GE EntelliPro ES Series Installation And Instruction Manual
GE EntelliPro ES Series Installation And Instruction Manual

GE EntelliPro ES Series Installation And Instruction Manual

Motor controller
Table of Contents

Advertisement

Quick Links

GE Industrial Solutions
 
 
 
 
 
 
EntelliPro ES Motor Controller
 
Installation and Instruction Manual
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
EntelliPro ES Revision: 3.0
Manual Part Number: GEH-6000
Copyright© 2011 GE Industrial Solutions

Advertisement

Table of Contents
loading

Summary of Contents for GE EntelliPro ES Series

  • Page 1                                                       EntelliPro ES Revision: 3.0 Manual Part Number: GEH-6000 Copyright© 2011 GE Industrial Solutions...
  • Page 2 This page was intentionally left blank...
  • Page 3: Table Of Contents

      GE Industrial Solutions               Table of Contents     Chapter 1: Introduction   Overview ........................................1.1   1.1.1 Warnings, cautions, notes, and references....................... 1.2   1.1.2 Definitions....................................1.3   1.1.3 Description of the EntelliPro ES Motor Control Module ..................1.4  ...
  • Page 4   TABLE OF CONTENTS     2.1.2 Electrical installation................................2.6   2.1.2.1 Power supply connection ..........................2.6   2.1.2.2 Communication connection ........................... 2.7   2.1.2.3 Thermistor connection ............................2.7   2.1.2.4 Phase Current Connection ..........................2.8   2.1.2.5 Input/output connection ..........................2.8  ...
  • Page 5 TABLE OF CONTENTS     Chapter 3: Motor Protection   Thermal Overload ....................................... 3.1   3.1.1 Unbalance and phase-loss biasing..........................3.2   3.1.2 Hot/cold biasing ..................................3.2   3.1.3 Overload curve ..................................3.3   3.1.4 Cooling rate ....................................3.6   3.1.5 Overload protection n-times reset ..........................
  • Page 6   TABLE OF CONTENTS     Profibu s ........................................4.33   4.2.1 Definitions....................................4.33   4.2.2 Profibus System concept ..............................4.34   4.2.3 Profibus Interface................................. 4.35   Profibus termination................................4.36 4.2.4   4.2.5 Profibus DP-parameterization ............................4.36   4.2.6 Communication set up and station addresses ....................... 4.36  ...
  • Page 7   TABLE OF CONTENTS   5.3.2.11 Modbus setting panel ............................. 5.26   5.3.2.12 Char (Characteristic) panel ........................... 5.27   5.3.2.13 Diagnostic panel ..............................5.27   5.3.2.14 Measure panel ..............................5.27   5.3.2.15 Alarm panel................................5.28   5.3.3 Debug panel ..................................... 5.28  ...
  • Page 8  This page was intentionally left blank  ...
  • Page 9: Chapter 1: Introduction

                        CHAPTER 1: INTR ODUCTION   GE Industrial Solutions             EPOS Motor Management System   Chapter 1: Introduction       This chapter provides an overview of the EPOS Motor Control System. Additional details are provided in subsequent chapters.
  • Page 10: Warnings, Cautions, Notes, And References

    Features may be described herein that are not present in all hardware and software systems. GE Industrial Solutions assumes no obligation of notice to holders of this document with respect to changes subsequently made.
  • Page 11: Definitions

    SEC, s seconds SEV 32, SEN GE Neumuenster switchboard systems sum of squares spst single pole-single throw transmission control protocol percent unbalance EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL...
  • Page 12: Description Of The Entellipro Es Motor Control Module

      CHAPTER 1: INTR ODUCTION   1.1.3 Description of the EntelliPro ES Motor Control Module   The EntelliPro ES is used in conjunction with CTs in branch-drawout systems. This system consists of LEDs, fuses, contactors, and additional components required for the control and switching of the branch. The EntelliPro ES includes the following input/output capabilities:  ...
  • Page 13   CHAPTER 1: INTR ODUCTION     Entellipro ES3 DOL standard configuration        EntelliPro ES5 DOL standard configuration Figure 1-1: Single-line diagram   EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL  ...
  • Page 14: Entellipro Es Order Code

      CHAPTER 1: INTR ODUCTION   1.1.4 EntelliPro ES order code   Five unique catalog numbers are offered: EntelliPro ES3 DP 2 0 EntelliPro ES3 DP 3 0 EntelliPro ES5 DP 2 2 EntelliPro ES5 DP 2 3 EntelliPro ES5 DP 3 3  ...
  • Page 15   CHAPTER 1: INTR ODUCTION     Table 1-1 shows features and protections available for the five catalogs.       EntelliPro EntelliPro EntelliPro EntelliPro EntelliPro Features / Protections ES3 DP 2 0 ES3 DP 3 0 ES5 DP 2 2 ES5 DP 2 3 ES5 DP 3 3 24Vdc Supply input...
  • Page 16: Entellipro Es Current Transformer Definition

      CHAPTER 1: INTR ODUCTION     1.1.5 EntelliPro ES Current Transformer Definition There are three items that must be considered when configuring the motor load level of the EntelliPro ES. The i tems to consider are the transformer type, the number of primary windings, and the EntelliPro ES full load current setting (FLA).  ...
  • Page 17: Specifications

      CHAPTER 1: INTR ODUCTION     1.2 Specifications   NOTE: Specifications are subject to change without notice.     1.2.1 Protection Specifications   Overload Fault (Thermal Model) IEC Class curves ..............5, 10, 15, 20, 25, 30, 35, 40 (IEC 60947) Thermal overload pickup ..........1.20 Motor full-load current (FLA) ..........1/6 Ict to Ict in steps of 0.1  ...
  • Page 18: Metering And Monitoring Specifications

    CHAPTER 1: INTR ODUCTION   Thermistor Sensor types: ................PTC (RHOT = 3.6 kΩ, RRESET = 1.5 kΩ) Time delay................500ms Elements ...................fault (trip) and warning (alarm) - warning not valid for ATEX Connection ................1, 3 or 6 thermistors in series Standard .................IEC 34-11-12 Max cable length to detect short ........AWG 14 = 266m AWG 16 = 160m AWG 20 = 70m...
  • Page 19   CHAPTER 1: INTR ODUCTION Phase Current Inputs   Range....................8A CT: 1.34–8.0A (10 x CT) 32A CT: 5.30–32A (10 x CT) 64A CT: 10.6–64A (10 x CT) 630A CT: 105–630A (10 x CT) Frequency .................47.5 to 63.0 Hz Accuracy...................with external CT: ±5% / direct: ±2%  ...
  • Page 20: Output Specifications

      CHAPTER 1: INTR ODUCTION     1.2.4 Output specifications   4 - 20 mA Output   Accuracy...................±1% from displayed RMS   Motor Contact Relays Configuration................electromechanical SPST Contact material ..............silver alloy Operate time................10ms Minimum contact load ............10mA at 5Vdc / 30Vdc Continuous current ..............5A at 240Vac  ...
  • Page 21: Power Supply Specifications

      CHAPTER 1: INTR ODUCTION     1.2.5 Power supply specifications   This section lists the specifications for the power supply. The power consumptions of the EntelliPro modules are listed in Table 1-3.     Nominal..................24Vdc (24Vdc version)/140mA (max) 110/240Vac (120/240Vac version)/60mA (max)  ...
  • Page 22: Testing And Certification

      CHAPTER 1: INTR ODUCTION   1.2.7 Testing and certification   Test Reference Standard Test Level   Dielectric voltage withstands ..........1.5kV Impulse voltage withstand ..........EN60255-5 Electrostatic discharge............EN61000-4-2/IEC60255-22-2 Level 4   RF immunity ................EN61000-4-3/IEC60255-22-3 Level 3   Fast transient disturbance ..........EN61000-4-4/IEC60255-22-4 Class A Surge immunity ....
  • Page 23: Approvals

      CHAPTER 1: INTR ODUCTION 1.2.8 Approvals   Applicable Council Directive According to Low-Voltage Directive EN60255-5, EN61010-1   CE compliance: EMC Directive EN50263 / EN61000-6-2/ EN61000-6-4   ISO: Manufactured under a registered quality program – ISO9001   ROSH compliance:   1.2.9 Physical specifications  ...
  • Page 24: Entellipro Cp3/Cp5 Hmi

    CHAPTER 1: INTR ODUCTION   1.3 EntelliPro CP3/CP5 HMI   The EntelliPro CP3 and CP5 HMI, shown in Figure 1-3, is a microprocessor-based device that connects to an industry- standard Modbus RTU on RS-485 wiring.   The HMI is factory programmed to communicate with the EntelliPro ES devices in a MCC environment in order to provide a convenient station for viewing metering, status and setting information and controlling contactors operations.
  • Page 25: Winesg Configuration Tool

      CHAPTER 1: INTR ODUCTION 1.4 WinESG Configuration Tool   WinESG is a Profibus-based HMI used with the EPOS System to configure the EntelliPro ES. It provides the capability for a full parameterization and configuration of the EntelliPro ES devices. In addition it supports metering, event log, analog data retrieval, and downloading of custom logic application.
  • Page 26: Chapter 2: Installation / Configuration

    CHAPTER 2: INSTALL ATION/CONFIGURATION       GE Industrial Solutions           EPOS Motor Management System   Chapter 2: Installation / Configuration         2.1 Installation and initial operating   The EntelliPro ES is an intelligent motor control relay that is mainly installed in low voltage systems for industrial usage.
  • Page 27: Mechanical Installation

      CHAPTER 2: INSTALL ATION/CONFIGURATION 2.1.1 Mechanical installation   This section describes the mechanical installation of the EPOS system, including dimensions for mounting and information on module withdrawal and insertion.     2.1.1.1 Dimensions   The EntelliPro ES is packaged in a modular arrangement . Figure 2-1 shows the dimensions of the EntelliPro ES. NOTE: All dimensions are in mm.
  • Page 28: Product Identification

      EntelliPro ES5 DP 2 2 defines the catalog number of the device. Ref-No. is a GE defined number for the unit . Relays 41, 43, and 45 are motor relays rated AC-15 5A/240Vac and DC-13 2.5A/24Vdc Supply Voltage A1+ A2-: 24V DC, indicates that the power supply for this unit is 24Vdc.
  • Page 29: Mounting

