents

Advertisement

SERIES 3000 MKIII TECHNICAL MANUAL

15.2 Serviceable sensor cell replacement

Caution:
For toxic sensors, remove the shorting clip from the bottom of the sensor prior
to installation. For O2 sensor, there is no shorting clip provided.
Caution: There are two types of sensor cap – teflon coated (black) and stainless steel.
Ensure that a teflon coated sensor cap is refitted for S3KXSF1SS (HF), XSR1SS (HCl)
and XSU1SS (F2) cells.
The serviceable sensor allows replacement of the cell inside the sensor. The cell can only be replaced
with the same type cell. To replace the cell follow the procedure below.
1. Enter the change sensor menu (see section 12).
2. Unscrew the weatherproof cover, loosen the sensor retainer locking screw and unscrew the sensor retainer.
3. Remove the old sensor by pulling without twisting.
4. Unscrew the sensor cap.
5. Remove the old cell by pulling without twisting.
6. Ensure the new cell is the same type as the old cell.
7. Plug the new cell into the sensor, taking care to align the sensor pins with the connector holes in the pcb.
8. Refit the sensor, taking care to align the sensor pins with the connector.
9. Refit the sensor cap, ensuring that it is the correct type. Refit the sensor retainer, tighten the locking
screw and refit the weatherproof cover.
10. Countdown time of up to 180 seconds (dependant on sensor type) is displayed.
11. Re-Calibrate the detector following the procedures in section 8.2.
New cell
Sensor Cap
Diagram 14: Serviceable Sensor Cell Replacement
Old cell
32
MAN0917_Issue 6_08/2015