Mounting; Strain Relief Of Cablel; Seal Housing; Technical Data - Honeywell 015600.01 Mounting And Connection Instructions

Rf bus-2 wireless receiver
Table of Contents

Advertisement

Available languages

Available languages

Mounting and Connection Instructions RF BUS-2 wireless receiver
6.3

Mounting

6.3.1
Strain relief of cable
Before closing the housing, secure the cable with a cable tie at the provided pull relief (see in Chapter 3.)
6.3.2

Seal housing

Seal the housing after mounting, programming and testing correctly the system by pressing the plastic seal into the
screw opening on the front of the housing.
Ensure that the housing is closed and screwed correctly. Clean the seal (free from grease) and cover with the label
(VdS imprint). After attaching the plastic seal, the housing cannot be opened without destroying the seal.
7.

Technical data

Operating voltage U_b
Operating voltage range
Current consumption
Frequency range 1
Transmission power 1
Frequency range 2
Transmission power 2
Transmitting range
Installation position
Protection class as per DIN 40 050
Environmental class as per VdS
Operating temperature range
Storage temperatur range
Dimensions W x H x D
Antennas (L)
Colour
Hereby, the Novar GmbH declares that the radio equipment RF BUS-2 wireless receiver, Item no.
015600.01 is in compliance with Directive 2014/53/EU.
The full text of the EU declaration can be downloaded from our homepage https://www.security.honeywell.de/ in
the service/download area.
12 V DC, residual ripple 1 Vss
10 V DC to 15 V DC
typ. 15 mA
433,05...434,79 MHz
<10 mW
863...870 MHz
<25 mW
typ. 300 m by free visibility
arbitrary
IP 30
II
-10 °C to +55 °C
-25 °C to +70 °C
118 x 118 x 31 mm without antennas
75 mm
135 mm
traffic white (similar to RAL 9016)