      CHAPTER 2: INSTALL ATION/CONFIGURATION     2.1.1.3 Mounting   CAUTION: To avoid the potential for personal injury from fire hazards, ensure the unit is mounted in a safe location and/or within an appropriate enclosure. Unit must be un-powered and all connectors removed during installation.
  • Page 30: Entellipro Es Connector Terminal Identification

    CHAPTER 2: INSTALL ATION/CONFIGURATION         2.1.1.4 EntelliPro ES Connector terminal identification   The EntelliPro ES connectors pinout and description are shown in Table 2-3   Connector Number Description Digital Input ( 24Vdc + or 110/230vac) Digital Input ( 24Vdc + or 110/230vac) Digital Input ( 24Vdc + or 110/230vac) Digital Input ( 24Vdc + or 110/230vac) Digital Input ( 24Vdc + or 110/230vac)
  • Page 31: Electrical Installation

      CHAPTER 2: INSTALL ATION/CONFIGURATION       2.1.2 Electrical installation   This section describes the electrical installation of the EntelliPro ES motor relay.     CAUTION: EntelliPro ES is not to be used in any way other than described in this manual.  ...
  • Page 32: Communication Connection

    CHAPTER 2: INSTALL ATION/CONFIGURATION     2.1.2.2 Communication connection   Two two-wire RS485 ports (Modbus RTU and Profibus) are available. Up to 32 EntelliPro ES relays can be daisy- chained together on a communication channel without exceeding the driver capability. Commercially available repeaters can be used to add more than 32 relays.
  • Page 33   CHAPTER 2: INSTALL ATION/CONFIGURATION       Digital Input Mapping Active High Signal Active Low Signal ON1 Command ON1 Command ON2 Command ON2 Command OFF Command OFF Command Main Contactor 1 Feedback Main Contactor 1 Feedback MCCB ON Feedback MCCB ON Feedback Main Contactor 2 Feedback Main Contactor 2 Feedback...
  • Page 34: 4-20Ma Output Connection

    CHAPTER 2: INSTALL ATION/CONFIGURATION         2.1.2.6 4-20mA output connection   Refer to Figure 2-4, Item G, for typical 4-20mA connections.     2.1.2.7 Dielectric strength testing   It may be required to test a complete motor starter for dielectric strength (“flash” or “HIPOT”) with the EntelliPro ES Installed.
  • Page 35: Motor Control Configuration

      CHAPTER 2: INSTALL ATION/CONFIGURATION     2.2 Motor Control Configuration   This section is split into two parts; one for an expert integrator requiring a full knowledge of all parameters and configuration and the other requiring minimal knowledge to configure the EntelliPro ES.  ...
  • Page 36: Local And Remote Sources Listing

    CHAPTER 2: INSTALL ATION/CONFIGURATION     Fixed Local Control commands (start, stop, reset etc) can only be issued by local sources. See section 2.2.1.1 for the local source listing.   NOTE: If the hardwire connection is set to 1-bit (level) then locals CP / Modbus RTU and WinESG are disabled.
  • Page 37   CHAPTER 2: INSTALL ATION/CONFIGURATION         Register Description Bit Definition Bit0 thru Bit2 defines the Remote source       Bit0 – Bit 2 0 - None   1 - Profibus Class 1   2- Modbus   3-Hardwire Bit4 thru Bit6 defines the source that controls the local/  ...
  • Page 38: Motor Control Via Winesg

          2.2.1.4 Motor Control via WinESG   Similar configuration as above can be done using GE configuration software WinESG. Refer to WinESG parameterization /control panel on Chapter 5.     2.2.1.5 Motor Control via Profibus Class 1  ...
  • Page 39: Control Variant 1 Configuration

      CHAPTER 2: INSTALL ATION/CONFIGURATION       Control Variant 1 Configuration   Profibus Class1 master is enabled, configured as remote source, and has the control of the “local- remote-off” switch. Profibus Class1 bus failure detection is enabled. On Class1 bus failure, switch position is forced to local position.
  • Page 40: Control Variant 2 Configuration

      CHAPTER 2: INSTALL ATION/CONFIGURATION         Control Variant 2 Configuration   Profibus Class1 master is enabled, configured as remote source, and hardwire has the control of the “local- remote-off” switch. Profibus Class1 bus failure detection is enabled. Class1 bus failure does not affect switch position. Modbus failure has affected the on switch position.
  • Page 41: Control Variant 3 Configuration

      CHAPTER 2: INSTALL ATION/CONFIGURATION     Control Variant 3 Configuration   Profibus Class1 master is enabled, configured as remote source, and Modbus has the control of the “local-remote-off” switch. Profibus Class1 bus failure detection is enabled. On Class1 bus failure, has no effect on the switch position.
  • Page 42: Control Variant 4 Configuration

    CHAPTER 2: INSTALL ATION/CONFIGURATION         Control Variant 4 Configuration   Profibus Class1 master is disabled. Modbus is configured as remote source and has the control of the “local- remote-off” switch. Profibus Class1 bus failure detection is disabled. On Modbus` failure the switch position is forced to local position Refer to figure 2-8  ...
  • Page 43: Control Variant 5 Configuration

      CHAPTER 2: INSTALL ATION/CONFIGURATION     Control Variant 5 Configuration   Profibus Class1 master is disabled. Modbus is configured as remote source and hardwire has the control of the “local-remote-off” switch. Profibus Class1 bus failure detection is disabled. Modbus failure has no effect on switch position.
  • Page 44: Control Variant 6 Configuration

    CHAPTER 2: INSTALL ATION/CONFIGURATION         Control Variant 6 Configuration   Profibus Class1 master is enabled. Any local sources (Modbus, WinESG, Hardwire) if enabled, can control the motor operation (ON/OFF). Profibus Class1 bus failure detection is disabled. Refer to Figure 2-10.  ...
  • Page 45: Motor Starter Configuration

      Actuator with limit or torque switch     In additional customers can order customized motor starter arrangement by providing GE with desired logic control for inputs, outputs and timers.     Customer can change pre-defined configurations of any motor starter if the default configuration is not NOTE: selected.
  • Page 46: Motor Starter Type - Full-Voltage Non-Reversing Starter

    CHAPTER 2: INSTALL ATION/CONFIGURATION           2.3.1 Motor Starter Type - Full-voltage non-reversing starter   The typical full-voltage non-reversing starter type is a full voltage or across the line non-reversing starter. Before the motor can be turned ON the “drawer ready switch” must be active. In order to activate the “drawer ready switch”...
  • Page 47   CHAPTER 2: INSTALL ATION/CONFIGURATION If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 48 CHAPTER 2: INSTALL ATION/CONFIGURATION     For EntelliPro ES3 types: Input 99 is mapped to contactor 1 feedback - active high Input 98 is mapped to external supervision - active low. Input 97 is mapped to control circuit feedback - active low Input 96 is mapped to main circuit feedback - active low Input 95 is mapped to emergency stop...
  • Page 49   CHAPTER 2: INSTALL ATION/CONFIGURATION NOTE: if default configuration box is left un-checked, the user will have the ability to change the mapping and other parameters. Refer to Tables 2-6 and 2-7 for the complete default configuration of the full-voltage non-reversing starter motor starter. Figures 2-11 and 2-12 show typical full-voltage non- reversing starter wiring diagrams for EntelliPro ES3 and EntelliPro ES5.
  • Page 50 CHAPTER 2: INSTALL ATION/CONFIGURATION     Figure 2-12: EntelliPro ES5 full-voltage non-reversing starter (DOL) wiring diagram       2.25 EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL  ...
  • Page 51: Motor Starter Type - Full-Voltage Reversing Starter

      CHAPTER 2: INSTALL ATION/CONFIGURATION 2.3.2 Motor Starter Type - Full-voltage reversing starter   The typical full-voltage reversing starter is a full voltage or across the line reversing starter. Before the motor can be turned ON the “drawer ready switch” must be active. In order to activate the “drawer ready switch”...
  • Page 52 CHAPTER 2: INSTALL ATION/CONFIGURATION     If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 53   CHAPTER 2: INSTALL ATION/CONFIGURATION If the default configuration and the DOL reverse typical are selected in the WinESG parameterization/information shown in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to 0x1,the inputs and outputs are mapped as below: For EntelliPro ES3 types: Input 99 is mapped to contactor 1 feedback...
  • Page 54 CHAPTER 2: INSTALL ATION/CONFIGURATION     Output 41 is mapped to contactor 1 Output 43 is mapped to contactor 2 Output 45 is mapped to ATEX redundancy contactor Output 22 is mapped to local control Output 23 is mapped to ON1 feedback Output 24 is mapped to ON2 feedback Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority) Output 26 is mapped to failure...
  • Page 55   CHAPTER 2: INSTALL ATION/CONFIGURATION   Figure 2-14: EntelliPro ES5 Full-voltage reversing starter wiring diagram EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2.30  ...
  • Page 56: Motor Starter Type Star-Delta Open Transition Starter

    CHAPTER 2: INSTALL ATION/CONFIGURATION         2.3.3 Motor Starter Type Star-delta open transition starter   The typical Star-delta open transition starter is a reduced voltage starter. Before the motor can be turned ON the “drawer ready switch” must be active. In order to activate the “drawer ready switch”...
  • Page 57   CHAPTER 2: INSTALL ATION/CONFIGURATION If Fixed local is selected as a controlling device, any source assigned as local can control the motor (ON/OFF). If Fixed remote is selected as a controlling device, only the remote source can control the motor (ON/OFF). NOTE: only one control (local or remote) can be enabled at a time.
  • Page 58 CHAPTER 2: INSTALL ATION/CONFIGURATION     If the default configuration and the Star delta typical are selected in the WinESG parameterization/information panel shown in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to 0x2,the inputs and outputs are mapped as below: For EntelliPro ES3 types: Input 99 is mapped to contactor 1 feedback...
  • Page 59   CHAPTER 2: INSTALL ATION/CONFIGURATION Output 41 is mapped to contactor 1 Output 43 is mapped to contactor D Output 45 is mapped to contactor Y Output 22 is mapped to ATEX redundancy contactor Output 23 is mapped to ON1 feedback Output 24 is mapped to local control Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority) Output 26 is mapped to failure...
  • Page 60 CHAPTER 2: INSTALL ATION/CONFIGURATION         Figure 2-16: EntelliPro ES5 Star-delta open transition starter wiring diagram       2.35 EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL  ...
  • Page 61: Motor Starter Type - Star-Delta Reverse Open Transition Starter

