82 Technical data

Low harmonic filters

A passive low harmonic filter is designed to decrease the Total Harmonic Distortion of
incoming current (THDI) below 5%. Filter type Schaffner ECOsine™ is used with
ACQ810. Filters are dimensioned to achieve THDI requirement at nominal load. THD
increases at partial load and can be higher than 5% at no-load.

400 V / 50 Hz

Drive type
Frame
ACQ810-04-...
size
-02A7-4
A
-03A5-4
A
-04A9-4
A
-08A3-4
B
-11A0-4
B
-14A4-4
B
-021A-4
C
-028A-4
C
-035A-4
C
-040A-4
C
-053A-4
D
-067A-4
D
-080A-4
D
Nominal
400 V/ 50 Hz
ratings
P
Filter type
(kW)
1,1
1,5
*
2,2
4
FN 3410-10-44
5,5
FN 3410-13-44
7,5
FN 3410-16-44
11
FN 3410-24-33
15
FN 3410-32-33
18,5
FN 3410-38-33
22
FN 3410-45-34
30
FN 3410-60-34
37
FN 3410-75-35
45
FN 3410-90-35
Height
Width
Depth
mm
mm
-
-
400
170
400
170
430
210
520
250
520
250
520
250
590
300
590
300
750
320
750
320
Weight
mm
kg
-
-
190
13
190
14
210
21
280
27
280
31
280
35
300
45
300
54
300
65
300