Download Print this page

Philips GreenPerform RC160V Mounting Instruction page 2

Advertisement

Run Current (A)
Model
RC160V LED30S 840 W60L60 PSU CAU
RC160V LED30S 865 W60L60 PSU CAU
RC160V LED40S 840 W60L60 PSU CAU
RC160V LED40S 865 W60L60 PSU CAU
RC160V LED40S 840 W60L60 PSU OC CAU
RC160V LED40S 840 W30L120 PSU OC CAU
RC160V LED60S 840 W60L120 PSU OC CAU
The leakage current *(touch current or protective conductor current) of electrical circuit may be greatly dependent upon electrical supply
cables used such as its rating and length, proper connection of electrical supply cables to luminaires and
wiring connection topology of luminaires to the supply electrical circuit amongst other site conditions.
* In some cases referred to as Earth Leakage Current.
(a) HCB (Height clearance to building element)
Minimum distance as specified by the luminaire manufacturer between the top of the recessed luminaire and any building
element above it.
(b) MIC (Minimum insulation clearance)
Minimum distance as specified by the luminaire manufacturer between the top of the recessed luminaire and the building
insulation above it.
(c) SCB (Side clearance to building element)
Minimum distance between the side of the recessed luminaire and any building element as specified in AS/NZS 3000, or as
specified by the luminaire manufacturer.
(d) The minmum distance from the side of luminaire to any building insulation is 0 mm.
Please read this manual carefully before using the product.
1. For indoor use only.
2. Do not switch on before complete installation.
3. The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical
regulations or the national requirements.
4. The external flexible cable or cord of this luminaire cannot be replaced; if the cord is damaged, the luminaire
shall be destroyed.
5. The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire
shall be replaced.
6. Luminaire must not be used or stored in corrosive environment where hazardous materials such as Sulphur,
Chlorine, phthalates, etc, are present.
7. Risk of overheating or fire if the clearance distances are compromised.
8. This product complies with the CA90 rating as per AS/NZS 60598.2.2:2016. Care should be taken at installation to
allow adequate air flow for optimum lifetime performance.
This marking indicates that this product should not be disposed with other household wastes throughout the
EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it
responsibly to promote the sustainable reuse of material resources. To return your used device, please use the
return and collection systems or contact the retailer where the product was purchased. They can take this
product for environmental safe recycling.
Start (Inrush) Current(A)
Start Current Duration (μs) /
(@230V)
/ Ipeak (A)
T(@50% of Ipeak) (μs)
0.140
15.60
15.60
0.140
0.176
15.80
0.176
15.80
0.176
15.80
0.176
15.80
0.263
20.60
HCB =50 mm MIC =25 mm SCB =50 mm
* Touch current or
Maximum Number of
protective conductor
Luminaire on MCB 16A
current (mA)
206.00
206.00
181.00
<0.7
181.00
181.00
181.00
181.00
Maximum Number of
Luminaire on MCB 16A
Type B (pcs)
Type C (pcs)
30
50
30
50
30
50
30
50
30
50
30
50
20
40
Unit: mm

Advertisement

loading

This manual is also suitable for:

Greenperform rc160v led30s 840 w60l60 psu cauGreenperform rc160v led30s 865 w60l60 psu cauGreenperform rc160v led40s 840 w60l60 psu cauGreenperform rc160v led40s 865 w60l60 psu cauGreenperform rc160v led40s 840 w60l60 psu oc cauGreenperform rc160v led40s 840 w30l120 psu oc cau ... Show all