FocusPRO
TM
TH6220D Programmable
Thermostat
Heating equip-
o
Check Installer Setup, Function
1 (System Type), to make sure it is set to
merit
is running
match the installed heating/cooling
equipment
(see page 11).
in cool mode
Cannot change
system setting
to "Heat"
*
Check Installer Setup, Function
1 (System Type), to make sure it is set to
match the installed heating equipment
(see page 11).
Change Installer
Setup, Function
12 (System Setting) to Manual or Auto
Chart eogeover(see page 12).
Cannot change
system setting
to "Cool"
*
Check Installer Setup, Function
1 (System Type), to make sure it is set to
match the installed cooling
equipment
(see page 11).
*
Change Installer
Setup, Function
12 (System Setting) to Manual or Auto
Chart eogeover(see page 12).
"Heat Oil" is
o
net displayed
"Cool On" is not
*
displayed
"Cool On" or
o
"Heat On"
is flashing
Change the System Setting to Heat, and set the temperature
level above
the current room temperature.
Change the System Setting to Cool, and set the temperature
level below
the current room temperature.
Compressor
protection
timeout is engaged. Wait 5 minutes for the
system to restart safely, without damage
to the compressor.
Please contact your distributor
to order replacement
parts.
Battery
holder ......................................................
Part Number 50007072-001
Cover plate assembly
........................................
Part Number 50002883-001
(Use to cover marks left by old thermostats,)
Temperature
Ranges
Heat: 40 ° to 90°F (4.5 ° to 32°C)
o
Cool: 50 ° to 99°F (10 ° to 37°C)
Electrical
Ratings
Terminal
Voltage (50/60Hz)
Running Current
W (O/B) Heating
20-30 Vac
0.02-1.0 A
Operating
Ambient
Temperature
*
32 ° to 120°F (0 ° to 48.9°C)
(Powerpile)
750 mV DC
100 mA DC
Shipping
Temperature
W2 (Aux) Heating
20-30 Vac
0.02-0.5 A
-20 ° to 120°F (-28.9 ° to 48.9°C)
Y Cooling
20-30 Vac
0.02-1.0 A
Operating
Relative
Humidity
Y2 Cooling
20-30 Vac
0.02-1.0 A
5% to 90% (non-condensing)
G Fan
20-30 Vac
0.02-0.5 A
Physical
Dimensions
E Emergency
heat
20-30 Vac
0.02-1.0 A
3-9/16"
H x 5-13/16"
W x 1-1/2"
D
91 mm H x 147 mm W x 38 mm D
L Heat pump reset
20-30 Vac
0.02-0.5 A
17