INSTALLING THE XFL5 HARDWARE MIGRATION ADAPTER
IMPORTANT NOTES
• Before starting the migration, refer to the notes (See step 3 of the "Removing XFL5xx I/O Modules from
XSL513/XSL514 terminal blocks" section on page 2) that indicate the location of each type of XFL5xx I/O module.
Select the precise XFL5 Hardware Migration Adapter and XF8xx/XFR8xx I/O module as described in Fig.1 and
Table 1.
• Migrating the XFL5xx LON I/O modules require additional space as after installing the XFL5 Hardware Migration
Adapter and XF8xx/XFR8xx Panel Bus I/O module, the height and width increases by 29mm and 15mm respec-
tively.
B
(99.5)
ALL DIMENSIONS ARE IN MM
1. Refer to the notes (See step 6 of the "Removing
XFL5xx I/O Modules from XSL513/XSL514 terminal
blocks" section on page 2) for the module address of
the XFL5xx I/O module and adjust the rotary dial on
the XFL5 Hardware Migration Adapter to set the
address.
XFL5 Hardware Migration
Adapter
Fig. 1.
B
A
Before Migration
A
(89)
Rotary dial
XFL5xx
I/O
Sl.
module
No.
type
1
XFL521A
XFL521B
2
XFL522A
XFL522B
3
XFL523A
XFL523B
4
XFL524A
XFL524B
After Migration
B+15
(114.5)
2. Install the new safety latches between each terminal
block as shown in the following figure.
3
XFL5 HARDWARE MIGRATION ADAPTER
Table 1.
ComfortPoint
Open XFL5
Hardware
Migration Adapter
XF8xx/XFR8xx
Model Name (A)
I/O Module (B)
CPO-XFL521M
CPO-XFL522M
XF822A/XFR822A
CPO-XFL523M
CPO-XFL524M
XF824A/XFR824A
A+29
(118)
MU1B-0074 IE10 R0518
XF821A
XF823A

Advertisement