      CHAPTER 2: INSTALL ATION/CONFIGURATION 2.3.4 Motor Starter Type - Star-delta reverse open transition starter   The typical Star-delta reverse open transition starter is a reduced voltage starter. Before the motor can be turned ON the “drawer ready switch” must be active. In order to activate the “drawer ready switch”...
  • Page 62 CHAPTER 2: INSTALL ATION/CONFIGURATION     If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 63   CHAPTER 2: INSTALL ATION/CONFIGURATION When the “Y contactor maximum ON time” timer expires or the current has fallen below a pre-defined value, set by threshold 4 (typical specific) in WinESG parameterization/device setting panel or Modbus function code 6 register 21, the EntelliPro contact output relay 23 will de-energize; contactor Y opens, opening the Wye connection.
  • Page 64 CHAPTER 2: INSTALL ATION/CONFIGURATION     Output 41 is mapped to contactor 1 Output 43 is mapped to contactor D Output 45 is mapped to contactor 2 Output 22 is mapped to ATEX redundancy contactor Output 23 is mapped to Y feedback Output 24 is mapped to local control Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority) Output 26 is mapped to failure...
  • Page 65: Motor Starter Type - Soft Starter Type

      CHAPTER 2: INSTALL ATION/CONFIGURATION 2.3.5 Motor Starter Type – Soft starter type The typical soft starter is used with an external soft starter that ramps the motor speed up to start and down to stop. Once the motor is ramped up, the soft starter can be bypassed. Before the motor can be turned ON the “drawer ready switch”...
  • Page 66 CHAPTER 2: INSTALL ATION/CONFIGURATION     If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 67   CHAPTER 2: INSTALL ATION/CONFIGURATION If the “soft stop time activated” parameter is set, the by-pass relay 43 will open immediately after the OFF command is received, and after the soft stop timer expires, output relay 41 opens, K1 opens, and removes power to the soft starter and motor.
  • Page 68 CHAPTER 2: INSTALL ATION/CONFIGURATION     Input 17 is mapped to safety circuit - active low Input 18 is mapped to mode switch local - active high Input 19 is mapped to mode switch remote - active high Output 41 is mapped to contactor 1 Output 43 is mapped to by-pass contactor Output 45 is mapped to ATEX redundancy contactor Output 22 is mapped to local control...
  • Page 69   CHAPTER 2: INSTALL ATION/CONFIGURATION     Figure 2-19: EntelliPro ES5 softstarter starter wiring diagram     EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2.44  ...
  • Page 70 CHAPTER 2: INSTALL ATION/CONFIGURATION     2.3.6 Motor Starter Type - Soft starter reverse type The typical soft starter reverse starter type is used with an external soft starter that ramps the motor speed up to start and down to stop. Once the motor is started, the soft starter can be bypassed. Before the motor can be turned ON the “drawer ready switch”...
  • Page 71   CHAPTER 2: INSTALL ATION/CONFIGURATION If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 72 CHAPTER 2: INSTALL ATION/CONFIGURATION     If the “soft stop time activated” parameter is set, the by-pass relay 45 will open immediately after the OFF command is received, and after the soft stop timer expires, output relay 41 opens, K1 opens, and removes power to the soft starter and motor.
  • Page 73   CHAPTER 2: INSTALL ATION/CONFIGURATION For EntelliPro ES3 types: Input 99 is mapped to forward contactor 1 feedback - active high Input 98 is mapped to reverse contactor 2 feedback - active low Input 97 is mapped to by-pass contactor feedback - active high Input 96 is mapped to up-to-speed feedback - active high...
  • Page 74 CHAPTER 2: INSTALL ATION/CONFIGURATION     NOTE: If default configuration box is left un-checked, the user will have the ability to change the mapping and other parameters.   NOTE: Ensure soft starter is located before contactor.     Refer to Tables 2-6 and 2-7 for the complete input, output , timer and control configurations of the reverse soft starter.
  • Page 75   CHAPTER 2: INSTALL ATION/CONFIGURATION   Figure 2-21: EntelliPro ES5 reverse softstarter starter wiring diagram       EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2.50  ...
  • Page 76: Breaker Control

    CHAPTER 2: INSTALL ATION/CONFIGURATION     2.3.7 Breaker Control The typical breaker control starter type is used to control opening and closing of the breaker. Before the breaker can be turned ON the “drawer ready switch” must be active. In order to activate the “drawer ready switch”...
  • Page 77   CHAPTER 2: INSTALL ATION/CONFIGURATION If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 78 CHAPTER 2: INSTALL ATION/CONFIGURATION     CAUTION: EntelliPro ES should not be used as a means to provide instantaneous breaker protection. If the default configuration and the breaker typical are selected in the WinESG parameterization/information panel shown in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to 0x8,the inputs and outputs are mapped as below: For EntelliPro ES3 types: Input 99 is mapped to Breaker ON feedback...
  • Page 79   CHAPTER 2: INSTALL ATION/CONFIGURATION Output 41 is mapped to breaker ON Output 43 is mapped to breaker OFF Output 45 is mapped to reset Output 22 is mapped to local control Output 23 is mapped to ON1 command (start) Output 24 is mapped to warning Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority) Output 26 is mapped to failure...
  • Page 80 CHAPTER 2: INSTALL ATION/CONFIGURATION         Figure 2-23: EntelliPro ES5 Breaker control starter wiring diagram     2.55 EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL  ...
  • Page 81: Motor Starter Type - Dahlander Starter Type

      CHAPTER 2: INSTALL ATION/CONFIGURATION 2.3.8 Motor Starter Type - Dahlander starter type   The typical Dahlander starter type is a full voltage across the line two-speed starter. Before the motor can be turned ON the “drawer ready switch” must be active. In order to activate the “drawer ready switch”...
  • Page 82 CHAPTER 2: INSTALL ATION/CONFIGURATION     If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 83   CHAPTER 2: INSTALL ATION/CONFIGURATION Refer to Tables 2-6 and 2-7 for the complete input, output, timer and control configurations of the Dahlander motor starter. Figures 2-24 and 2-25 show typical Dahlander starter diagrams for EntelliPro ES3 and EntelliPro ES5. If the default configuration and the Dahlander typical are selected in the WinESG parameterization/information panel shown in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to 0x6,the inputs and outputs are mapped as below:...
  • Page 84 CHAPTER 2: INSTALL ATION/CONFIGURATION     Input 18 is mapped to mode switch local - active high Input 19 is mapped to mode switch remote - active high Output 41 is mapped to contactor 1 Output 43 is mapped to contactor 2 Output 45 is mapped to contactor Y Output 22 is mapped to ATEX redundancy contactor Output 23 is mapped to slow ON1 feedback...
  • Page 85   CHAPTER 2: INSTALL ATION/CONFIGURATION   Figure 2-25: EntelliPro ES5 Dahlander starter wiring diagram     EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2.60  ...
  • Page 86: Motor Starter Type - Pole Changer Starter Type

    CHAPTER 2: INSTALL ATION/CONFIGURATION     2.3.9 Motor Starter Type – Pole changer starter type The typical Pole changer starter type is a full voltage across the line two-speed starter. Before the motor can be turned ON the “drawer ready switch” must be active. In order to activate the “drawer ready switch”...
  • Page 87   CHAPTER 2: INSTALL ATION/CONFIGURATION If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 88 CHAPTER 2: INSTALL ATION/CONFIGURATION     If the default configuration and the pole changer typical are selected in the WinESG parameterization/information panel shown in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to 0x7,the inputs and outputs are mapped as below: For EntelliPro ES3 types: Input 99 is mapped to contactor 1 feedback...
  • Page 89   CHAPTER 2: INSTALL ATION/CONFIGURATION Output 22 is mapped to local control Output 23 is mapped to slow ON1 feedback Output 24 is mapped to fast ON2 feedback Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority) Output 26 is mapped to failure NOTE: If default configuration box is left un-checked, the user will have the ability to change the mapping and...
  • Page 90 CHAPTER 2: INSTALL ATION/CONFIGURATION         Figure 2-27: EntelliPro ES5 Pole changer starter wiring diagram     2.65 EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL  ...
  • Page 91: Solenoid Valve Type

      CHAPTER 2: INSTALL ATION/CONFIGURATION 2.3.10 Solenoid valve type Before the solenoid can be activated the “drawer ready switch” must be active. In order to activate the “drawer ready switch” the following must be done:  All faults and device errors must be cleared using WinESG control panel, Modbus function code 6 registers 65 thru 106 depending on the fault type, Profibus class 1 telegram B2701, or hardwire (make sure an input is mapped to “reset alarm”...
  • Page 92 CHAPTER 2: INSTALL ATION/CONFIGURATION     If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor (ON/OFF).
  • Page 93   CHAPTER 2: INSTALL ATION/CONFIGURATION When limit switch 2 is reached (input 96 on EntelliPro ES3 and input 19 on EntelliPro ES5) a “switch position” warning or a fault will be generated. CAUTION: The phase system in WinESG parameterization\device settings panel shown in the illustration below or Modbus function code 6 register 5 must be set to 1 phase if the system is a 1 phase system for proper overload protection.
  • Page 94 CHAPTER 2: INSTALL ATION/CONFIGURATION     For EntelliPro ES5 types: Input 99 is mapped to contactor 1 feedback - active high Input 98 is mapped to drawer in test position - active high Input 97 is mapped to drawer in operation mode - active high Input 96 is mapped to mode switch local - active high...
  • Page 95   CHAPTER 2: INSTALL ATION/CONFIGURATION   Figure 2-28: EntelliPro ES3 Solenoid valve wiring diagram EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2.70  ...
  • Page 96 CHAPTER 2: INSTALL ATION/CONFIGURATION       Figure 2-29: EntelliPro ES5 Solenoid valve wiring diagram     2.71 EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL  ...
  • Page 97: Actuator Type

