Alarm
Alarm
ID-
Name
Cause
ID
0001-01
Abnorm
al
mains
volt.
0001-02
Abnorm
al
mains
volt.
Issue 18 (2021-07-16)
Alarm
Alarm
Severit
Clearan
y
ce
Mode
Minor
Automa
tic
Minor
Copyright © Huawei Technologies Co., Ltd.
D
Impact on the System
● The rectifier transfers to
battery mode, which does
not affect the power
supply to loads.
● If no battery is installed,
the UPS shuts down.
D Alarm Handling
Alarm Handling
Handling Suggestion
Possible causes:
● The mains voltage
exceeds 280 V.
● The mains voltage is
less than 80 V.
● The mains frequency
is not in the range of
40 Hz to 70 Hz.
● The mains fuse is
abnormal.
Measures:
● Check whether the
mains input voltage
is less than 272 V. If
not, wait until the
mains recovers.
● Check whether the
mains input voltage
is greater than 88 V.
If the voltage is
greater than 88 V
and the Abnormal
mains volt. alarm
persists, the mains
fuse may be
abnormal. Replace
the faulty
equipment. If not,
143