Figure 5-9 Setting of three-line mode 2
As shown in the preceding figure, if SB1 is ON, the AC drive starts running when SB2 is
pressed to be ON; the AC drive instructs forward rotation when K is OFF and instructs reverse
rotation when K is ON. The AC drives stops immediately after SB1 becomes OFF. During normal
startup and running, SB1 must remain ON. The AC drive's running state is determined by the final
actions of SB1, SB2 and K.
Function
Code
P4-12
It is used to adjust the rate of change of frequency when the frequency is adjusted by means of
terminal UP/DOWN.
If P0-22 (Frequency reference resolution) is 2, the setting range is 0.001–65.535 Hz/s.
If P0-22 (Frequency reference resolution) is 1, the setting range is 0.01–655.35 Hz/s.
Function
Code
P4-13
Corresponding setting of AI curve 1
P4-14
P4-15
Corresponding setting of AI curve 1
P4-16
P4-17
These parameters are used to define the relationship between the analog input voltage and the
Parameter Name
Terminal UP/DOWN rate
Parameter Name
AI curve 1 minimum input
minimum input
AI curve 1 maximum input
maximum input
AI1 filter time
Setting Range
0.01–65.535 Hz/s
Setting Range
0.00 V to P4-15
-100.00%–100.0%
P4-13 to 10.00 V
-100.00%–100.0%
0.00–10.00s
109
Description of Function Codes
PE6000
Default
1.00 Hz/s
Default
0.00 V
0.0%
10.00 V
100.0%
0.10s