Six circuit supervised control module

Advertisement

NOTE: Power must not be applied to the unit when changing functionality of
the shunts.
NOTE: Whether in Class B or Class A wiring, power supply monitoring and
short circuit protection must be enabled on the NAC circuits that are sharing
a power supply.
NOTE: Short circuit protection can only be disabled if a power supply is not
being shared by multiple NACs.
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or FPLP cable as
required by Article 760 of the NEC.
• For easier wiring, assign all power-limited wiring to one side of the en-
closure rather than alternating with non power-limited.
PROGRAMMING
The XP6-C module operates with the following Fire Alarm Control Panels:
• AM2020/AFP1010
• AFP-200
• AFP-300/AFP-400
• System 5000 with AIM-200
• AFC-600
• NFS-640
• NFS-3030
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.
FIGURE 8:
TOP VIEW:
SIDE VIEW:
NOTIFICATION APPLIANCE/
POWER SUPPLY TERMINAL
NOTE: SLC wiring is the top terminal block, notification appliance/power
supply is the bottom.
NAC WIRING AND SUPERVISION
For Class B, Style Y applications (figures 9, 10, and 13 are typical): connect the
positive terminal of the notification appliance(s) to the NAC+ terminal and
the negative device terminal to the adjacent NAC- terminal. Connect one (for
each NAC) of the supplied EOL resistors across the NAC+ and NAC- wires, at
the ends farthest away from the NAC terminal of the XP6-C.
For Class A, Style Z applications (figures 11, 12, and 14 are typical) wire the
NACs per table 2. The A/B select shunt must be removed prior to connect-
ing the XP6-C to the SLC. The EOL resistors should not be used. The XP6-C
is capable of supporting 3 Class A, Style Z NACs. The XP6-C will only respond
at the base address, base address +2, and base address +4 (assuming no ad-
dresses have been disabled).
TABLE 2
NAC#
(+) CONNECTIONS
+0
+0 NAC+, +1 NAC+,
NOTIFICATION APPLIANCE+
+2
+2 NAC+, +3 NAC+,
NOTIFICATION APPLIANCE+
+4
+4 NAC+, +5 NAC+,
NOTIFICATION APPLIANCE+
N500-79-00
SYNC GENERATOR
ENABLE POWER SUPPLY MONITOR
DISABLE SHORT CIRCUIT PROTECTION
J1 SHUNT
SLC WIRING
TERMINAL
(–) CONNECTIONS
+0 NAC–, +1 NAC–
NOTIFICATION APPLIANCE–
+2 NAC–, +3 NAC–,
NOTIFICATION APPLIANCE–
+4 NAC–, +5 NAC–
NOTIFICATION APPLIANCE–
POWER SUPPLY WIRING AND SUPERVISION
Table 3 gives an overview of how the power connectors, T0–T5 and T10–T15,
are interconnected by the circuit board (PCB). The external supply connection
points, at T0–T5, are marked by PS– and PS+ on the PCB legend. Pin 1 is
indicated by a dot next to T10–T16. The odd pins, on T10–T16, always con-
nect to PS– pins (e.g. PS–, of the +0 NAC, is connected to T10–1 and T11–1).
The even pins always connect to PS+ pins (e.g. PS+, of the +5 NAC, is con-
nected to T15-4 and T16-2).
TABLE 3
PS OR NAC NUMBER (TERMINAL / PINS)
+0 (T0 – BOTTOM / PS- & PS+)*
+1 (T1 / PS- & PS+)
+2 (T2 / PS- & PS+)
+3 (T3 / PS- & PS+)
+4 (T4 / PS- & PS+)
+5 (T5 / PS- & PS+)
*Note: T0–TOP is reserved for SLC connections only (see Figure 8).
All power supplies, external to the cabinet (in which the XP6-C is housed),
should be connected to T0–T5 which are suitable connectors for field wiring.
The 1 x 4 terminal blocks, shown on page 1, should be used to make these
connections.
All NACs can be wired to be powered by separate external supplies (figures
9 and 11 are typical), or a single supply (figures 10 and 12 are typical) can be
shared among multiple NACs. If a supply is to be shared, between NACs wired
to a common PCB, use the short power supply jumpers shown on page 1. The
jumpers can be used on T11–T15. Refer to Table 4 for jumper functions. When
multiple (2 or more) NAC circuits share a power supply, the wiring for the
power supply must be in conduit and 20 feet or less from the XP6-C board.
TABLE 4
JUMPER LOCATION
T11*
T12
T13*
T14
T15*
*NOTE: Jumpers must be placed on T11, T13 and T15 for all Class A, Style Z
applications.
A supply can be wired to be shared among multiple PCBs in the same cabinet
(figure 15 is typical). To share among multiple PCBs: use the long power sup-
ply jumpers (shown on page 1) to connect either T10 or T16, of one PCB, to
either T10 or T16 of the other PCB..
An EOL relay must be used for every external power supply (figures 9–12 are
C0174-00
typical). The EOL relay coil should always be connected at the external power
supply input of the module which is connected to the ends of the wires which
are farthest from the power supply. The EOL relay contacts should always be
connected in series with the NAC wiring of the same module. The EOL relay
coil should be connected across the PS+ (red wire) and PS- (black wire) if
it is connected at T0 – T5. The EOL relay coil should be connected across
adjacent pins (red – even pin#, black – odd pin#), of the same connector, if
T10 – T16 are used. If the supply is an audio amplifier then the points, where
the EOL relay coil would normally be connected, should be connected to the
amplifier supervision EOL device (figures 13 and 14 are typical).
All wiring must be in accordance with the NEC, NFPA 72 and all other ap-
plicable codes and standards. All external power supplies must be voltage
regulated with battery back-up. All external power supplies, audio amplifiers,
EOL relays, and notification appliances must be UL listed for fire protection
signaling applications.
NOTE: All references to power limited represent "Power Limited (Class 2)".
4
TERMINAL / PINS
T10 / 1 & 2, T11 / 1 & 2
T11 / 3 & 4, T12 / 1 & 2
T12 / 3 & 4, T13 / 1 & 2
T13 / 3 & 4, T14 / 1 & 2
T14 / 3 & 4, T15 / 1 & 2
T15 / 3 & 4, T16 / 1 & 2
NAC PAIR SHARING SUPPLY
+0 and +1
+1 and +2
+2 and +3
+3 and +4
+4 and +5
I56-1805-019