2 0 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump

6 Outoor Unit Installation

Step 1: Select installation location
Before installing the outdoor unit, you must choose an appropriate location. The
following are standards that will help you choose an appropriate location for the
unit.
 Proper installation locations meet the following standards:
Meets all spatial minimum requirements shown in Installation Space
Requirements (Figure 42)
Figure 42
Good air circulation and ventilation
Firm and solid ‒ the location can support the unit and will not vibrate
Noise from the unit will not disturb others
Protected from prolonged periods of direct sunlight or rain
 DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets
Near a public street, crowded areas, or where noise from the unit
will disturb others
Near animals or plants that will be harmed by hot air discharge
Near any source of combustible gas
In a location that is exposed to large amounts of dust
In a location exposed to excessive amounts of salty air
NOTICE
 If the unit is exposed to heavy wind: Install unit so that air
outlet fan is at a 90° angle to the direction of the wind. If
needed, build a barrier in front of the unit to protect it from
extremely heavy winds. See Figures 43 and 44.
Data subject to change
Strong wind
Figure 43
Figure 44
NOTICE
 If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the
rain or snow. Be careful not to obstruct air flow around
the unit.
The length of refrigerant piping will aff ect the performance and energy
effi ciency of the unit. Nominal effi ciency is tested on units with a pipe
length of 5 meters (16.5ft). A minimum pipe run of 3 meters (9.8ft) is
required to minimize vibration & excessive noise.
Refer to the table below for specifi cations on the maximum length and
drop height of piping.
Maximum length and drop height of refrigerant piping per unit model
Model
Capacity (BTU/h)
< 15,000
R410A
15,000 to < 24,000
Inverter
Split Air
24,000 to < 36,000
Conditioner
36,000 to 60,000
Table 6
Installation Manual
Strong wind
Wind Baffle
Strong
wind
Max. Equivalent
Max. Height
Length m (ft)
Variation m (ft)
25 (82ft)
10 (33ft)
30 (98.5ft)
20 (66ft)
50 (164ft)
25 (82ft)
65 (213ft)
30 (98.5ft)
05.2019 | Bosch Thermotechnology Corp.