      CHAPTER 2: INSTALL ATION/CONFIGURATION 2.3.11 Actuator type The typical actuator type is typically used on applications where a motor moves a valve between two endpoints – open and closed. Before the motor can be turned ON the “drawer ready switch” must be active. In order to activate the “drawer ready switch”...
  • Page 98 CHAPTER 2: INSTALL ATION/CONFIGURATION     If Fixed local is selected as a controlling device, any source assigned as local can control the motor (ON/OFF). If Fixed remote is selected as a controlling device, only the remote source can control the motor (ON/OFF). Only one control (local or remote) can be enabled at a time.
  • Page 99   CHAPTER 2: INSTALL ATION/CONFIGURATION Only the following six configurations are valid: Configuration Limit switch Torque switch Switch OFF Switch OFF at Switch OFF activated activated at limit switch torque switch at current threshold Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled...
  • Page 100 CHAPTER 2: INSTALL ATION/CONFIGURATION     When an OFF command is received, EntelliPro contact output relays 41 or 43 open, contactors K1 and K2 close, and the motor stops. The starter logic is fully symmetrical between right and left. Configuration 2 operation - limit switched activated and switch OFF at current threshold: In order to start the motor on either direction, the limit switch 1 reached and limit switch 2 reached inputs (inputs 96 and 97on EntelliPro ES3 and inputs 18 and 19 on EntelliPro ES5) must NOT be active at the same time.
  • Page 101   CHAPTER 2: INSTALL ATION/CONFIGURATION Configuration 3 operation - limit switched activated, torque switch activated and switch OFF at limit switch: In order to start the motor on either direction, limit switch 1 reached and limit switch 2 reached inputs (inputs 96 and 97on EntelliPro ES3 and inputs 18 and 19 on EntelliPro ES5) must NOT be active at the same time.
  • Page 102 CHAPTER 2: INSTALL ATION/CONFIGURATION     Configuration 4 operation - limit switched activated, torque switch activated and switch OFF at torque switch: In order to start the motor on either direction, limit switch 1 reached and limit switch 2 reached inputs (inputs 96 and 97on EntelliPro ES3 and inputs 18 and 19 on EntelliPro ES5 must NOT be active at the same time.
  • Page 103   CHAPTER 2: INSTALL ATION/CONFIGURATION Configuration 5 operation - limit switched activated disabled, torque switch activated disabled and switch OFF at current threshold: When an ON1 right command is received, contactor K1, controlled by EntelliPro output relay 41, will close, provided the motor is in the off state and the drawer ready switch is active, which will start the motor in a right direction.
  • Page 104 CHAPTER 2: INSTALL ATION/CONFIGURATION     Configuration 6 operation - torque switch activated and switch OFF at torque switch: In order to start the motor on either direction, the Torque switch 1 reached and torque switch 2 reached inputs (inputs 14 and 15 on EntelliPro ES5) must NOT be active at the same time.
  • Page 105   CHAPTER 2: INSTALL ATION/CONFIGURATION For EntelliPro ES3 types: Input 99 is mapped to contactor 1 feedback - active high Input 98 is mapped to contactor 2 feedback - active low Input 97 is mapped to limit switch 1 reached - active low Input 96 is mapped to limit switch 2 reached - active low...
  • Page 106 CHAPTER 2: INSTALL ATION/CONFIGURATION     Refer to Tables 2-6 and 2-7 for the complete input, output, timer and control configurations of an actuator starter. Figures 2-30 and 2-31 show typical actuator starter diagrams for EntelliPro ES3 and EntelliPro ES5. Figure 2-30: EntelliPro ES3 Actuator wiring diagram 2.81 EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL...
  • Page 107   CHAPTER 2: INSTALL ATION/CONFIGURATION   Figure 2-31: EntelliPro ES5 Actuator starter wiring diagram EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2.82  ...
  • Page 108 CHAPTER 2: INSTALL ATION/CONFIGURATION       Tables below show the default configuration for all typicals.       Motor Starter Standard Configuration EntelliPro ES3   Full-voltage Star-delta   Full-voltage Star-delta Softstarter Pole- Solenoid non- non- Softstarter Breaker Dahlander Actuator reversing reversing reversing...
  • Page 109   CHAPTER 2: INSTALL ATION/CONFIGURATION         Motor Starter Standard Configuration EntelliPro ES3 Full-voltage Star-delta     Full-voltage Star-delta Softstarter Pole- Solenoid non- non- Softstarter Breaker Dahlander Actuator reversing reversing reversing changer valve reversing reversing Input 97 Mapping Control Control Contactor 3...
  • Page 110 CHAPTER 2: INSTALL ATION/CONFIGURATION             Motor Starter Standard Configuration EntelliPro ES5     Full-voltage Star-delta   Full-voltage Star-delta Softstarter Solenoid non- non- Softstarter Breaker Dahlander Polechanger Actuator reversing reversing reversing Valve reversing reversing Feedback via contact Activated Activated Activated...
  • Page 111   CHAPTER 2: INSTALL ATION/CONFIGURATION       Motor Starter Standard Configuration   EntelliPro ES5     Full-voltage Star-delta   Full-voltage Star-delta Softstarter Solenoid non- non- Softstarter Breaker Dahlander Polechanger Actuator reversing reversing reversing Valve reversing reversing Input 97 Mapping Reset Alarm Reset Alarm Delta...
  • Page 112 CHAPTER 2: INSTALL ATION/CONFIGURATION             Motor Starter Standard Configuration EntelliPro ES5     Full-voltage Star-delta   Full-voltage Star-delta Softstarter Solenoid non- non- Softstarter Breaker Dahlander Polechanger Actuator reversing reversing reversing Valve reversing reversing First Function Relay 23 Mapping ON 1 ON 1 ON 1...
  • Page 113: Chapter 3: Motor Protection

      CHAPTER 3: MOTOR PR OTECTION   GE Industrial Solutions             EPOS Motor Management System   Chapter 3: Motor Protection       The EntelliPro ES provides the following protection functions: Thermal overload with n-times auto-reset  ...
  • Page 114: Unbalance And Phase-Loss Biasing

    CHAPTER 3: MOTOR PR OTECTION   3.1.1 Unbalance and phase-loss biasing   Unbalanced phase currents (that is, negative-sequence currents) cause rotor heating in addition to the normal heating caused by positive-sequence currents. When the motor is running, the rotor rotates in the direction of the positive- sequence MMF wave at near synchronous speed.
  • Page 115: Overload Curve

      CHAPTER 3: MOTOR PR OTECTION 3.1.3 Overload curve   The overload curve accounts for the rapid motor heating that occurs during stall, acceleration, and overload. Specifically, the overload curve controls the rate of increase of the accumulated motor heating value whenever the equivalent average motor heating current is greater than 1.12 times the full-load current setpoint .
  • Page 116   CHAPTER 3: MOTOR PR OTECTION         10,000   EntelliPro ES Overload Trip Characteristic 3-Pole / 3-Wire       1,000                       Class 40 Class 35 Class 30 Class 25 Class 20 Class 15...
  • Page 117   CHAPTER 3: MOTOR PR OTECTION         10,000   EntelliPro ES Overload Trip Characteristic 2-Pole / 2-Wire       1,000                         Class 40 Class 35 Class 30 Class 25 Class 20...
  • Page 118: Cooling Rate

      CHAPTER 3: MOTOR PR OTECTION     3.1.4 Cooling rate   The thermal cooling model causes the accumulated motor heating value to decrease exponentially when the steady- state accumulated motor heating value is less than the actual accumulated motor heating value. The cooling time constant (K) is programmable up to 15 times the time constant for the selected trip class.
  • Page 119   CHAPTER 3: MOTOR PR OTECTION     M otor Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Class 5 Heating K = 1 K = 2...
  • Page 120   CHAPTER 3: MOTOR PR OTECTION     M otor Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0 Class 1 0...
  • Page 121   CHAPTER 3: MOTOR PR OTECTION     M o tor Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5 Class 1 5...
  • Page 122   CHAPTER 3: MOTOR PR OTECTION     M o to r Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Class 20 Heating K = 1...
  • Page 123   CHAPTER 3: MOTOR PR OTECTION     M o to r Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Class 25 Heating K = 1...
  • Page 124   CHAPTER 3: MOTOR PR OTECTION     M otor Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Class 30 Heating K = 1 K = 2...
  • Page 125   CHAPTER 3: MOTOR PR OTECTION     M o to r Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Class 35 Heating K = 1...
  • Page 126   CHAPTER 3: MOTOR PR OTECTION     M o to r Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Class 40 Heating K = 1...
  • Page 127: Overload Protection N-Times Reset

      CHAPTER 3: MOTOR PR OTECTION   3.1.5 Overload protection n-times reset   EntelliPro ES has an n-times automatic reset function, which allows a defined number of automatic reset operations. The reset count will be automatically cleared when one hour elapses from the last overload trip.  ...
  • Page 128 CHAPTER 3: MOTOR PR OTECTION   When the auto-reset parameter is set to 1, the Auto-Reset is allowed after an overload trip occurred.   NOTE: auto reset will NOT be allowed for 1 hour after the last trip.     When the auto-reset parameter is set to 2, 2 auto-Resets are allowed after an overload trip occurred.
  • Page 129: Overload Protection Programmable Settings

    The EntelliPro ES motor trip and alarm overload setpoints may be viewed or changed through Modbus or Profibus DP communication protocols. GE offers a Profibus configuration application (WinESG), for easy set-up. EntelliPro ES supports the use of two current transformer (CT rated current for single speed motor and CT rated current low for two speed motor) and two motor load (motor rated current and motor rated current low settings for protection.
  • Page 130   CHAPTER 3: MOTOR PR OTECTION CAUTION: Make sure the proper system phase is selected for the application. If having a three-phase system, 3- phase must be selected in WinESG parameterization/device settings panel shown in the illustration below or Modbus function code 6 register 5.
  • Page 131: Phase Loss And Current Unbalance

