Electromagnetic Compatibility (Emc); Durability Information - Honeywell CENTRA LINE WEB-HMI Series User Manual

Capacitive touch screen
Table of Contents

Advertisement

USER'S MANUAL FOR HTML5 PANELS WEB-HMI CAPACITIVE TOUCH SCREEN
Radiated disturbance test
Electrostatic discharge
immunity test
Radiated, radio-frequency,
electromagnetic field
immunity test
Burst immunity test
Surge immunity test
Immunity to conducted
disturbances inducted by
radio-frequency field
Power frequency magnetic
field immunity test
Voltage dips, short
interruptions and voltage
variations immunity test
Test executed on the 230 Vac side of the Power Supply
Backlight service life
(LED type)
NOTE:
Extended use in environments where the surrounding air temperature is 40°C or higher may
degrade backlight quality/reliability/durability.

Electromagnetic Compatibility (EMC)

Table 7. Electromagnetic Compatibility (EMC)
Class A
8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
80 MHz ... 1 GHz, 10V/m
1.4 GHz ... 2 GHz, 3 V/m
2 GHz ... 2.7 GHz, 1 V/m
± 2 kV dc power port
± 1 kV signal line
± 0.5 kV dc power port (line to earth)
± 0.5 kV dc power port (line to line)
± 1 kV signal line (line to earth)
0.15 ... 80 MHz, 10 V
Enclosure, 50/60 Hz, 30 A/m
Port: AC mains; Level:
100% duration:
40% duration:
70% duration:
Phase:
Port: DC mains; Level:
0% duration:
Table 8. Durability information
40 000 Hrs. or more
(LED type) (Time of continuous operation until the brightness of the
backlight reaches 50% of the rated value when the surrounding air
temperature is 25°C) - see note below.
11
CISPR 22
CISPR 16-2-3
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8
1 cycle and 250 cycles (50Hz);
1 cycle and 300 cycles (60Hz);
10 cycles (50Hz);
12 cycles (60Hz);
25 cycles (50Hz);
30 cycles (60Hz);
0°...180°
EN 61000-4-11
10 ms, 20 interruptions in 1 s

Durability information

EN2Z-1070GE51 R0920

Advertisement

Table of Contents
loading

Table of Contents