Download Print this page
Honeywell 4219 Installation And Setup Manual

Honeywell 4219 Installation And Setup Manual

Wired zone expander module

Advertisement

Quick Links

GENERAL INFORMATION
This module adds up to eight end-of-line resistor supervised zones
to compatible control/communicators via the control's keypad
wiring.
The module may be mounted within the control's cabinet (if room
permits), or remotely. If mounted remotely, there are provisions to
tamper protect the unit.
supervised so that it cannot be disconnected from the keypad wiring
without detection by the control. If the wiring is cut, a tamper
alarm or signal will result, to indicate that this device (and possibly
other similarly connected devices) has become inoperative.
IMPORTANT: Some carbon monoxide detectors may not be
compatible with the Honeywell 4219 hardwire zone expanders.
When using carbon monoxide detectors in systems that support the
4219 zone expanders, install the detectors only on the basic
hardwire zones of the system control panel, and NOT on the zone
expanders.
INSTALLATION
1. Power should be disconnected before proceeding.
2.
Be sure to mount the 4219 before making any wire
connections.
When the module is mounted remotely, holes on the back of the
module's housing permit it to be mounted horizontally or vertically.
Wires can exit from the side or the breakout on the back of its
housing.
For tamper protection, attach the tamper magnet
(provided) (Figure 1) to the module inside cover. Place DIP switch
position #8 in the OFF position. Affix the connections label that
accompanies the module to the inside of the module's cover. When
the installation is complete, put the modules cover on. The magnet
attached to the cover, positioned near the reed switch, will cause a
tamper signal to be sent to the control if the cover is removed.
When the module is to be mounted inside the control's cabinet,
mount it horizontally to the raised tabs at the back of the cabinet.
Insert self-tapping screws (provided) in two adjacent raised tabs at
the back of the cabinet. Leave the heads projecting 1/8". Hang the
module on the screw heads via two slotted holes on the back of the
module's housing. When the module is installed in the control's
cabinet, it need not be tamper protected.
NOTE: For EN50131-3 compliance a tie-wrap must be secured
around the case of a remotely mounted 4219.
Apply tie-wrap around the case to the right of the large zone wire
opening (4-inch case width). This is in opposition of the tamper
switch and magnet.
Affix the connections label that accompanies the module to the
inside of the control's cover.
See the control's installation and setup guide for additional
information.
CONNECTIONS AND SETTINGS
Make protection zone connections to the module's 12-position
terminal block TB1. Each zone that is used must have a 2K-ohm
end-of-line resistor connected across the end of its loop, as shown
in Figure 2.
For CE installations ADEMCO N6361 EMI
C E
suppression bead is required. Refer to the
N6361 installation guide for wire routing
instructions.
INSTALLATION AND SETUP GUIDE
Communication to the module is
Wired Zone Expander Module
1. INSERT BOTTOM TABS FIRST.
2. ENGAGE TOP WITH CLIP.
Figure 1. Tamper Magnet Installation
If a zone is not programmed, the resistor need not be used. The
method of programming each zone for the type of alarm and
reporting code to the central monitoring station varies with the
control to which the module is connected. Refer to the Installation
and Setup Guide for that control unit.
Set the DIP Switch to one of 31 addresses, as shown in Figure 3, so
the control can identify the module and communicate with it
properly. The address to be set is determined by the particular
control to be used, and the control's installation instructions must
be consulted. As shipped, the DIP Switch is set for an address of
"0".
Zone A can be set for fast response time of 10ms to an open circuit,
if desired, by setting position 1 of the DIP Switch to "OFF". As
shipped, it is set to "ON" for a response time of 300ms, as shown in
the table below. All other module protection zones have a nominal
response time of 300ms.
Connections to the control's keypad wiring points can be made via
4-terminal block TB2 or the 4-pin plug (wire color connections are
the same).
SPECIFICATIONS
Physical
Electrical
Input Voltage:
Current:
6-7/16"W x 4-1/4"H x 1-1/4" D (163mm
x 108mm x 32mm)
12VDC (from control's remote keypad
connection points)
30mA
4219
4219-002-V0

Advertisement

loading

Summary of Contents for Honeywell 4219

  • Page 1 Honeywell 4219 hardwire zone expanders. When using carbon monoxide detectors in systems that support the 4219 zone expanders, install the detectors only on the basic hardwire zones of the system control panel, and NOT on the zone expanders.
  • Page 2 Cet appareil ne doit pas causer d' interferences nuisibles. (2) Cet appareil doit accepter toute interference reçue y compris les interferences causant une reception indésirable. ÊN8924V3nŠ For the latest warranty information, please go to: http://www.security.honeywell.com/hsc/resources/wa N8924V3 5/11 Rev. C 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright © 2008 Honeywell International Inc.
  • Page 3 CONTROL PANELS | ECP BUS 4219 Description: Compatibility: Addressable eight-zone expander for Honeywell All VISTA control panels that are compatible with ■ ECP bus addressable systems ECP bus zone expandability such as VISTA-20P and VISTA-21iP Product advantages: Not compatible with V-Plex control panels ■...