      CHAPTER 3: MOTOR PR OTECTION   3.2 Phase loss and current unbalance   The Current Unbalance is detected whenever the minimum of the three phase currents is less than 70% of the maximum phase current (RMS value). The Phase Loss is detected whenever the minimum of the three phase currents is less than 40% of the maximum phase current (RMS value).
  • Page 132: Ground Fault

    CHAPTER 3: MOTOR PROTECTION     3.3 Ground fault   The ground fault function is designed for grounded networks. The ground fault current is derived by summing the CT’s secondary currents. Ground fault is disabled when the average current falls below half of the motor load setting or exceeds 3 times the motor load setting.
  • Page 133: Overcurrent And Stalled Rotor Protection

      CHAPTER 3: MOTOR PR OTECTION 3.4 Over current and stalled rotor protection This protection scheme addresses the starting inrush current and stalled-rotor current. The over current and stalled rotor current threshold is set in WinESG parameterization/device settings panel shown in the illustration below or Modbus function code 06 register 18.
  • Page 134 CHAPTER 3: MOTOR PROTECTION   Overcurrent/stalled rotor protection can be enabled or disabled, set as a warning or failure and requiring an auto or manual reset after a failure, in WinESG parameterization/alarms panel shown in illustration below or Modbus function code 6 registers 114 (enable/disable), 64 (warning/failure), and 63 (auto/manual reset). 3.22 EP OS MOTOR MANAGEMENT SYSTEM –...
  • Page 135: Undercurrent Protection

      CHAPTER 3: MOTOR PR OTECTION   3.5 Undercurrent protection   The undercurrent function switches off the motor during an undercurrent condition. Under current threshold is set in WinESG parameterization/device settings panel shown in the illustration below or Modbus function code 06 register 20. The under current threshold is settable from 1 to 100% of motor load (Ir), If a current falls below the under current threshold for a pre-defined timer set in WinESG parameterization/timer panel shown in the illustration below or Modbus function code 06 register 40 a failure or warning will be generated depending on the alarm setting.
  • Page 136 CHAPTER 3: MOTOR PROTECTION   Under current can be enabled or disabled, set as a warning or failure and requiring an auto or manual reset after a failure, in WinESG parameterization/alarms panel shown in illustration below or Modbus function code 6 registers 114 (enable/disable), 64 (warning/failure), and 63 (auto/manual reset).
  • Page 137: Thermistor (Tma)

      CHAPTER 3: MOTOR PR OTECTION   3.6 Thermistor (TMA)   The thermistor protection module protects a motor by evaluating a PTC resistor inside the motor. The system allows connection of 1, 3, or 6 thermistors in series, per IEC34-11-2.  ...
  • Page 138: Chapter 4: Communication

    CHAPTER 4: COMMUNICATION     GE Industrial Solutions             EPOS Motor Management System   Chapter 4: Communication         The EntelliPro DP offers two communication protocols: Modbus RTU and Profibus DP over RS-485. They are independent and can run simultaneously.
  • Page 139 CHAPTER 4: COMMUNICATION   If the software address is selected, the address value can be set In WinESG parameterization/Modbus setting panel shown In Illustration below or Modbus function code 6 register 103. If Modbus address is misplaced or forgotten, the front left switch can be set to address "D" and the Entellipro ES will reset Modbus to address 247.
  • Page 140: Modbus Baud Rate And Port Configuration

    CHAPTER 4: COMMUNICATION       4.1.2 Modbus baud rate and port configuration   The EntelliPro supports the configured baud rate settings listed in Table 4-1, which can be set in WinESG parameterization/Modbus setting panel shown In Illustration below or Modbus function code 6 register 90. The EntelliPro supports the configured baud rate settings listed in Table 4-1, which can be set via communications.
  • Page 141: Modbus Function Codes

    CHAPTER 4: COMMUNICATION       300-8N2 600-8N2 1200-8N2 2400-8N2 4800-8N2 9600-8N2 19200-8N2 300-8O1 600-8O1 1200-8O1 2400-8O1 4800-801 9600-801 19200-8O1 300-8E1 600-8E1 1200-8E1 2400-8E1 4800-8E1 9600-8E1 19200-8E1 300-8N1 600-8N1 1200-8N1 2400-8N1 4800-8N1 9600-8N1 19200-8N1   Table 4-1: EntelliPro baud rate settings.  ...
  • Page 142: Modbus Topology

    CHAPTER 4: COMMUNICATION     4.1.4 Modbus topology   Figure 4-2 illustrates the standard two-wire Modbus topology. To minimize the effects of reflections from the ends of the RS- 485 cable caused by impedance discontinuities in the system, a line-terminating resistor on the RC network must be placed near each end of the bus, as illustrated in Figure 4-2.
  • Page 143: Connections

    CHAPTER 4: COMMUNICATION       4.1.5 RS-485 connections   On the upper left side of the EntelliPro ES is a nine-pin connector for the Modbus connection. A mating connector is included for customer connection. The pin assignments for the connector are shown in Figure 4-3 and section 2.1.1.4. If the EntelliPro ES is to be the first or last device on the RS-485 network, it must be terminated with a terminating resistor or RC network.
  • Page 144: Implementation Basics

    CHAPTER 4: COMMUNICATION       4.1.8 Implementation basics   The EntelliPro ES implements a subset of the Modicon Modbus RTU protocol standard. Modbus is a master-slave protocol, which means that a single host/master device initiates and controls all communication with the other devices on the network.
  • Page 145: Entellipro Es Function Code

    CHAPTER 4: COMMUNICATION       4.1.10 EntelliPro ES Function Code   The following sections describe the Modbus function code supported by the EntelliPro ES.     4.1.10.1 Function code 03H   For the EntelliPro ES implementation of Modbus, this function code can be used to read any setpoints (“holding registers”).
  • Page 146: Function Code 04H

    CHAPTER 4: COMMUNICATION       4.1.10.2 Function Code 04H   Modbus Implementation: Read Input Registers   EntelliPro ES implementation: Read Actual Values   For the EntelliPro ES implementation of Modbus, this function code can be used to read any actual values (“input registers”).
  • Page 147: Function Code 05H

    CHAPTER 4: COMMUNICATION       4.1.10.3 Function Code 05H   Modbus Implementation: Force Single Coil   EntelliPro ES Implementation: Execute Operation   This function code allows the master to request a EntelliPro ES to perform specific command operations.   For example, to request slave 17 to execute operation code 1 (reset), we have the following master/slave packet format:  ...
  • Page 148 CHAPTER 4: COMMUNICATION       The following table shows the command that can be initiated using function code 05.       Operation Code Description   Contactor1 ON Contactor2 ON Contactors 1 & 2 OFF Module Identification (request EntelliPro ES ID) Lock Switch Command Switch to Local mode Switch to Reset mode...
  • Page 149 CHAPTER 4: COMMUNICATION         Reset Overload Current Warning Reset External Supervision Warning Reset Long Start Warning Reset Typical Specific Warning Reset Parameter Error Reset Watchdog Error Reset Timer Interrupt Error Reset Current Measurement Ungauged Error Reset NOV RAM EEPROM Reset Current Measurement Error Reset Start Atte,[t Reset Thermistor Error...
  • Page 150: Function Code 06H

    CHAPTER 4: COMMUNICATION         4.1.10.4 Function Code 06H   Modbus Implementation: Preset Single Register   EntelliPro ES Implementation: Store Single Setpoint   This command allows the master to store a single setpoint into the memory of a EntelliPro ES. The slave response to this function code is to echo the entire master transmission.
  • Page 151: Function Code 10H

    CHAPTER 4: COMMUNICATION       4.1.10.5 Function Code 10H   Modbus Implementation: Preset Multiple Registers   EntelliPro ES Implementation: Store Multiple Setpoints   This function code allows multiple Setpoints to be stored into the EntelliPro ES memory. Modbus “registers” are 16-bit (two byte) values transmitted high order byte first .
  • Page 152: Function Code 14H

    CHAPTER 4: COMMUNICATION       4.1.10.6 Function Code 14H   Modbus Implementation: Read File Record   EntelliPro Implementation: Read Full Event and Analog Data   This command allows the master to read a file containing the full 255 events and analog RMS data. All Request Data Lengths are provided in terms of number of bytes and all Record Lengths are provided in terms of registers.
  • Page 153: Error Responses

    CHAPTER 4: COMMUNICATION       4.1.11 Error Responses   When a EntelliPro ES detects an error other than a CRC error, a response will be sent to the master. The MSBit of the FUNCTION CODE byte will be set to 1 (i.e. the function code sent from the slave will be equal to the function code sent from the master plus 128).
  • Page 154: Modbus Register Map

