Maintenance Recommendation - ABB ACS1000 User Manual

Medium voltage ac drives air-cooled
Hide thumbs Also See for ACS1000:
Table of Contents

Advertisement

1
2
Figure 2-3: MCB opening timing diagram
(1) Short-circuit occurs
(2) Open and or trip command is set at the drive control output
(3) No further damage to the drive
(4) No hazard to personnel
(5) Maximum protection trip time
(6) Maximum safety trip time
In order to meet the stipulated safety requirements, ABB recommends of the following:
-
MCB equipped with 2 independent opening coils
-
MCB equipped with an opening coil and an undervoltage coil for monitoring of the control
voltage
-
Upstream protection coordination scheme is provided which uses the "breaker failure"
(ANSI 50BF) signal to automatically trip the upstream breaker, in case the MCB does
not open.
The upstream breaker must open within the maximum safety trip time after a failure
has occurred.
2.8.3

Maintenance recommendation

The MCB trip circuits should be checked annually.
3BHS213401 E01 REV H
3
5
6
ACS1000 AIR-COOLED USER MANUAL
02 IMPORTANT SAFETY INFORMATION
4
25/184