1MRS757203 A
4.1.4
4.1.4.1
4.1.4.2
4.1.4.3
4.1.4.4
Table 13:
I103EF Non group settings (basic)
Name
Values (Range)
FunctionType
630 series
Communication Protocol Manual
IEC 60870-5-103 vendor specific implementation
Table 11:
I103AR supported indications
Info. no.
Message
16
Autorecloser active
17
Teleprotection active
18
Protection active
128
CB on by Autorecloser
129
CB 'on' by long-time AR
130
Autorecloser blocked

Function status earth-fault for IEC 60870-5-103 I103EF

Functionality

I103EF is a function block with defined functions for earth fault indications in
monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.

Function block

I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290-1-en.vsd
IEC10000290 V1 EN
Figure 7:
I103EF function block

Signals

Table 12:
I103EF Input signals
Name
BLOCK
51_EFFW
52_EFREV

Settings

Unit
1 - 255
-
Supported
Yes
No
No
Yes
No
Yes
Type
Default
Description
BOOLEAN
0
Block of status reporting
BOOLEAN
0
Information number 51, earth-fault forward
BOOLEAN
0
Information number 52, earth-fault reverse
Step
Default
1
160
Section 4
Description
Function type (1-255)
23