SETUP
OUTPUTS
STG4/PUMP
POSTPURGE
Fig. 53. Setup Pump - Postpurge.
Fig. 54. Setup Pump - Exit.
SETUP
ALARMS
Fig. 55. Setup Alarms.
SETUP
ALARMS
HI ALARM
Fig. 56. Setup High Alarm.
T775P SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP
OUTPUTS
STG4/PUMP
POSTPURGE
0
SEC
ENTER
PUMP POST-
PURGE TIME
FOR
STG4/PUMP
M24679
SETUP
OUTPUTS
STG4/PUMP
RESET RT
PUMP OUT
EXERCISE
PREPURGE
POSTPURGE
EXIT
M24680
SETUP
ALARMS
HI ALARM
LO ALARM
DIF ALARM
EXIT
M24681
SETUP
ALARMS
HI ALARM
YES
NO
ENABLE
HIGH
LIMIT
ALARM
M24682
1.3.7.4. POSTPURGE
1. From the Stage/Pump menu, use the  and 
buttons to select POSTPURGE.
2. Press the  button to display the postpurge time.
3. Use the  and  buttons to increase/decrease the
postpurge time.
Default: 0 (zero) seconds
Range: 0 to 3600 seconds
4. Press the  button to accept the value and display
the Stage/Pump menu.
NOTE: A positive Postpurge time causes the pump
to run for the set number of seconds after the
last stage de-energizes.
1.3.7.5. Pump Exit
Press the  button (or highlight EXIT and press the 
button) to exit the current Stage/Pump menu and return to
the Outputs menu.
This completes the pump setup. Continue with "1.4. Setup
Alarms".

1.4. Setup Alarms

1. From the Setup menu, use the  and  buttons to
highlight the Alarms.
2. Press the  button to display the Alarms menu.
There are three alarms available, High, Low, and
Differential. When an alarm is selected, its alarm limit
selection displays on the Alarms menu.
When an alarm is active, the Digital Output (D.O.) closes
and "ALARM" displays on the home screen.
NOTE: Low and differential relay alarms require the
condition to prevail for 5 minutes before
contacts will close.

1.4.1. HIGH ALARM

Only Sensor A can be used to sense the high alarm
temperature. Sensor C cannot be used.
1. From the Alarms menu, use the  and  buttons to
select HI ALARM.
2. Press the  button to display the alarm options.
3. Use the  and  buttons to select YES or NO.
Default: NO
4. Press the  button to accept the value and display
the Alarms menu.
Selecting YES displays the HI LIMIT option on the Alarms
menu once you exit this screen. Continue with "1.4.1.1.
HIGH LIMIT" on page 24.
For systems with no high limit alarm, select NO, press
the  button, and continue with "1.4.2. LOW ALARM" on
page 24.