General Parameters - ABB ACS880-07 User Manual

Safely-limited speed with the encoder interface (option +q965)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Note: When the motor is running, you cannot change the password, adjust parameter
values, nor upload or download the FSO configuration file.
Note: The FSO module activates the STO function if the motor speed hits a ramp monitoring
limit during the deceleration ramp. The FSO module activates the SSE function if the motor
speed hits a trip limit during SLS or SMS monitoring. Remember to configure the STO and
SSE functions (see sections Parameters for the STO function and Parameters for the SSE
function).
Follow the configuration steps described in the FSO module user's manual, chapter
Configuration.
There are parameters that you must always set and parameters that are related to certain
safety functions only. These tables list all the parameters that you must check and set for
the option +Q965. The example values apply only to the option +Q965.

General parameters

These parameters are common to all safety functions.
Index
Name
FSOGEN.21
Motor nominal speed
FSOGEN.22
Motor nominal fre-
quency
FSOGEN.41
Power-up acknow-
ledgement
FSOGEN.42
Acknowledgement
button input
Example value
Description
1500 rpm
Sets the nominal motor speed. Adjust the
default value to meet the ratings of the mo-
tor in use.
50 Hz
Sets the nominal motor frequency. Adjust
the default value to meet the ratings of the
motor in use.
Automatic
Sets the power-up acknowledgement
method of the FSO module.
Automatic: You do not need to push a reset
button after switching on the FSO module.
The FSO module generates the acknow-
ledgement signal automatically after the
power-up.
Manual: The FSO module reads the extern-
al acknowledgement signal through the di-
gital input defined by parameter FSO-
GEN.42.
Make sure that the value is Automatic.
None
Selects the digital input for the acknowledge-
ment signal when parameter FSOGEN.41
Power-up acknowledgement or STO.02
STO acknowledgement has value Manual.
In the safety functions described in this
manual, parameters FSOGEN.41 Power-
up acknowledgement and STO.02 STO
acknowledgement have value Automatic,
and this digital input is not used. The safety
functions are configured not to require a
reset/acknowledgement of the safety func-
tion after power-up or the removal of the
safety function request.
Option description 33