Section 4
IEC 60870-5-103 vendor specific implementation
4.2.1.5
4.2.2
4.2.2.1
4.2.2.2
4.2.2.3
34
Supported information types
Function commands in control direction, pre-defined I103CMD
Number of instances: 1
Function type is selected with parameter FunctionType .
Information number is defined for each output signals.
Info. no.
Message
16
Auto-recloser on/off
17
Teleprotection on/off
18
Protection on/off
IED commands for IEC 60870-5-103 I103IEDCMD
Functionality
I103IEDCMD is a command block in control direction with defined IED functions.
Function block
I103IEDCMD
BLOCK
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283-1-en.vsd
IEC10000283 V1 EN
Figure 14:
I103IEDCMD function block
Signals
Table 29:
I103IEDCMD Input signals
Name
Type
BLOCK
BOOLEAN
Table 30:
I103IEDCMD Output signals
Name
Type
19-LEDRS
BOOLEAN
23-GRP1
BOOLEAN
24-GRP2
BOOLEAN
25-GRP3
BOOLEAN
26-GRP4
BOOLEAN
Supported
Yes
Yes
Yes
Default
Description
0
Block of commands
Description
Information number 19, reset LEDs
Information number 23, activate setting group 1
Information number 24, activate setting group 2
Information number 25, activate setting group 3
Information number 26, activate setting group 4
1MRS757203 A
630 series