Westerm D20A: Jumpers; Westerm D20A: Jumper Settings - GE D20 Installation And Operation Manual

Hide thumbs Also See for D20:
Table of Contents

Advertisement

D20/D200
Installation and Operations Guide
Connections and Configuration
WESTERM
Jumper locations on the WESTERM D20A:
D20A: Jumpers
Z1
Z2
To set Module address jumpering on Z1, see "WESTERM Addressing", page 65.
Use jumpers:
Z2 to enable/disable low loop supply voltage sensing
Z3 and Z4 to set Analog loop supply.
WESTERM
The following table gives jumper settings for Z2, Z3 and Z4.
D20A: Jumper
Settings
Jumper
Jumper
Number
Position
Z2
1 – 2
1 – 2
Z3 & Z4
1 – 2
2 – 3
1 – 2 & 2 – 3
66
, continued
Z4
Z3
Jumper
Option 1
Setting
1A
IN
OUT
Option 2
2A
2B
IN
IN
OUT
994-0078-2.00-7
Jumper Definition – Low Loop Supply
1B
Enable bypass for low loop supply sensing
Disable bypass for low loop supply sensing
Jumper Definition – Analog Loop Supply
2C
Internal Analog loop supply provided by DC1 or
External Analog loop supply on TB1-1 & 3
Not required
GE Energy
DC2
General
Full

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D200

Table of Contents

Save PDF