6 Quick installation guide
Make sure that the voltage between the drive module input power terminals
(L1/U1, L2/V1, L3/W1) and the grounding (PE) busbar is close to 0 V.
Make sure that the voltage between the drive module UDC+ and UDC-
terminals and the grounding (PE) busbar is close to 0 V.
6.
Install temporary grounding as required by the local regulations.
7.
Ask for a permit to work from the person in control of the electrical installation work.

Select the power cables

Size the power cables according to local regulations to carry the nominal current given
on the type designation label of your drive.

Ensure the cooling and fuses (UL)

See the table below for the losses and cooling air flow through the drive. The allowed
operating temperature range of the drive without derating is -15 to +40 °C.
Drive type
ACQ580-505A-4
ACQ580-585A-4
ACQ580-650A-4
ACQ580-725A-4
ACQ580-820A-4
ACQ580-880A-4
For more information, see the hardware manual 3AXD5000004867748677 (English).

Protect the drive and input power cables

See the table above for the UL class fuses for branch circuit protection per NEC. Check
that the operating time of the fuse is below 0.1 seconds. Obey local regulations.

Install the drive module into a cabinet

See figure B on page 13:
Install the punched section to the back of the cabinet frame.
Remove the pedestal guide plate from the bottom of the drive module.
Install the support rails and pedestal guide plate to the cabinet bottom frame.
Install the telescopic insertion ramp to the pedestal guide plate.
For option +B051: See figure C on page 13:
Remove the sheeting from the clear plastic shrouds from both sides.
See figure D on page 13:
Install the mounting bracket to the drive module.
For option +B051:
Install the bottom grille to the drive module if there is no bottom plate in the
cabinet and degree of protection of IP20 is needed for the drive module from
the bottom side.
Air flow
Heat dissipation
3
ft
/min
W
707
5602
707
6409
707
8122
707
8764
707
9862
848
10578
Fuse
UL class
Type
T
JJS-600
L
A4BY800
L
A4BY800
L
A4BY800
L
A4BY900
L
A4BY1000