    CHAPTER 4: COMMUNICATION       4.1.12 Modbus Register Map   Function Code 03 - Read Holding Registers Function Code 06 - Write Holding Registers Function Code 16 Write Multiple Holding Registers             Holding Modbus Variable Description Step...
  • Page 155 CHAPTER 4: COMMUNICATION                   Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit Ground Fault Delay msec GF Dly Unsigned   Setting Integer x 10 10 = 100msec 32 bit Analog Output Value If analog output is set to 0-20mA - the current...
  • Page 156 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit Current Unbalance/Loss Delay 0-Disable Unsigned   Integer 16 bit Analog RMS value time interval Time interval between analog value log Unsigned  ...
  • Page 157 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit Reset Configuration   65535 Unsigned   Integer BIT0 - Overload 1 = Manual Reset required 0 = Auto Reset   Note: The number of Auto reset is depending  ...
  • Page 158 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit Time Sync Year Year Unsigned           Integer   16 bit Time Sync Month Unsigned Month    ...
  • Page 159 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit Typical Specific Feature                 bit 0 - ATEX_Activated 1 = ATEX Enable 0 - ATEX Disable  ...
  • Page 160 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit ForceLocalRemote switch Switch setting upon Modbus and/or Profibus Unsigned     class1 Bus failure integer Bit 0: for local switch on Class1 failure. 0 = None - Switch remains as is 1 = Local on Profibus Class 1 failure  ...
  • Page 161 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit Digital Input[98 & 99] Active High Configuration 65536 Unsigned 10244     Integer   01 = Contactor 1 ON Command Setting example: 02 = Contactor 2 ON Command Digital 0 is mapped to Reset alarm Input...
  • Page 162 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size Unsigned   16 bit DigitalInput[96 & 97) See holding register 118 definition 8 996 integer Unsigned   16 bit DigitalInput[94 & 95] See holding register 118 definition 10021 integer...
  • Page 163 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit Digital Output - Motor Relay 41 1 = Main Contactor 1 / Breaker ON / Slow Unsigned     Contactor Integer  ...
  • Page 164 CHAPTER 4: COMMUNICATION         Holding Modbus Variable Description Step Units Scale Format Default Register Size 16 bit Configuration Bits Unsigned       Integer bit 0 - Class1BusFailureDetection 0 - disabled 1- enabled bit 1 - ModbusBusFailureDetection 0 - disabled 1- enabled bit 2 - ActivateThermistorLineBreakAnd...
  • Page 165 CHAPTER 4: COMMUNICATION       Function Code 04 - Read Input Registers 53 = Low byte / 54 = high byte         Input Data Register Parameter Name Units Scale Format Note Size Address        ...
  • Page 166 CHAPTER 4: COMMUNICATION         Input   Data Register Parameter Name Units Scale Format Note Size Address 16 bit Event Code Unsigned Integer Indicates the event type base on Index selected on holding     0 = Thermal Overload Fault regsiter 101 1 = Thermistor Fault 2 = Ground Fault Sum Fault...
  • Page 167 CHAPTER 4: COMMUNICATION         Input   Data Register Parameter Name Units Scale Format Note Size Address 16 bit 133 = Emergency Stop Fault Reset Unsigned Integer Indicates the event type base on Index selected on holding    ...
  • Page 168 CHAPTER 4: COMMUNICATION         Input   Data Register Parameter Name Units Scale Format Note Size Address EntelliPro ES Status 32 bit Unsigned Integer Status Definition     bit0 - Contactor1FeedbackStatus When Relay 41 is turned ON , on receiving the feedback signal from of the the mapped input, the status will be set to 1  ...
  • Page 169 CHAPTER 4: COMMUNICATION         Input   Data Register Parameter Name Units Scale Format Note Size Address 16 bit Fault Type Unsigned Integer “1 means the fault has occurred     BIT0 - Overload Failure (Trip) To clear the fault refer to FC 04 command 65-80” BIT1 - Phase Loss Failure (Trip) BIT2 - Gf Failure (Trip) (trip) BIT3 - Unbalanced Load Failure (Trip)
  • Page 170: Profibus

    Please refer to Chapter 5 for WinESG set-up.   A device data (GSD), which is provided by GE on its website, that has the operational characteristic of the EntelliPro ES DP. It provides the system with an easier means to change communication options, diagnostic, metering among other parameters.
  • Page 171: Profibus System Concept

    CHAPTER 4: COMMUNICATION       4.2.2 Profibus System concept   Figure 4.4 shows the the communication network system overview consisting of: Profibus class 1 master (PLC or PC), with cyclic data exchange Profibus class 2 master (WinESG), which provides acyclic data exchange EntelliPro ES which are Profibus DP slaves  ...
  • Page 172: Profibus Interface

      CHAPTER 4: COMMUNICATION     4.2.3 Profibus Interface   The EntelliPro ES supports DPV0 and DPV1 protocols, which is comprised of Cyclic and Acyclic data transfer. The external connections through the Profibus interface (female D-sub connector) are as follows:  ...
  • Page 173: Profibus Termination

      CHAPTER 4: COMMUNICATION 4.2.4 Profibus termination   The Profibus port provides a 5V, so no external voltage is required (pin 5 (V-) and pin 6 (V+) of the 9-D connector). This 5Vdc can be used for an active termination.  ...
  • Page 174: Profibus Dp Cyclic Data

      CHAPTER 4: COMMUNICATION       4.2.7 Profibus DP Cyclic Data   The cyclic data is a fast process data transfer between the Profibus DP master and the slave which occurs once every DP cycle. EntelliPro ES is a modular device supporting up to 144 bytes of input data and 18 bytes of output data.
  • Page 175: Entellipro Es Cyclic Read Telegram Definitions

      CHAPTER 4: COMMUNICATION     4.2.7.1 EntelliPro ES Cyclic Read Telegram Definitions   The following table shows the detailed input telegram definitions.   16-bit Reserved 0x0000     Size Telegram Name Description Default Bytes Unit Scale   Identification Telegram 16-bit Type Identifier 8 = ESS-DP V4...
  • Page 176   CHAPTER 4: COMMUNICATION       Size Telegram Name Description Default Bytes Unit Scale dependent 8-bit * 12 Serial number Serial Number     format - 1 8-bit (Format 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12) 8-bit 8-bit 8-bit...
  • Page 177   CHAPTER 4: COMMUNICATION       Size Telegram Name Description Default Bytes Unit Scale BIT0 - Safety circuitStatus 1 indicates that safety circuit input is set. Input must be mapped.             BIT1 - EntelliPro Local Mode Status 1 indicates that switch position is set to local.
  • Page 178   CHAPTER 4: COMMUNICATION       Size Telegram Name Description Default Bytes Unit Scale 2 * 8-bit B30008 Failure Telegram   BIT0 - Overload Failure 1 indicates Overload Failure (Trip)             BIT1 - Phase Loss Failure 1 indicates Phase Loss Failure (Trip)  ...
  • Page 179   CHAPTER 4: COMMUNICATION       Size Telegram Name Description Default Bytes Unit Scale 2 * 8-bit B30776 Device Error Telegram BIT0 - Reserved Free   0x00       BIT1 - Reserved Free BIT2 - Parameter Error 1 indicates parameter error BIT3 - Watchdog Error 1 indicates watchdog error BIT4 - Free...
  • Page 180 CHAPTER 4: COMMUNICATION           Size Telegram Name Description Default Bytes Unit Scale   B2721 Debug Telegram     Cyclic Control Byte 2 BE 16 15 14 13 12 11 10 9       Cyclic Control Byte 3 BE 24 23 22 21 20 19 18 17  ...
  • Page 181   CHAPTER 4: COMMUNICATION       Size Telegram Name Description Default Bytes Unit Scale             B2734 Additonal Counter (not available on EntelliPro ES Retrofit version) 32-bit Contactor 1 Operations Counter 32-bit Contactor 2 Operations Counter 32-bit Contactor 3 Operations Counter 32-bit...
  • Page 182   CHAPTER 4: COMMUNICATION This page was intentionally left blank 4.45 EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL  ...
  • Page 183: Entellipro Es Cyclic Write Telegram Definitions

      CHAPTER 4: COMMUNICATION     4.2.7.3 EntelliPro ES Cyclic Write Telegram Definitions   The following table shows the detailed write telegram descriptions.     Note Size Telegram Name Description Bytes   B10008 Write Control Telegram   BE (Customer Logic)  ...
  • Page 184   CHAPTER 4: COMMUNICATION       Size Telegram Name Description Default Bytes 2 * 8-bit Reset Device Errors Reset Device Errors   BIT0 - Reserved 1 will reset the specific error   BIT1 - Reserved   BIT2 - Reset Parameter Error BIT3 - Reset Watchdog Error  ...
  • Page 185: Profibus Dp Cyclic Data

      CHAPTER 4: COMMUNICATION     4.2.8 Profibus DP Cyclic Data   The cyclic data is a fast process data transfer between the Profibus DP master and the slave, which occurs once in every DP cycle. EntelliPro ES is a modular device supporting up to 144 bytes of input data and 18 bytes of output data.  ...
  • Page 186   CHAPTER 4: COMMUNICATION     The EntelliPro ES extended diagnostic is composed of 34 tables. Below table shows the system extended diagnostic 34-bytes (7 thru 40)     Byte Description   User diagnostic data length   Diagnostic state   Free  ...
  • Page 187: Profibus Protocol Communication Set-Up

      CHAPTER 4: COMMUNICATION     4.2.10 Profibus Protocol communication set-up   The configuration and parameterization of the EntelliPro ES is to be performed with the fielbus configurator of the bus master. Following the configuration and parameterization with the ‘SyCon’ configuration tool for CIF communication cards (Hilscher) is described as an example.
  • Page 188   CHAPTER 4: COMMUNICATION       Append the desired module telegram. The telegram selection list is in the GSD file.                                        ...
  • Page 189   CHAPTER 4: COMMUNICATION       After completion of configuration and parameterization, data must be sent to the master component by means of a download:                 The menu item ´Online` and ´Start Debug Mode` is to be used to check whether the EntelliPro ES has accepted the parameters.
  • Page 190: Profibus-Dp Class1 Parameterizing

    CHAPTER 4: COMMUNICATION 4.2.11 Profibus-DP Class1 parameterizing When starting the EntelliPro ES using Profibus-DP, the Profibus Class1 (PB-C1) master sends parameters to the EntelliPro ES device. This Profibus-DP Set_Param service can also include device-specific parameters, to change the EntelliPro behavior. These specific parameters can be adjusted in the PB-Class1 master configurator software tool.
  • Page 191 CHAPTER 4: COMMUNICATION To do the parameterization from Profibus-DP Class1 master, select the correct EntelliPro ES device. Using the right-hand mouse key or double clicking, the device parameter list can be opened. Press buttons to switch the parameter texts display. The Parameter list appears in a new window.
  • Page 192 CHAPTER 4: COMMUNICATION NOTE: If the parameter “Set Parameters” is deactivated, the EntelliPro ES device will ignore the settings and accept the settings stored in EntelliPro ES. NOTE: If the parameter “Set Parameters” is activated, the EntelliPro ES device accepts the settings into the internal memory.
  • Page 193 CHAPTER 4: COMMUNICATION After completion of parameterization, the data must be sent to the master component by means of a download. The menu item ´Online` and ´Start Debug Mode` is to be used to check whether the EntelliPro ES has accepted the parameters. If all lines are green, the communication is free from defects.
  • Page 194 CHAPTER 4: COMMUNICATION Profibus-DP communication is not running and no data change is possible. The Profibus-DP line is green, all parameters and configuration is ok. The cyclic Profibus-DP communication is running and the configured data change is possible To see the current status of the EntelliPro ES device, click on the device. The correspondence diagnostic window opens showing an overview of the cyclic Profibus-DP communication.
  • Page 195 CHAPTER 4: COMMUNICATION When the Profibus-DP line is red, this indicates an error in parameter values or configuration has occured. The Cyclic Profibus-DP communication is not running and no data change is possible. To investigate the parameter status click on the EntelliPro ES device. When the diagnostic window for the correspondence device opens, it shows that there is a “Parameter Fault".
  • Page 196 CHAPTER 4: COMMUNICATION To get more information click the button “Ext. Diagnostic”. The following window appears with more helpful information about the current device status to correct all errors. When all errors are eliminated and the data is downloaded into the PB-C1 master device, the Profibus-DP line in SyCon tool will turn green as shown before.
  • Page 197: Chapter 5: Winesg

