4.6.3.4 Battery Parameters Screen

The configured number of batteries on the LCD must match the actual number.
When the actual number changes, change the configured number. If the
configured number is less than the actual number, the battery lifespan is
shortened. If the configured number is greater than the actual number, battery
leakage may cause a fire.
Issue 18 (2021-07-16)
Item
Description
Auto
Specifies whether to automatically check the
check bus
bus capacitance upon power-on and generate
capa.
capacitance failure warnings. If the value is
set to Enabled, the UPS startup time takes
additional 30 seconds to 180 seconds. This
parameter is configurable only after the
inverter is shut down.
Note: This parameter is configurable only for
the 15 kVA/20 kVA UPS.
Auto start
Specifies whether to automatically start
normal mode after the UPS connects to the
mains. This parameter is configurable only
after the inverter is shut down.
No
If this parameter is set to Disable, the No
battery
battery alarm is not reported. This
alarm
parameter automatically changes to Enable
after batteries are connected. This parameter
is configurable only when batteries are not
connected.
NOTE
If batteries are connected and you try to set this
parameter, the system displays a message
indicating that batteries are connected and this
parameter cannot be set.
EPO
Specifies whether to enable EPO. EPO is
enable
performed only when this parameter is set to
Enable and the EPO switch is triggered. This
parameter is configurable only for the
UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01.
CA UTION
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Def
Value
ault
Range
Val
ue
Ena
Disable
bled
d,
Enabled
Dis
Disable
able
d,
d
Enabled
Ena
Disable
bled
d,
Enabled
Dis
Disable
able
d,
d
Enabled
69