Mounting the Wall Module
Mount the wall module on an inside wall approximately 54 in.
(1372 mm) from the floor (or in the specified location) to allow
exposure to the average zone temperature. Do not mount the
wall module on an outside wall, on a wall containing water
pipes, or near air ducts. Avoid locations that are exposed to
discharge air from registers or radiation from lights,
appliances, or the sun. When mounting to drywall, use the
horizontal mounting screw locations, as shown in Fig. 3.
63/64 (25)
1-5/32 (29)
Fig. 2. Wall Module subbase dimensions in inches (mm)
(TR23 shown).
SUBBASE
NO. 6 SCREW
FRONT COVER
TEMPERATURE LIMIT
END STOPPER
LOCATIONS
END STOPPERS
Fig. 3. Mounting the wall module on the wall and
temperature limit set screw locations (TR23 shown).
There is a locking screw option to prevent tampering and
access to batteries. The screw is provided with the wall
module, and screws into the slot shown in Fig. 9 after the
device is snapped onto the subbase.
3 (77)
7/8
STANDARD
(22)
UTILITY
CONDUIT
BOX (2 X 4)
MOUNTING
HOLES
7/8
(22)
70
2-3/8
(60)
9/16 (14)
2-3/8 (60)
TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR
If desired, insert the two red end stoppers into temperature
scale to set the desired temperature range limit. See Fig. 3.
For TR23 models, insert the desired dial through the opening
in the cover. Align the keyed shaft on the knob with the keyed
slot into the fitting on the subbase, then press down until it
snaps into place.
WIRING
Attach the wires from the device terminals to the appropriate
receiver terminals.
CAUTION
Improper Electrical Contact Hazard.
Screw type terminal blocks are designed to accept
no more than one 16 AWG (1.31 sq. mm)
conductor.
Connect multiple wires that are 16-18 AWG
4-11/16
(1.31-0.82 sq. mm) with a wire nut. Include a pigtail
(119)
with this wire group and attach the pigtail to the
individual terminal block.
Wire the terminal block as follows:
1. For single wires, strip 3/16 in. (5 mm); for multiple wires
going into one terminal, strip 1/2 in. (13 mm) insulation
from the conductor.
2. If two or more wires (18 to 22 AWG only) are being
inserted into one terminal, twist the wires together
before inserting.
M29050
NOTE: When two or more wires are being inserted
3. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
4. Review and verify the terminal connection wiring and
DIP switch settings.
1.
STRIP 1/2 IN.
1/2
(13 MM) FROM
(13)
WIRES TO BE
ATTACHED AT
ONE TERMINAL.
M29054
2.
TWIST WIRES
TOGETHER
WITH PLIERS
(A MINIMUM OF
THREE TURNS).
Fig. 4. Attaching two wires (18 to 22 AWG) to
3
into one terminal, be sure to twist them
together. Deviation from this rule can result
in improper electrical contact. See Fig. 4.
CONTROLLER OR
RECEIVER
E-BUS CONNECTOR
TERMINALS
3.
CUT TWISTED END OF WIRES TO
3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING
SCREW. THEN PULL ON EACH WIRE
IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
receiver terminals.
M29055
62-0291—09