    Microsoft Windows 2000, Windows XP or Windows 7 operating system. A PCI Profibus master universal card and the OPC server from Softing are required. The WinESG CD, GE part number 720020, and Softing Profibus card and OPC server, GE part numbers 720031 thru 720037 can be purchased thru GE.
  • Page 198 CHAPTER 5: Wi nE S G   Step 4: From the Options menu, open the Settings window and select the OPC Server tab. Browse the directory (C:\Program files \ Softing \ PROFIBUS \ Configurator) to select the appropriate XML WinESG.xml has four configurable slave devices. Slaves adress from 1 to 4. WinESG_75 has 75 configurable slave devices.
  • Page 199 CHAPTER 5: WinESG   Step 5: Right click on "Segment0" and select Properties to set up the Profibus system. The WinESG Profibus -DP parameter must fit to the Profiibus-DP C1 communication parameter in SCADA system else communication problems can appear. Step 7: Right click on "Segment0"...
  • Page 200: File Menu

    CHAPTER 5: WinESG     WinESG main panel shown In the Illustration below, displays all field devices connected on the network with their line number, device address, name, status of the contactor and any warnings or failures. A maximum of 32 devices can be displayed in the panel.
  • Page 201: Winesg Configuration

    CHAPTER 5: WinESG 5.1.1 WinESG Configuration   To configure WinESG, select the file menu, click configuration, and then click WinESG. English, German, French, Spanish, Italian, Portuguese and Russian, languages; and automatic parameterization, off, 1 trial, 2 trials, 3 trials, 4 trials and 5 trials, can be selected. Automatic parameterization activates or deactivates the automatic parameterization function for connected field devices.
  • Page 202: Slave Device Configuration

    CHAPTER 5: Wi nE S G         5.1.2 Slave Device Configuration   To add a slave devices in the system, select the file menu, click configuration, and then click device configuration. Check the edit box and the EntelliPro ES button on the WinESG device configuration panel. Double click on the slave address number to select the device(s) to be added.
  • Page 203: Options Menu

    CHAPTER 5: WinESG     5.2 Options Menu   The Options menu contains six sub-menus. For details of each refer to the help menu. The Options menu contains six sub-menus: Alarm protocol, Access protection, Alarms, Time synchronization, Read all parameters and Send all parameters, shown in figure 5.3. Figure 5-3: WinESG windows menu panel options NOTE: The lock symbol, shown in the illustration below, in the main menu opens the Access protection panel.
  • Page 204: Access Protection Panel

    CHAPTER 5: Wi nE S G   CAUTION: A change of maximum data record in an existing alarm protocol trace causes a break in the serial number of the entries in the database. 5.2.2 Access protection panel In the Access protection panel, shown in the illustration below, user can set login settings, password and prevent unauthorized access.
  • Page 205: Alarm Panel

    CHAPTER 5: WinESG   5.2.3 Alarm panel The Alarm panel, shown in the illustration below, shows the number of alarms in the system. 5.2.4 Time synchronization panel In the Time synchronisation panel, shown in the configuration below, when the time synchronization is selected, the PC operating time is sent to the EntelliPro ES based on time interval selected.
  • Page 206: Windows Menu

    CHAPTER 5: Wi nE S G   5.3 Windows menu The Windows menu contains eight sub-menus: Control, Parameterizing, Char (characteristic), Diagnostic, Measure, Alarms, Debug, and Analog data capture, shown in figure 5.4. Figure 5-4: WinESG windows menu panel options 5.3.1 Control Panel The control panel gives the user the ability to view the status of the EntelliPro ES, contactors and drawer and to control the motor operation.
  • Page 207 CHAPTER 5: WinESG   Figure 5-5: WinESG control panel contactor operation The lower part of the control panel provides the EntelliPro ES status and the capability to reset faults, warnings, and device errors. A red highlight indicates a function is active. To view the fault, warning, or device error details click on details as shown in the Figure 5-6.
  • Page 208: Parameterization

    CHAPTER 5: Wi nE S G   5.3.2 Parameterization The parameterization panel is mainly used to monitor and configure various EntelliPro ES functional parameters. The panel is comprised of the following sub-panels: Info, device settings, alarms, functions , timer, counter, control, typical settings, I/O’s, Cyclic communication, and Modbus settings.
  • Page 209 CHAPTER 5: WinESG   The first row, illustration A, shows the number of bus line, bus address and device identification. In illustration B the origin of the data in the screen is shown: Database: screen parameters match database parameters. Field: screen parameters match device parameters.
  • Page 210: Device Setting Panel

    CHAPTER 5: Wi nE S G   Successful writing is displayed in the message area, shown in illustration E. The writing can be invalid, if there is no communication, or the device is not ready for parameterization or one or more parameters are out of limit. Illustration F shows the Place Identifier, which allows the user to indentify the unit in the system.
  • Page 211 CHAPTER 5: WinESG   Figure 5-8: WinESG parameterization device setting panel Illustration A shows the current setting. CT rated current (Ict): current transformer (CT) primary current. It is the upper value of the CT range divided by the feed-thru factor. The feed-thru factor is how often the primary conductor is fed through the CT.
  • Page 212 CHAPTER 5: Wi nE S G   Phase unbalance/loss delay: select the delay time when phase unbalance or phase loss fault or warning is issued. Selectable from 1 to 15 seconds. When ATEX is selected the time is fixed to immediate. Max current delay: time delay before the maximum current will be measured.
  • Page 213 CHAPTER 5: WinESG   Illustration D shows the ground fault function. Three phase currents are added to calculate the RMS value of the ground fault current. Ground fault is only activated, when the mean value of the three phases currents is within the range of 0.5 to 3 times the rated motor current.
  • Page 214: Alarms Panel

    CHAPTER 5: Wi nE S G   5.3.2.3 Parameterization Alarms panel The alarm panel provides a means to enable and disable protections, set protections and inputs as fault or warning, and set the number of allowable auto resets after an overload trip. Refer to Figure 5-9 for the WinESG parameterization alarms panel.
  • Page 215: Function Panel

    CHAPTER 5: WinESG   5.3.2.4 Parameterization Function panel The function panel provides a means to define motor operation during start-up, enable the debug screen, and select the type of parameterization. Refer to figure 5-10 for the WinESG parameterization function panel. Figure 5-10-: WinESG parameterization function panel Parameterization definition: Parameterization...
  • Page 216: Timer Panel

    CHAPTER 5: Wi nE S G   5.3.2.5 Parameterization Timer panel Timer panel – The timer panel provides a means for setting the 16 timers available on EntelliPro ES. The timers can be adjusted within the range of 0.1 to 6553.5 seconds. Refer to Figure 5-11 for the WinESG parameterization timer panel.
  • Page 217: Counter Panel

    CHAPTER 5: WinESG   Soft starter time: use on soft starter typical. Transition to by-pass will occur after this time expires. Soft stop time: use on soft starter typical. Transition from by-pass to soft starter stop control will occur after this time expires. Under current delay time: fault or warning is indicated if a current is below under current threshold for the set amount of time.
  • Page 218 CHAPTER 5: Wi nE S G   Figure 5-13-: WinESG parameterization control panel Control configuration in illustration A enables and disables the source, defines the sources as local or remote, and defines the mode of operation of the source (1-bit or 2-bit). Only one source can be set as a remote. The rest, if enabled, will be automatically set as local.
  • Page 219: Typical Settings Panel

    CHAPTER 5: WinESG   Local / Remote selection switch in illustration B allows the setting of a source that controls the local-remote switch Switch selection control: The following sources can be selected: Class 1, Modbus, Hardwire, Fixed local, or Fixed Remote. The selected source determines if local or remote sources control the motor operation (ON/OFF).
  • Page 220 CHAPTER 5: Wi nE S G   ATEX activated: if active, overload, phase loss and unbalance cannot be disabled and set to warning and there is not a delay band for phase loss and unbalance. The maximum allowed auto-reset Is 3. Thermistor protection is enabled and set to failure.
  • Page 221: I/O's Panel

    CHAPTER 5: WinESG   5.3.2.9 I/O’s panel The I/O panel provides a mean for mapping the inputs and outputs. Refer to figure 5-15 for the WinESG parameterization I/O panel. The mapping can be changed by unselecting the default configuration in the parameterization/Information panel.
  • Page 222: Cyclic Panel

    CHAPTER 5: Wi nE S G   5.3.2.10 Parameterization Cyclic panel The cyclic panel enables the customer to select parameters to be viewed over Profibus class 1 master. Refer to Figure 5-16 for the WinESG parameterization cyclic communication panel. Figure 5-16: WinESG parameterization cyclic panel The following parameters status can be mapped to the Dynamic status data block: Contactor 1 feedback, Contactor 2 feedback, Parameter mode, Switch protected, Star attempt, Drawer ready, General warning, General Fault, Safety circuit, Local mode, Remote mode, Drawer operational mode, Drawer test mode, Limit...
  • Page 223: Char (Characteristic) Panel

    CHAPTER 5: WinESG   5.3.2.12 Char (Characteristic) panel The characteristic (Char) window shown below, displays the device type (catalog), unit serial number, software version and the fully flexible logic version if available. 5.3.2.13 Diagnostic panel The diagnostic panelshown below, shows the operations counters, trip information, maximum currents, and fault currents. The operations counters can be set by pressing “set value”...
  • Page 224: Alarm Panel

