INSTALLER SYSTEM-TEST

Use the Installer System-Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system-tests.
To start the system-test:
CAUTION
Equipment Damage Hazard.
Minimum compressor off-time is bypassed
during the Installer System Test.
Be aware that equipment damage can occur if the
compressor is cycled too quickly.
Press and hold the increase
the same time, until two zeros appear. All segments of the
LCD are displayed before the zeros appear.
Em Ht Temporary Setting
Aux Ht
Repl
Wait
Batt
System
Em HeatOffCool Auto Only
Key To
Test
Press
Number
Heating Equipment System-Test
i
10
11
12
11
10
Emergency Heating Equipment System-Test
i
20
21
20
Cooling Equipment System-Test
i
30
31
30
a
Available on select models.
and decrease
keys, at
Remote
Room
%Humid
Outdoor
Heat Cool
Fan
OnAuto
M4844
Table 4. Installer System-Test Options.
Enter heating equipment system-test.
Stage-one heat comes on. The system fan is also energized.
Stage-two heat comes on. Stage-one heat and system fan remain on.
Stage-two heat turns off.
Stage-one heat and system fan turn off.
a
Change from heating to emergency heating equipment system-test.
Emergency heat comes on. System fan also comes on.
Emergency heat turns off.
Change from heating or emergency heating to cooling equipment system-test.
Stage-one cooling and system fan come on.
Stage-one cool and system fan turn off.
MICROELECTRONIC HEAT PUMP THERMOSTAT
TEST NUMBER
NOTE: Press and hold the increase
keys for three seconds to exit the system-test.
The system-test times out after five minutes
without any key presses.
Table 3. Installer System-Tests.
Test
Number
10-19
Heating equipment can be turned on and off
20-29
Emergency heat (select models) equipment
can be turned on and off
30-39
Cooling equipment can be turned on and off
40-49
Fan equipment can be turned on and off
60-69
System key or system switch position test
70-79
Thermostat information displayed including
date code and software versions.
Refer to Table 4 for descriptions of the specific tests.
Description
7
and decrease
System-Test Description
M6792
(continued)
69-0961—4