    CHAPTER 5: Wi nE S G   5.3.2.15 Alarm panel The alarm panel shown below, provides the EntelliPro ES status and the capability to reset faults, warnings and device errors. To view fault, warning, and device error details click on Details. To reset a particular fault, the fault type must be selected then click Reset.
  • Page 225 CHAPTER 5: WinESG       Table 5-1 below shows the full debug register definitions.   Element Type Size Description Notes PMS1 Input Overload Alarm PMS2 Input Phase loss Alarm PMS3 Input Ground fault Alarm PMS4 Input Unbalanced load Alarm PMS5 Input Thermistor Alarm...
  • Page 226 CHAPTER 5: Wi nE S G         Element Type Size Description Notes DI 13 Input Input 13 State DI 14 Input Input 14 State DI 15 Input Input 15 State DI 16 Input Input 16 State DI 17 Input Input 17 State DI 18...
  • Page 227 CHAPTER 5: WinESG         Element Type Size Description Notes BEAC11 Input Reserved BEAC12 Input Reserved BEAC13 Input Reserved BEAC14 Input Reserved BEAC15 Input Reserved BEAC16 Input Reserved BEAC17 Input Reserved BEAC18 Input Reserved BEAC19 Input Reserved BEAC20 Input Reserved BEAC21...
  • Page 228 CHAPTER 5: Wi nE S G         Element Type Size Description Notes BERW1 Input Overload Warning Reset Command BERW2 Input Phase loss Warning Reset Command BERW3 Input Ground fault Warning Reset Command BERW4 Input Unbalanced load Warning Reset Command BERW5 Input Thermistor Warning Reset Command...
  • Page 229 CHAPTER 5: WinESG         Element Type Size Description Notes HBAM24 Output Charge Status (Typical Specific) Status HBAM25 Output Torque switch 1 (Typical Specific) Status HBAM26 Output Torque switch 2 (Typical Specific) Status HBAM27 Output Start Phase Status HBAM28 Output Run Phase Status...
  • Page 230 CHAPTER 5: Wi nE S G         Element Type Size Description Notes HBAG15 Output Reserved HBAG16 Output Reserved       SEA1 & SEG1 Input / Output Overload SEA2 & SEG2 Input / Output Overload pre warning SEA3 &...
  • Page 231 CHAPTER 5: WinESG         Element Type Size Description Notes MA20 Input - RS FLipFlop Reserved Use on motor starter typicals only MA21 Input - RS FLipFlop Reserved Use on motor starter typicals only MA22 Input - RS FLipFlop Reserved Use on motor starter typicals only MA23...
  • Page 232 CHAPTER 5: Wi nE S G         Element Type Size Description Notes TA10 Input Maximun switch time (limit switch) - Timer Use on motor starter typicals only TA11 Input Maximun soft starter time - Timer Use on motor starter typicals only TA12 Input Maximunsoft stop time - Timer...
  • Page 233: Tools Menu

    CHAPTER 5: WinESG         5.4 Tools Menu The following options can be selected from the dropdown menu: event protocol, analog data capture and free logic download.   5.4.1 Event Protocol The event log panel provides a means to view the event of all EntelliPro in the system with its associate time stamp. Refer to Figure 5-19 for the WinESG event log panel.
  • Page 234: Analog Data Panel

    CHAPTER 5: Wi nE S G   5.4.2 Analog Data Capture panel     The analog data capture panel provides a means to view phases A, B, and C, and average currents of RMS samples based on trigger configuration set on the parameterization/device setting panel. If the trigger is set to Manual, by pressing the “Start recording“...
  • Page 235: Flexible Logic Download

    5.4.3 Flexible logic download panel   The flexible logic download panel provides a means to download the custom logic. GE will provide custom logic upon receiving an order. Refer to figure 5-21 for the WinESG custom logic download. The following procedure must be followed to download the fully flexible logic: Select Bus line on which EntelliPro ES device is connected.
  • Page 236: Chapter 6: Entellipro Cp3 And Cp5

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION GE Industrial Solutions EPOS Motor Management System   Chapter 6: EntelliPro CP3 and CP5 application 6.1 EntelliPro CP3 Main panel The EntelliPro CP3 device is a touch control display integrated into the Motor Control Center MCC for local control; alarm handling;...
  • Page 237 CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION Profibus-DP address of the connected EntelliPro ES device Device text of the connected motor / breaker / starter … Current status of the branch 2 : Valve 1 Ready message of the branch Drawer ready Background color informs the local...
  • Page 238 CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION If “Communication Error” appears in the message box, there is no communication to the EntelliPro ES. When a communication error is reported, check for missing cable connections and appropriate Modbus address settings. See section 6.2 for additional settings information. 2 : Valve 1 Communication Error Drawer ready...
  • Page 239 CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION The buttons in the figure below, are used to control the EntelliPro ES device and to switch into sub screens. Button to switch into the launch menu screen 2 : Valve 1 Drawer ready local operate Button to switch the device...
  • Page 240 CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION The following two figures show the menu screen selections and descriptions Button to switch into the parameter screen 2 : Valve 1 Button to switch into the measurement screen Button to switch into the diagnostic screen Button to switch into the characteristics screen...
  • Page 241: Entellipro Cp3 Application Setting

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.2 EntelliPro CP3 application setting Screen “Settings 2” shows the application version number, the current Modbus address, and the current Modbus timeout time in seconds. This timeout value can be set in the EntelliPro ES device. This value is shown if the Modbus communication is connected. To establish a communication between the EntelliPro CP and the EntelliPro ES, the Modbus address must set to the same Modbus address as in EntelliPro ES device.
  • Page 242 CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION Changing the Modbus RTU address COM 1 The input of a new address is protected with a user level password “22222222”. COM 1 The Modbus RTU address range is 1 thru 247. The address is stored permanently in the CP3 panel. EPOS MOTOR MANAGEMENT SYSTEM –...
  • Page 243: Entellipro Cp3 Screen Saver Display

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.3 EntelliPro CP3 screen saver display This screen appears in the application after a period of time without a user handling. The backlight will also switch off after an extended time of inactivity. The application screen resumes when the user touchs the display. COM 1 EPOS MOTOR MANAGEMENT SYSTEM –...
  • Page 244: Entellipro Cp3 Application Tree Structure

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.4 EntelliPro CP3 application tree structure Root screen Menue screen Parameter screen Next Parameter screens Back to previous menu Chararistics screen Shows device characteristic Back to previous menu Measuring screen Single phase displaying Back to previous menu Diagnostic screen Next diagnostic screen...
  • Page 245 CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION Screen choice Root screen selection selection CP3 settings Language selection Back to previous menu Modbus settings Display settings Service screen (in work) Back to previous menu Back to previous menu EPOS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6.10...
  • Page 246: Entellipro Cp5 Main Panel

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.5 EntelliPro CP5 Main panel The EntelliPro CP5 device is a touch control display integrated into the Motor Control Center MCC for local control; alarm handling and visualization the device status, values, and parameter settings. The EntelliPro CP5 application has been created to opearte and handle the pre-programmed drive typical, such as DOL, DOL reverse, Star delta, Star delta reverse, Soft starter, Soft starter reverse, Dahlander, Pole changing starter, Solenoid valve, and Actuator...
  • Page 247 CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION Each row in the root screen below shows information about one EntelliPro ES device. The row assignment must be done in the device configuration screen. The columns show the device index, which appears on all menus, the device text, the device status, and the device condition, respectively.
  • Page 248: Entellipro Cp5 Application Setting

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.6 EntelliPro CP5 application setting The application setting menu, shown in the figure below can be accessed by pressing function key “F4” from root menu. 6.13 EPOS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL...
  • Page 249: Entellipro Cp5 Device Addresses

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.7 EntelliPro CP5 device addresses The device setting menu, shown in the figure below, can be accessed by pressing function key “F5” from root menu. For each device in the system, a unique a Modbus RTU address must be assigned. No two devices can have the same address.
  • Page 250: Entellipro Cp5 Device Screen

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.8 EntelliPro CP5 device screen The device setting menu, shown in the figure below, can be accessed by touching the device row on the main screen. All information related to the particular device is made available. 6.15 EPOS MOTOR MANAGEMENT SYSTEM –...
  • Page 251: Entellipro Cp5 Control Screen

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.8 EntelliPro CP5 control screen The screen shown in the figure below, controls the assigned EntelliPro ES device when the device is configured to local control. EPOS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6.16...
  • Page 252: Entellipro Cp5 Screen Saver Display

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION EntelliPro CP5 screen saver display This screen appears in the application after a period of time without a user handling. The backlight will also switch off after an extended time of inactivity. The application screen resumes when the user touchs the display. 6.17 EPOS MOTOR MANAGEMENT SYSTEM –...
  • Page 253: Entellipro Cp5 Installation

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION EntelliPro CP5 installation The EntelliPro CP5 has three communication (COM) ports on the back side. The communication port COM3 is used for the Modbus communication with the EntelliPro CP5 application. Pin3 of the COM3 port is the Modbus DataP signal and Pin6 is the DataN signal.
  • Page 254: Entellipro Cp5 Application Tree Structure

    CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION 6.1 EntelliPro CP5 application tree structure teetetetetet 6.19 EPOS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL...
  • Page 255 CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION EPOS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6.20...
  • Page 256: Chapter 7: Revision / Service / Sales

    CHAPTER 7: REVISION / SERVICE / SALE S   GE Industrial Solutions           EPOS Motor Management System   Chapter 7: Revision / Service / Sales       AFTER SALES TECHNOLOGY 2-07-12 Update CP chapter N Vicente...
  • Page 257: Service For Low Voltage Equipment

    You can rely on GE’s Field Service teams for all your electrical infrastructure, as we are at home in all industries, specialized in solutions and services for your electrical infrastructure.
  • Page 258 CHAPTER 7: REVISION / SERVICE / SALE S     Global Services   We are at home in all industries, specialized in solutions and services for your electrical infrastructure, including:   Air Circuit Breaker EntelliGuard-G M-Pact I, ME 06 ME07, MEG, MEY ME...

This manual is also suitable for:

Entellipro es3 dp 2 0Entellipro es3 dp 3 0Entellipro es5 dp 2 2Entellipro es5 dp 2 3Entellipro es5 dp 3 3

Table of Contents